HomeMy WebLinkAbout7378b.gro (fnl) dated 10-22-19 GEOTECHNICAL REPORT OF GRADING
KUMAR CONVENIENCE MART
301 NORTH MAIN STREET
CITY OF LAKE ELSINORE
RIVERSIDE COUNTY, CALIFORNIA
ac '� •
f
MR. R KUMAR
401 EAST 6TH ET
CORONA, CALIFORNIA 92879
W.O. 7378-B-SC OCTOBER 22,2019
•
A49
MOP 6 lk
tQ0
•is • P�tIIV•SAPy
197�9 /
Geotechnical • Geologic • Coastal • Environmental
26590 Madison Avenue • Murrieta, California 92562 • (951) 677-9651 • FAX (951) 677-9301 • www.geosoilsinc.com
October 22, 2019
W.O. 7378-B-SC
Mr. Raj Kumar
401 East 6t" Street
Corona, California 92879
Subject: Geotechnical Report of Grading, Kumar Convenience Mart, 301 North Main
Street, City of Lake Elsinore, Riverside County, California
Dear Mr. Kumar:
In accordance with your request, GeoSoils, Inc. (GSI) is providing this geotechnical report
of grading for the subject building pad, Kumar Convenience Mart, 301 North Main Street,
City of Lake Elsinore, Riverside County, California. Grading of the new building pad area
began on October 12, 2019 and was substantially completed on October 16, 2019. Based
on the observations and testing performed by GSI, it is our opinion that the graded building
pad appears suitable for it's intended commercial use. Unless specifically superceded by
recommendations presented herein, the recommendations and conclusions contained in
the referenced reports by GSI (see Appendix A) remain pertinent and applicable, and
should be appropriately implemented, as warranted.
ENGINEERING GEOLOGY
The geologic conditions exposed during the process of grading were observed on a
part-time basis by representatives from our firm. Observations during the process of
grading included removals of weathered and loose, potentially compressible near surface
artificial fill, and young alluvial fan deposits to competent fan deposits, as well as fill
placement, along with the typical grading procedures of the contractor, in general
accordance with the referenced preliminary geotechnical investigation for the site
(GSI, 2018b). The earth materials encountered during the process of grading within the
project included near surface artificial fills and young alluvial fan deposits and were
generally as indicated within the referenced report by GSI (2018b).
PURPOSE OF EARTHWORK
The purpose of the grading was to remove and recompact near-surface weathered soils,
and provide a relatively level building pad for the proposed commercial construction
(Kumar Convenience Mart), along with associated infrastructure and underground utility
improvements. Typical cut/fill grading techniques were utilized to attain the desired graded
configurations.
EARTHWORK CONSTRUCTION
Earthwork operations have been completed in general accordance with recommendations
provided in the field based upon conditions exposed and/or in accordance with the
recommendations provided in the referenced report by GSI (2018b).
Preparation of Existing Ground
1. Deleterious material, such as concentrated organic matter, and miscellaneous
debris, etc., were stripped from the surface and disposed of offsite, prior to grading
and subsequent fill placement. The locations, elevations, and limits of proposed
improvements were provided by others.
2. Potentially compressible and weathered near surface artificial fills and young alluvial
fan deposits were removed to the limits indicated in the approved referenced report
(GSI, 2018b).
3. After surficial removals of weathered near surface materials had been completed,
bottom tests were performed on the existing in-place young alluvial fan deposits to
evaluate if potentially compressible materials had been removed. Bottom testing
indicated that the in-situ native materials, below the recommended removals, were
above minimum density requirements of 105 pcf. Bottom tests are included in the
enclosed Table 1 at the end of this report.
4. Subsequent to the above removals,the exposed subsoils were scarified to a depth
of about 6 inches, brought to at least optimum moisture content, then compacted
to a minimum relative compaction of 90 percent of the laboratory standard
(ASTM D 1557).
5. All processing of original ground was observed by a representative of GSI.
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 2
Fill Placement
In areas that received fill, soils consisting of native onsite earth materials were placed in
6-to 8-inch lifts, watered, and mixed to achieve at least optimum moisture conditions, and
compacted to a minimum relative compaction of 90 percent of the laboratory standard
(ASTM D 1557) utilizing a heavy earth scraper, skid-steer loader, and fire hose. Fill
materials were placed in general accordance with the approved earthwork guidelines for
the site (GSI, 2018b). The approximate minimum to maximum depth of fill placed during
site grading is presented in the attached Table 2.
Field Testing
1. Field density tests were performed using the nuclear (densometer) methods
ASTM D 6938-10 (Procedure A), and the sand-cone method ASTM D 1556. The test
results are presented in the enclosed Table 1 . The approximate locations of the
bottom tests and field density tests taken during the precise grading operations are
shown on Figure 1 , which utilize the 20-scale precise grading plans prepared by
Love Engineering, Inc. (LEI, 2016).
2. Field density tests were taken at periodic intervals and selected locations to check
the compactive efforts provided by the contractor. Where test results indicated less
than optimum moisture content, or less than 90 percent relative compaction, the
contractor was notified and the area was reworked until retesting indicated at least
optimum moisture conditions and a minimum relative compaction of 90 percent
were attained. Based upon the grading operations observed, the test results
presented herein are considered representative of the compacted fill.
3. Visual classification, supplemented by laboratory testing, was the basis for
evaluating which maximum density value to use for a given density test.
Groundwater and Seepage
No perched water or seepage was encountered during grading operations in the areas
under the purview of this report. Generally, and based upon the available data to date,
regional groundwater is not expected to be a major factor in the development of the site.
However, perched groundwater and/or seepage may occur in the fill due to migration from
drainage areas and development during and/or after periods of above normal or heavy
precipitation or irrigation. This potential increases on shallow fill pads. Thus, perched
groundwater conditions and/or seepage may occur in the future, and should be
anticipated. These observations reflect site conditions at the time of this report and do not
preclude changes in local groundwater conditions in the future. If in the future, perched
water conditions are observed due to excessive irrigation, precipitation,or otherfactors not
obvious during site grading, GSI should be contacted for recommendations for mitigation.
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 3
76.67 E- (77.21 EG) - -_ I `° wR S,w �v -
- - a (77.21 EC)
711,
- � 20 'C 0 20 40 1273'/2
I I 7.00 EG TE 1273'/2 FX-18.-. 7(-21 X 12 BT 2 I SCALE 1X-7 LLJ
000 1.2% BT-3BT 1 X 15 I ;. I GSI LEGEND
I � ri � � � r` oo ;� X-16
n rn 00 ..� X-10
Iv ' v 06 3 aD ao ao ao 5 a) PROP FOODMA;?'
r- a6 r` X 13 AfC PE=79.00
78.52 FS r- 78.64 00 GAL FF=79.67 X 8 I Afc Artificial Fill - Compacted
PROPANE
N H LJ�
,2�� LOT 1 TANK X-22 Qyf X-20 BT_6 I Qyf Pleistocene-age Young Alluvial Fan Deposits,
I ; ;� , _ , Circled where Buried
• X-14 _
oo O 12 LL
BT-4 X-9 -1 'Ij BT-6 Approximate Location of Remedial Removal
n ^ 0D o I PROP X-11 I Bottom Test
1 v.� I I `^^, r^. • ol", WALL
X-22 Approximate Location of Field Density Test
1 I 78.45 EG �2� •• �7 z2 X-17 BT-5 X-19
W ( ) F.. I 1273Yz Approximate Elevation of Remedial Removal
• \-71 1273'/2 n 1273'/2 I u � Bottom
7 •( 8.69 EG)
L I - Area Under the Purview of this Report
�J (78.81 EG) 80.00 FS
I
I 179.65 FS
LZ u
L
LLJ CN
I N o
7 � M a?I o L` • 80.35 FS
00 rn
l � � i 79.23 FS 80.15 FS Is
00 CIO
ao ao _ -00 r-
--j r` 79.40 •• fcc--c
(81.00 EG)
7960 3S 80.77 FS
w 80.31 FS
J L 80.29 FS
L) cc
� ^ 80.00 FS 2 1 1 1 1 1 1 1
_ 80.45 FS _
j 1.3% • • 128 r10
r- LL_ cn n 1.5x 82.15 FS
17! i s1.65 FS 82.3 /HIP z ALL LOCATIONS ARE APPROXIMATE
rn °' __ _ 81.80 EG)
81.84 EG) 82.22 EG) ° (82.52 EG) This document or e file is not part of the Construction
Documents and should not be relied upon as being an
(80.34 EG) (80.57 EG) _ �-(82.17 EG) accurate depiction of design.
�Attr --- ---- N 18'28'04"E 100.04'17 - - i a�--- N 18'28'04"E i 00.04' - - -
i PREPARED BY: LOVE ENGINEERING s1,42TC T PRO p 82.0 TC)
,�,
PLANNING - ENGINEERING - SURVEYING CITY OF LAKE ELSINORE HEET 2 (80.92 FL) W=40 2 (81.5 FL)
31915 Rancho California Road, Suite 200-166, Temecula, CA 92591 11.18 TC) (81.39 TC) 81.86 TC)
TEL (951) 440 - 8149 / FAX (951) 303 - 6701 KUMAR CONVENIENCE CENTER 2 o.ss FL) (ac.89 FL) (81.36 FL FIELD DENSITY TEST LOCATION MAP
301 N MAIN ST :F ,HEETs
LAKE ELSINORE, CA 92530 FILE r,:: MAIN STREET Figure 9
THOMASS.LOVE DATE PRECISE GRADING PLAN Figure adapted from Precise Grading Plan by Love Engineering, Inc.2016. W.O.7378-B-SC DATE:10/19 SCALE: See Bar Scale
LABORATORY TESTING
Maximum Density Testing
The laboratory maximum dry density and optimum moisture content for the major soil type
encountered was evaluated in general accordance with test method ASTM D 1557. The
following table presents the results:
MAXIMUM DRY OPTIMUM MOISTURE
SOIL TYPE DENSITY (pcf) CONTENT (%)
A - Brown, Clayey SAND 133.5 7.7
B - Light Brown, Silty SAND 132.0 10.1
Expansion Potential
Expansion Index (E.I.) testing was performed subsequent to grading for the typical
foundation soil type exposed at pad grade, in general accordance with the 2016 California
Building Code ([2016 CBC], California Building Standards Commission [CBSC], 2016).
Based on the test results obtained (<5), the expansive potential of the soils for the subject
building pad may be classified as very low (i.e., E.I. between 0 to 20).
Soluble Sulfates/Corrosivity
Subsequent to site grading, a typical sample of the site earth materials was analyzed for
soluble sulfate and corrosion potential. Based upon the soluble sulfate test results and the
American Concrete Institute (ACI, 2014a), the soluble sulfate content for the subject
building pad is considered Class "SO" (0.00 to 0.10 Water-Soluble Sulfate in Soil,
Percentage by Mass). As such, sulfate-resistant concrete is not required for these specific
conditions. The soluble sulfate results are indicated in the table below:
SAMPLE ID-F-SAMPLE H CHLORIDE SULFATE RESISTIVITY
DEPTH (FT.) p (ppm) % BY WEIGHT (ohm-cm)
Building Pad I 0-1.5' I 7.3 I 170 I 0.0230 890
Based on the results of the resistivity and pH testing,the onsite soils are considered neutral
(a pH between 6.6 and 7.3 is considered neutral) and are considered severely corrosive
toward ferrous metals in a saturated state (below 1,000 ohm-cm is considered severely
corrosive). Chloride testing yielded a concentration of 170 parts per million (ppm), which
is somewhat elevated.
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 5
Although the site soils are generally categorized as being severely corrosive toward ferrous
metals in a saturated state, other than Exposure Classes SO and C1, no other exposure
conditions are indicated in Table 19.3.1 .1 of the ACI (2014a) were warranted. It is our
understanding that ferrous metals embedded in properly placed and formed concrete
should be adequately protected from these conditions. Typical development of this type
does not generally use significant amounts of exposed metal piping and/or other buried
metal improvements. Based on the conditions encountered, a consulting corrosion
engineer should be considered to provide recommendations for foundations, piping, etc.,
as warranted.
SEISMIC SHAKING PARAMETERS
The following table summarizes the reevaluated site-specific design criteria obtained from
the 2016 CBC, Chapter 16 Structural Design, Section 1613, Earthquake Loads. The
computer program Seismic Design Maps, provided by the California Office of Statewide
Health Planning and Development (OSHPD, 2019) has now been utilized to aid in design
(https://seismicmaps.org). The short spectral response utilizes a period of 0.2 seconds.
2016 CBC SEISMIC DESIGN PARAMETERS
PARAMETER VALUE 2016 CBC
REFERENCE
Risk Category I, II, or III Table 1604.5
Site Class D Section 1613.3.2/ASCE 7-10
(p. 203-205)
Spectral Response F2.349(0.2 sec), Ss g Section 1613.3.1
Figure 1613.3.1(1)
Spectral Response- (1 sec), S, 0.945 g Section 1613.3.1
Figure 1613.3.1(2)
Site Coefficient, Fa 1.0 Table 1613.3.3(1)
Site Coefficient, F, 1.5 Table 1613.3.3(2)
Maximum Considered Earthquake Spectral 2.349 g Section 1613.3.3
Response Acceleration (0.2 sec), SMs (Eqn 16-37)
Maximum Considered Earthquake Spectral 1.4179 Section 1613.3.3
Response Acceleration (1 sec), S1V11 (Eqn 16-38)
5% Damped Design Spectral Response 1.566 g Section 1613.3.4
Acceleration (0.2 sec), Sps (Eqn 16-39)
5% Damped Design Spectral Response 0.945 g Section 1613.3.4
Acceleration (1 sec), SD1 (Eqn 16-40)
PGAM 0.928g ASCE 7-10 (Eqn 11.8.1)
Seismic Design Category(') E Section 1613.3.5/ASCE 7-10
Table 11.6-1 or 11.6-2
Mr. Raj Kumar W.O. 7378-13-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 6
GENERAL SEISMIC PARAMETERS
PARAMETER VALUE
Distance to Seismic Source-A fault** 2.2 mi (3.5 km)*
Upper Bound Earthquake (Elsinore-Glen Ivy/Temecula Fault) M, = 6.8**
FBlake (2000a)
ao, et al. (2003)
Conformance to the criteria above for seismic design does not constitute any kind of
guarantee or assurance that significant structural damage, ground failure, or surface
manifestations will not occur in the event of a large earthquake in this region. The primary
goal of seismic design is to protect life, not to eliminate all damage, since such design may
be economically prohibitive. Cumulative effects of seismic events are not addressed in the
2016 CBC and regular maintenance and repair following locally significant seismic events
(i.e., MW 5.5) will likely be necessary.
It is important to keep in perspective that in the event of a maximum probable or credible
earthquake occurring on any of the nearby major faults, strong ground shaking would
occur in the subject site's general area. Potential damage to any structure(s) would likely
be greatest from the vibrations and impelling force caused by the inertia of a structure's
mass. This potential would be no greater than that for other existing structures and
improvements in the immediate vicinity.
CONCLUSIONS AND RECOMMENDATIONS
Based on the recent grading conducted and testing performed by GSI, it is our opinion that
the subject building pad appears suitable for its intended commercial use from a
geotechnical viewpoint. Recommendations for foundation design,foundation construction
(mat slab systems), soils moisture transmission considerations, wall design, and
development criteria, etc. have been previously provided within our limited evaluation of
surficial soil conditions report (GSI, 2018b). Based on the observations, testing, and
laboratory data obtained at the conclusion of site grading, the conclusions and
recommendations previously presented by GSI (2018b) are considered valid and
applicable. All other findings, conclusions and recommendations in previous referenced
reports by GSI remain pertinent and applicable, except as specifically superceded herein.
GSI should review foundation plans, prior to construction.
Mr. Raj Kumar W.O. 7378-13-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 7
SUMMARY OF RECOMMENDATIONS REGARDING
GEOTECHNICAL OBSERVATION AND TESTING
We recommend that observation and/or testing be performed by GSI at each of the
following construction stages:
• During grading/recertification.
• During excavation.
• During placement of subdrains, toe drains, or other subdrainage devices, prior to
placing fill and/or backfill.
• After excavation of building footings, retaining wall footings, and free standing walls
footings, prior to the placement of reinforcing steel or concrete.
• Prior to pouring any slabs or flatwork, after presoaki ng/presatu ration of building
pads and other flatwork subgrade, before the placement of concrete, reinforcing
steel, capillary break (i.e., sand, pea-gravel, etc.), or vapor retarders.
• During retaining wall subdrain installation, prior to backfill placement.
• During placement of backfill for area drains, interior plumbing, utility line trenches,
and retaining wall backfill.
• During slope construction/repair.
• When any unusual soil conditions are encountered during any construction
operations, subsequent to the issuance of this report.
• When any developer or owner improvements, such as flatwork, foundations, walls,
etc., are proposed, prior to construction. GSI should review and approve such
plans, prior to construction.
• A report of geotechnical observation and testing should be provided at the
conclusion of each of the above stages, in order to provide concise and clear
documentation of site work, and/or to comply with Code requirements.
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 8
OTHER DESIGN PROFESSIONALS/CONSULTANTS
The design civil engineer, structural engineer, foundation designer, architect, landscape
architect, wall designer, etc., should review the recommendations provided herein,
incorporate those recommendations into all their respective plans, and by explicit
reference, make this report part of their project plans.
This report presents minimum design criteria for the design of slabs,foundations and other
elements possibly applicable to the project. These criteria should not be considered as
substitutes for actual designs by the structural engineer/designer. Please note that the
recommendations contained herein are not intended to preclude the transmission of water
or vapor through the slab or foundation. The structural engineer/foundation and/or slab
designer should provide recommendations to not allow water or vapor to enter into the
structure so as to cause damage to another building component, or so as to limit the
installation of the type of flooring materials typically used for the particular application, per
the State of California (2019).
The structural engineer/designer should analyze actual soil-structure interaction and
consider, as needed, bearing, expansive soil influence, and strength, stiffness and
deflections in the various slab, foundation, and other elements in order to develop
appropriate, design-specific details. As conditions dictate, it is possible that other
influences will also have to be considered. The structural engineer/designer should
consider all applicable codes and authoritative sources where needed. If analyses by the
structural engineer/designer result in less critical details than are provided herein as
minimums,the minimums presented herein should be adopted. It is considered likely that
some, more restrictive details will be required.
If the structural engineer/designer has any questions or requires further assistance, they
should not hesitate to call or otherwise transmit their requests to GSI. In order to mitigate
potential distress, the foundation and/or improvement's designer should confirm to GSI
and the governing agency, in writing,that the proposed foundations and/or improvements
can tolerate the amount of differential settlement and/or expansion characteristics and
other design criteria specified herein.
PLAN REVIEW
Final project plans (foundation, block wall, landscaping, etc.), should be reviewed by this
office prior to construction, so that construction is in accordance with the conclusions and
recommendations of this report. Based on our review, supplemental recommendations
and/or further geotechnical studies may be warranted.
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 9
LIMITATIONS
The materials encountered on the project site and utilized for our analysis are believed
representative of the area; however, soil and bedrock materials vary in character between
excavations and natural outcrops or conditions exposed during mass grading.
Site conditions may vary due to seasonal changes or other factors.
Inasmuch as our study is based upon our review and engineering analyses and laboratory
data, the conclusions and recommendations are professional opinions. These opinions
have been derived in accordance with current standards of practice, and no warranty,
either express or implied, is given. Standards of practice are subject to change with time.
GSI assumes no responsibility or liability for work or testing performed by others, or their
inaction; or work performed when GSI is not requested to be onsite, to evaluate if our
recommendations have been properly implemented. Use of this report constitutes an
agreement and consent by the user to all the limitations outlined above, notwithstanding
any other agreements that may be in place. In addition, this report may be subject to
review by the controlling authorities. Thus, this report brings to completion our scope of
services for this portion of the project.
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 10
The opportunity to be of service is sincerely appreciated. If you should have any
questions, please do not hesitate to contact our office.
Respectfully submitted, \,VpFE3s/0*
AI GFD �Qti��p VTSk 'f1,ell
GeoSoils, Inc. `��000A'cRF���N NA
a No.2377 N' No. RCE 47 57
Certified 7t Exp. I 1 �c
N Engincering .�
Todd A. Greer �F01 `FOP David W. keII gTFOF CA'�ef®Q
Engineering Geologist, C Civil Engineer, RCE 4785
TMP/TAG/JPF/DWS/jh
Enclosures: Table 1 - Field Density Test Results
Table 2 - Lot Summary - As-Graded Conditions
Appendix A - References
Appendix B - Laboratory Data
Distribution: (3) Addressee (2 wet signed for governing agency)
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October 22, 2019
File:a\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 11
Table 1
FIELD DENSITY TEST RESULTS
TEST ,gATE .TEST LOCATION. TRACT ELEV .MOISTURE DRV. REL .TEST. SOIL.
NO. NO.- Of; CONTENT DENSITY COMP METHOD TYPE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEPTH (ft) (%)
Grading
BT-1 10/12/19 Building Pad NW Main St. 1263.5 5.7 107.3 ND
BT-2 10/12/19 Building Pad NW Corner Main St. 1263.5 6.1 107.7 ND
BT-3 10/12/19 Building Pad NW Main St. 1263.5 6.7 108.8 ND
BT-4 10/14/19 Building Pad Main St. 1263.5 12.3 106.1 ND
BT-5 10/14/19 Building Pad Main St. 1263.5 7.8 108.2 ND
BT-6 10/14/19 Building Pad Main St. 1263.5 5.3 108.5 ND
7 10/14/19 Building Pad Main St. 1 1265.0 11.2 119.7 90.7 1 ND B
8 10/14/19 Building Pad Main St. 1265.0 10.2 120.3 91.2 SC B
9* 10/14/19 Building Pad Main St. 1265.0 10.0 116.5 88.3 ND B
9A 10/14/19 Building Pad Main St. 1265.0 10.4 119.8 90.8 ND B
10 10/14/19 Building Pad Main St. 1266.0 10.8 120.5 91.3 ND B
11 10/15/19 Building Pad Main St. 1266.0 11.1 122.9 93.1 SC B
12 10/15/19 Building Pad Main St. 1 1266.0 8.3 123.6 92.6 1 ND A
13 10/15/19 Building Pad Main St. 1266.0 7.9 122.1 91.5 ND A
14 10/15/19 Building Pad Main St. 1267.0 12.1 119.3 90.4 ND B
15 10/15/19 Building Pad Main St. 1267.0 11.8 121.2 91.8 ND B
16 10/16/19 Building Pad Main St. 1267.0 11.4 120.5 91.3 ND B
17 10/16/19 Building Pad Main St. 1267.0 10.6 119.7 1 90.7 SC B
18 10/16/19 Finish Grade Bulding Pad Main St. FG 11.0 122.5 92.8 ND B
19 10/16/19 Finish Grade Bulding Pad Main St. FG 11.3 120.9 91.6 ND B
20 10/16/191 Finish Grade Bulding Pad Main St. FG 11.1 123.4 93.5 ND B
21 10/16/191 Finish Grade Bulding Pad Main St. FG 10.8 121.4 92.0 ND f__qB22 10/16/19 Finish Grade Bulding Pad Main St. FG 10.5 122.3 92.7 ND
LEGEND
* = Failing Test
A= Retest
BT= Bottom Test
FG = Finish Grade
ND = Nuclear Densometer Test
SC = Sand Cone Test
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October,2019
File:C:\excel\tables\7300\7378b.gro Tbl1 GeoSoils, Inc. Page 1
Table 2
LOT SUMMARY - AS-GRADED CONDITIONS
MiNiMuM!'�;-MAXiMU;M")'•;EXPANSION POTENTIAL(2r•••••'•••SOLUBLE' SATURATED'RESISTIVITy
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L•OT . .DEPTH . . .REPTH . . . . . . . . . . . . . . . . . . . . .SULFATE . . . .•CHi ORIDE -P
LASTICITY.-.•.-.-.-AND•.•.•.•.•.•.•.(F.ERRQU.S.METAL•S).
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............. ....................... . . .'..•'...'..•.'.
.NUMBER. .'OF'FILL•..'..OF.FILL•..'EXPANSION' ' ASTM/CBC• -USDA •'.•'.•.'•'.•'.•.'.'..'.•.'.'..'.•.'.'..'.•.'.
:.:(ft}; ; :(##) ; :�IVDI=X:.:. .:.GLr4SS.: ;{%:bjr VV#) CLASS.�3J. . �pPm). . . . . . . . . . . . .CLASS csr.:.:.:.:•(olim-crji) ; .CRTEGORYt'?
Bldg. Pad 5'/2 51/2 0 Very Low 0.0230 SO 170 NP 7.3 Neutral 890 Severely
Corrosive
(1) All field measurements approximate (5) Plasticity Index per ASTM 4318 and CBC(2016) NP= Non-Plastic ND*=No Detection
(2) Test and Classification per ASTM D 4829 and CBC(2016) (6) pH per CTM 643 and Classification per USDA(1993)
(3) Classification per Table 19.3.1.1 of ACI(2014a)and CBC(2016) (7) Corrosivity to ferrous metals only,per CTM 643. There are no exposure conditions that relate to Tables
(4) Chloride Content as per CTM 422 19.3.1.1 or 19.3.2.1 of ACI(2014a)
Mr. Raj Kumar W.O. 7378-B-SC
Kumar Convenience Mart, Lake Elsinore October, 2019
File:c:\excel\tables\7300\7378b.gro Tb12.xIs Page 1
APPENDIX A
REFERENCES
GeoSoils, Inc.
APPENDIX A
REFERENCES
American Concrete Institute, 2014a, Building code requirements for structural concrete
(ACI 318-14), and commentary (ACI 318R-14): reported by ACI Committee 318,
dated September.
2014b, Building code requirements for concrete thin shells (ACI 318.2-14), and
commentary (ACI 318.2R-14), dated September.
American Society of Civil Engineers, 2010, Minimum design loads for buildings and other
structures, ASCE Standard ASCE/SEI 7-10.
California Building Standards Commission, 2016a, California Building Code, California
Code of Regulations,Title 24, Part 2,Volume 2 of 2, based on the 2015 International
Building Code, 2016 California Historical Building code, Title 24, Part 8, 2016
California Existing Building Code, Title 24, Part 10, and the 2015 International
Existing Building Code.
2016b, California Building Code, California Code of Regulations, Title 24, Part 2,
Volume 1 of 2, Based on the 2015 International Building Code.
California Office of Statewide Health Planning and Development (OSHPD), 2019, Seismic
design maps, https://seismicmaps.org/.
Cao, T., Bryant, W.A., Rowshandel, B., Branum, D., and Wills, C.J., 2003,The revised 2002
California probabilistic seismic hazard maps, dated June,
http://www.conservation.ca.gov/cgs/rghm/psha/fault_parameters/pdf/Documents
/2002_CA_Hazard_Maps.pdf.
County of Riverside Transportation and Land Management Agency, Building and Safety
Department, Planning Department, Transportation Department, 2000, Technical
guidelines for review of geotechnical and geologic reports.
Desert Design, 2016, Kumar convenience mart site plan, 1 sheet, scale: 3/32" = 1',
dated March.
GeoSoils, Inc., 2019, Foundation plan and calculation review,
proposed Kumar Convenience Mart, 301 North Main Street, City of Lake Elsinore,
Riverside County, California, W.O. 7378-Al-SC, dated April 29.
2018a, Response to commercial plan corrections, proposed Kumar Convenience
Mart, 301 North Main Street, City of Lake Elsinore, Riverside County, California,
W.O. 7378-Al-SC, dated June 7.
GeoSoils, Inc.
2018b, Preliminary geotechnical investigation, 301 North Main Street,
proposed Kumar Convenience Mart, City of Lake Elsinore, Riverside County,
California, W.O. 7378-A-SC, dated January 16.
Kanare, Howard M., 2005, Concrete floors and moisture, Engineering Bulletin 119,
Portland Cement Association.
Love Engineering, Inc., 2016, Precise grading plan Kumar convenience center, in the
City of Lake Elsinore, 2 sheets, various scales, dated April 10.
2006, Elsinore Valley Municipal Water District, Kumar Convenience Center,
water and sewer improvement plans, in the City of Lake Elsinore, 3 sheets, plotted
September 22.
Peyton-Tomita &Associates, LLC, 2018, Kumar Convenience Mart, 301 N. Main St., Lake
Elsinore, CA, 10 Sheets, J.N. DS201501 , delta revision 3, dated March 6.
State of California, 2019, Civil Code, Sections 895 et seq.
Mr. Raj Kumar Appendix A
File:e:\wp10\murr\sc7300\7378b.gro GeoSoils, Inc. Page 2
APPENDIX B
LABORATORY DATA
GeoSoils, Inc.
SailEar
CORROSION&THERMAL SCIENCES
42184 Remington Ave,Temecula CA 92560
ph(951)795-3135 • fx(951)894-2683
Work Order No. : 19J1141
Client: GeoSoils, Inc.
Project No. : W.O. 7378-B-SC
Project Name: Kumar Conv. Mart - Lake Elsinore CA
Report Date: October 22, 2019
Laboratory Test(s) Results Summary
The subject soil sample was processed with the U.S. Standard No. 10 Sieve and tested for pH
(ASTM G 51-95 2012), Soil Resistivity (ASTM G 57-06 2012), Sulfate Ion Content (ASTM D 516-16)
and Chloride ]on Content (ASTM D 512-12B). The test results follow:
As Rec'd Saturated Sulfate Chloride
Sample Identification (H") Resistivity Resistivity Content Content
(ohm-cm) (ohm-cm) (mg/L) (mg/L)
Sample E-1 @ 0-18" 7.3 31,000 890 230 170
*ND=No Detection
We appreciate the opportunity to serve you. Please do not hesitate to contact us with any
questions or clarifications regarding these results or procedures.
Ahmet K. Kaya, Laboratory Manager
ulr" Form No. 1-PR
�fiA«o�� WWW SOlICOr.COl77 Rev. 08/2019