HomeMy WebLinkAboutCOLLIER AVE 18310 (2)HVAC GENERAL SPECIFICATIONS HVAC GENERAL NOTES 30. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, TRANSITIONS, DAMPERS, VALVES AND OTHER DEVICES REQUIRED FOR A 1. EVERY DUCT AND PLENUM WHICH IS A PORTION OF THE COMFORT HEATING 1. ALL WORK SHALL CONFORM TO 2016 CAUFORNIA MECHANICAL CODE, COMPLETE WORKABLE INSTALLATION. AND/OR COOLING SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THE CALIFORNIA BUILDING CODE AND ALL OTHER APPLICABLE CITY CODES CALIFORNIA MECHANICAL CODE AND/OR CALIFORNIA ADMINISTRATIVE CODE. THE AND REGULATIONS, INCLUDING CALIFORNIA ENERGY CONSERVA- 31. AUTOMATIC FIRE DAMPER REQUIREMENTS ARE AS FOLLOWS: CONSTRUCTION, INSULATION AND SUPPORT OF EVERY DUCT AND PLENUM SHALL TION STANDARDS. A) PROVIDE AUTOMATIC FIRE DAMPERS AT ALL PENETRATIONS OF COMPLY WITH LOCAL CODE. FIRE -RATED CEILINGS AND WALLS THROUGHOUT. CONTRACTOR 2. THE CONTRACTOR SHALL PAY FOR ALL PERMITS AND FEES. SHALL COORDINATE WITH FIRE -RATED CEILING AREAS AND WALLS 2. CONCEALED SPACES, CIRCULATION AIR AS INDICATED ON ARCHITECTURAL DRAWINGS. THIS NOTE SHALL 3. CONTROL LOW VOLTAGE WIRING BY MECHANICAL CONTRACTOR AND TAKE PRECEDENCE OVER ANY OMISSIONS ON THE DRAWINGS. SEE CONDUIT BY ELECTRICAL CONTRACTOR. SPECIFICATIONS. INSULATED WIRES, PLASTIC TUBING OR PIPING, PIPE INSULATION, 4. CONDENSATE DRAIN PIPING AND FINAL CONNECTION TO UNIT BY B ) LOCATION OF FIRE -RATED CEILINGS AND WALLS ARE AS CONDENSATE PAN INSULATION, WOOD, PVC, ABS AND OTHER PLASTICS) PLUMBING CONTRACTOR. INDICATED ON THE ARCHITECTURAL DRAWINGS. TO BE IN CONCEALED SPACES USED TO CONVEY CIRCULATING AIR SUPPLY. WHEN COMBUSTIBLE MATERIAL IS TO BE LOCATED IN THE ABOVE SPACES, 5. REDWOOD SLEEPER OR PLATFORM FOR ROOF MOUNTED UNIT, DUCT 32. ALL HVAC EQUIPMENT SHALL BE CERTIFIED BY THE CALIFORNIA ENERGY IT SHALL BE APPROVED FOR SUCH INSULATION. PENETRATION, CUTTING AND PATCHING BY GENERAL CONTRACTOR, COMMISION TO COMPLY WITH LOCAL EFFICIENCY STANDARDS. 3. INSULATION OF DUCTS UNLESS OTHERWISE NOTED ON PLAN. 33. ALL CEILING DIFFUSERS ARE 4-WAY UNLESS OTHERWISE NOTED. DIFFUSERS 6. CONNECT MAIN DUCT TO AIR CONDITIONING UNIT WITH WEATHERPROOF AND REGISTERS SHAD_ BE KRUEGER, ADP, ANEMOSTAT OR EQUAL. EVERY CONDITIONED AIR SUPPLY AND PLENUM SHALL BE INSULATED WITH FLEXIBLE CONNECTION. SUN SHIELD OVER ENTIRE FLEXIBLE CONNECTION NO LESS THAN THE AMOUNT OF INSULATION INDICATED BELOW EXCEPT IS REQUIRED IF FLEXIBLE CONNECTION IS EXPOSED TO WEATHER. ALL HVAC UNITS OR SYSTEMS SERVING A COMMON AIR SPACE MUST FOR DUCTS AND PLENUMS USED FOR EVAPORATIVE COOLING SYSTEMS.) BE INTERCONECTED TO SHUT DOWN IMMEDIATELY UPON ALARM ONLY APPROVED MATERIALS SHALL BE USED WITHIN DUCTS OR PLENUMS 7. THERMOSTAT SHALL BE 24 VOLT, ONE STAGE HEATING AND ONE OR TWO CONDITION FROM DUCT DETECTORS (OR FIRE ALARM SYSTEM WHEN FOR INSULATING, SOUND DEADENING OR OTHER PURPOSES. STAGE COOLING WITH MATCHING SUBBASE AND TAMPER PROOF COVER. USING AREA SMOKE DETECTORS IN LIEU OF DUCT DETECTORS ) WITHOUT INTERFERENCE FROM EMS OR ANY OTHER SYSTEMS. ALL CONTROL RELAYS USED FOR SHUT DOWN MUST BE CAUOFORNIA 8. PROVIDE FILTER FOR AIR CONDITIONING AND/OR AIR SIDE UNITS AS STATE FIRE MARSHAL LISTED FOR RELEASING SERVICE. DUCT LOCATION INSULATION TYPE REQUIRED PER ASHRAE AND MECHANICAL CODE. COOLING ONLY HEATING ONLY 35. ALL HVAC AND FAN UNITS SHOWN ON THE PLAN IS RECOMMENDED. ROOF OR EXPOSED TO OSA C & W A & W 9• THE CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR FOR FINAL MAKE AND MODEL OF THE UNITS WILL BE DETERMINED BY ATTICS BETWEEN AND UNDER SIZE AND LOCATION OF DUCTWORK ROOF OPENINGS AND WITH ELECTRICAL THE OWNER/MECHANICAL CONTRACTOR WITH AN APPROVAL FROM THE FLOOR CRAWL SPACES AND A A CONTRACTOR FOR ELECTRICAL REQUIREMENTS OF ALL MECHANICAL MECHANICAL ENGINEER. BASEMENTS EQUIPMENT AND ARCHITECTURAL DRAWINGS FOR AIR DISTRIBUTION 36. LISTED GREASE HOOD ASSEMBLIES SHALL BE INSTALLED IN LOCATION. ACCORDANCE WITH THE TERMS OF THEIR USTING AND THE INSULATION TYPES MANUFACTURER'S INSTALLATION INSTRUCTIONS. 10. THE CONTRACTOR SHALL SUBMIT BID BASED ON THE DRAWINGS AND A 1", 0.60 LB/CU. FT. MINERAL FIBER BLANKET ALTERNATE FOR COST SAVING. THESE DRAWINGS ARE FOR BIDDING 37. A PERFORMANCE TEST OF THE INSTALLATION OF THE VENTILATION 1/2 INC., 1.5 LB/CU. FT. MINERAL FIBER BLANKET (DUCT LINER) PURPOSES. SYSTEM FOR HEAT -PROCESSING EQUIPMENT IS REQUIRED TO VERIFY 1/2 INC., 3 LB/CU. FT. MINERAL FIBER BOARD THE RATE OF AIR FLOW AND PROPER OPERATION. 11 • COORDINATE THE LOCATION OF ALL CEILING DIFFUSERS. REGISTERS MATERIAL WITH A CONDUCTANCE OF 0.48 OR LESS AND GRILLES WITH THE ARCHITECTURAL REFLECTED CEILING PLAN, 38. THE HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE AFTER THE ELECTRICAL UGH71NG LAYOUT AND ARCHITECTURAL ROOM ELEVATIONS. EXTINGUISHING SYSTEM IS ACTIVATED UNLESS SHUTDOWN IS REQUIRED C 3", 0.60 LB/CU. FT. MINERAL FIBER BLANKET AS A COMPONENT OF THE EXTINGUISHING SYSTEM. 1-1/2", 1.5 LB/CU. Fr. MINERAL FIBER BLANKET (DUCT LINER) 12. DUCTS SHALL BE SUPPORTED WITH 1" WIDE 16-GAUGE HANGER STRAPS 1-1/2". 3 LB/CU. FT. MINERAL FIBER BOARD AND SHALL BE SPACED AT NO MORE THIN 7'-0" ON CENTERS AND MATERIAL WITH A CONDUCTANCE OF 0.16 OR LESS SHALL BE SECURED TO STRUCTURAL MEMBER. EXPOSED DUCTWORK ON ROOF SHALL BE SUPPORTED BY GALVANIZED STEEL ANGLE & SHALL W WEATHERPROOF BARRIER BE PER LOCAL CODE. WHERE DUCTS ARE USED FOR BOTH HEATING AND COOLING, THE MINIMUM 13. ROUND AND RECTANGULAR DUCTWORK ARE INTERCHANGEABLE IF CROSS SYMBOLS AND ABBREVIATIONSINSULATIONTOBEASREQUIREDFORTHEMOSTRESTRICTIVECONDITION. SECTION AREAS ARE EQUIVALENT. CONTRACTOR IS TO VERIFY THE EXACT CEILING SPACE AND INTERCHANGE THE DUCT SIZE TO FIT THE CEILING INSULATION MAY BE OMITTED ON THAT PORTION OF A DUCT WHICH IS SPACE WITHOUT ADDITIONAL FEE CHARGE. LOCATED WITHIN A WALL OR A FLOOR -CEILING SPACE WHERE BOTH SIDES AND THIS SPACE ARE EXPOSED TO CONDITIONED AIR AND WHERE THIS 14. INSTALL VOLUME CONTROL DAMPERS AT EACH SUPPLY DIFFUSER TO AFFORD SA SUPPLY AIR PLENUM CROSS-SECTION SPACE IS NOT VENTILATED OR OTHERWISE EXPOSED TO UNCONDITIONED COMPLETE CONTROL OF THE AIR FLOW IN THE VARIOUS DUCT SYSTEMS. RA RETURN AIR PLENUM CROSS-SECTIONAIR. INSTALL SPUTTER DAMPER AT DUCT TAKEOFFS AND DAMPER AS REQUIRED. 4. SEALING 15. COORDINATE ENTIRE INSTALLATION OF THE H.VAC. SYSTEM WITH THE CD m - CEILING SUPPLY DIFFUSER, 2 - WAY TRANSVERSE SUPPLY DUCTS, TAPED OR SEALED WITH MAS11C EXCEPT FOR WORK OF ALL OTHER TRADES PRIOR TO ANY FABRICATION OR INSTAL - fDUCTSEXPOSEDTOCONDITIONEDSPACE, WHERE DUCT STATIC PRESSURE LATLON. PROVIDE ALL FITTINGS, OFFSETS. AND TRANSITIONS AS EXCEEDS 3/4' WATER, LONGITTUDINAL JOINTS. TAPED OR SEALED WITH REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. f ®- o• CDCEILING SUPPLY DIFFUSER, 4 -WAY MASTIC 16. PROVIDE BACK -DRAFT DAMPER FOR ALL EXHAUST AIR DUCT UNLESS 5. INSPECTION OTHERWISE NOTED PER CODE. INSPECTION TO BE MADE AND DUCTWORK APPROVED BEFORE COVERING 17. CONTRACTOR SHALL SUBMIT A COMPLETE BALANCE REPORT FOR RAG RETURN AIR GRILLE WITH INSULATION. APPROVAL SYSTEMS AIR BALANCE SHALL BE PERFORMED BY AN INDIPENDENT AIR BALANCE CONSULTANT. A CERTIFIED AABC OR NEBB. EAG EXHAUST AIR GRILLE 6. PIPE INSULATION THE REPORT SHALL INCLUDE THE FOLLOWING: A) AIR QUANTITIES AT EACH REGISTER. SWS SIDE WALL SUPPLY REGISTER ALL PIPING SHALL BE INSULATED IN ACCORDANCE WITH THE FOLLOWING TABLE B) STATIC PRESSURE READINGS AT INLET AND DISCHARGE OF EACH AIR HANDLING SYSTEM AND AT INLET OF EACH EXHAUST AIR SYSTEM. SWR L- SIDE WALL RETURN GRILLE C) COOLING AND HEATING SUPPLY AND RETURN AIR TEMPERATURES AT PIPE INSULATION REQUIREMENTS EACH AIR CONDITIONING UNIT. CD CD CONDENSATE DRAIN MINIMUM R-VALUE 18. ALL LINED DUCT DIMENSIONS ARE NET CLEAR DIMENSION AFTER LINING RD RD REFRIGERANT DISCHARGE LESSORGREATERSYSTEM EQUAL TO THAN 2" BEEN INSTALLED. 2' HAS RS IRS REFRIGERANT SUCTION DOMESTIC HOT WATER R-4 R-6 19. ANY MATERIAL, ARTICLE OR PIECE OF EQUIPMENT OTHER THAN THAT INDICATED SHALL NOT BE USED UNLESS APPROVED IN WRITING BY THE TO ROOM THERMOSTAT HYDRONIC HEATING SUPPLY LINES R-4 R-6 ENGINEER AND ANY CHANGES IN MECHANICAL, ELECTRICAL AND/OR OTHER QS ROOM SENSOR COOLING SYSTEMS (PIPES BELOW 55'H7 R-4 R-4 SYSTEMS REQUIRED DUE TO SUCH SUBSTITUTION SHALL BE THE RESPONS- CFM CUBIC FEET PER MINUTE IBILITY OF THE HVAC CONTRACTOR; AND AT NO ADDITIONAL COST TO THE OWNER. EA EXHAUST AIR EXCEPTIONS: THE FOLLOWING PIPING DOES NOT HAVE TO BE THERMALLY 20. w EXHAUST TERMINATION SHALL BE MINIMUM 10 -0 AWAY OR 3 -0 ABOVE EF EF. (TOILET) EXHAUST FAN INSULATED: ( 1) FACTORY -INSULATED PIPING WITHIN SPACE CONDITIONING FROM ANY FRESH AIR INTAKE, OPENABLE WINDOWS, DOORS AND 10'-0" ESP EXTERNAL STATIC PRESSURE EQUIPMENT; ( 2) PIPING THAT CONVEYS FLUIDS THAT HAVE A DESIGN OPERATING TEMPERATURE RANGE BETWEEN 55 DEGREES AND 105 DEGREES MINIMUM ABOVE GRADE. EXIST E) EXISTING FAHRENHEIT. ( 3) GAS PIPING; (4) COLD DOMESTIC WATER PIPING; (5) DRAINS, 21 WARRANTIES; 1-YEAR WARRANTY FOR EQUIPMENT, 5-YEAR COMPRESSORS. VENTS, AND WASTE PIPING. REFER TO CONSTRUCTION CONTRACT FOR OTHER APPLICABLE WARRANTIES. FD FIRE DAMPER 22. ACCURATE AS -BUILT DRAWINGS SHALL BE MADE DURING CONSTRUCTION AND FLA FULL LOAD AMPERES 7. TEMPERATURE CONTROLS SUBMITTED FOR APPROVAL UPON COMPLETION OF INSTALLATION. EACH HVAC SYSTEM SHALL BE PROVIDED WITH AT LEAST ONE AUTOMATIC 23. EQUIPMENT SPECIFICATION AND INTERLOCK DIAGRAM SHALL BE SUBMITTED HZ HERTZ TEMPERATURE CONTROL DEVICE FOR THE REGULATION OF TEMPERATURE FOR APPROVAL PRIOR TO PURCHASE OF EQUIPMENT FOR INSTALLATION. THESE AUTOMATIC TEMPERATURE CONTROL DEVICES SHALL BE HP HORSEPOWER CAPABLE OF BEING SET TO MAINTAIN SPACE TEMPERATURE SET 24. THE CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING TO VERIFY LOCATIONS POINTS FROM 55 DEGREES F TO 85 DEGREES F, SHALL BE AND SIZES OF ALL EXISTING EQUIPMENT AND INFORM THE ARCHITECT AND MVD MANUAL VOLUME DAMPER CAPABLE OF OPERATING THE SYSTEM HEATING AND/OR ENGINEER OF ANY DISCREPANCIES. COOLING IN SEQUENCE. OSA OUTSIDE SUPPLY AIR 25. THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR, EQUIPMENT, EXCEPT AS ALLOWED, THESE CONTROLS SHALL BE ADJUSTABLE TO TRANSPORTATION AND SERVICES NECESSARY FOR COMPLETION OF THE RLA RATED LOAD AMPERES PROVIDE A DEAD BAND OF 5 DEGREES F BETWEEN FULL HEATING WORK. ALL MATERIALS AND WORK SHALL COMPLY WITH APPLICABLE CODES AND FULL COOLING. CONTROLS SHALL HAVE THE CAPABILITY OF AND GOVERNING REGULATIONS AND MEET THE APPROVAL OF THE LOCAL RA RETURN AIR TERMINATING ALL HEATING AT A TEMPERATURE NO MORE THAN JURISDICTION. 70 DEGREES F AND OF TERMINATING ALL COOLING AT A TEMPERATURE SA SUPPLY AIR NOT LESS THAN 78.DEGREES F. 26. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE MATERIALS BEFORE, DURING AND AFTER INSTALLATION. IN THE EVENT OF DAMAGE, IMMEDIATELY Q SD SMOKE DEFECTOR REPAIR ALL DAMMED AND DEFECTIVE WORK TO THE APPROVAL OF THE 8. A MAINTENANCE LABEL SHALL BE AFFIXED TO MECHANICAL EQUIPMENT ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO THE OWNER PER SP STATIC PRESSURE STANDARDS. 27. THESE DRAWINGS ARE DIAGRAMMATIC. THE CONTRACTOR SHALL BE NOTE: RESPONSIBLE FOR COORDINATING HIS WORK WITH ALL OTHER TRADES. TYP TYPICAL REFER TO THIS INCLUDES COORDINATING THE LOCATION AND SIZE OF ALL OPENINGS, LSHEETS LOCATIONS OF EQUIPMENT PADS AND CHANGES OF ELEVATIONS OF U/C OR D/U vU UNDERCUT DOOR FOR ANY DUCTWORK, PIPING AND OTHER EQUIPMENT. ADDITIONAL U.T. R. UP THRU ROOF LEGEND, 28. PROVIDE ALL FRESH AIR INTAKES AND EXHAUST OUTLETS WITH HOOD, 1/2" SYMBOLS AND GALVANIZED MESH SCREENS AND OUTSIDE AIR BACKDRAFT DAMPERS. V VOLT RELATED ABBREVIATIONS. 29. DUCTWORK SHALL BE INSULATED OR LINED AS NOTED ON DRAWINGS. VTR VENT THRU ROOF ALL DUCTWORK EXPOSED ON ROOF SHALL BE INTERNALLY LINED UNLESS OTHERWISE INDICATED OR SPECIFIED. ALL DUCT SIZES ARE SHEET METAL SIZES. ALL DUCT JOINTS SHALL BE SEALED PER SPECIFICATIONS. B PACKAGED ROOFTOP UNIT SCHEDULE SYM MFR & MODEL # AREA SERVICED COOLING CAPACITY SEER/ EER HEATING CAPACITY CFM OSA CFM ESP ELECTRICAL WT REMARKS U P P E) RTU 1,2 CARRIER 48HCO6 SEE PLAN 5 TON RXISTING NOTE: A. AREAS WITH UNIT SUPPLYING MORE THAN 2,000 CFM SHALL BE EQUIPPED WITH AN DUCT SMOKE DETECTION SYSTEM. THE SYSTEM SHALL SHUT DOWN UNIT(S) IN THAT COVERED AREA. B. ELECTRICAL SHALL PROVIDE ONE DISCONNECT SWITCH AND SINGLE FEED FOR UNIT AND POWER EXHAUST. C. ALL MODULATING POWER EXHAUST SHALL BE MODULED VIA BUILDING/SPACE PRESSURE INITIALLY SET AT 0.05" W.C. D. PROVIDE CO2 SENSOR. EXHAUST FAN/ MUA FAN SCHEDULE SYM MANUF./ MODEL CONDITION LOCATION AREA SERVED TYPE CFM PRESSURE STATIC RPM DRIVE MOTOR SO ES REMARKS HP VOLT EF COOK 70 ACE-8 NEW ROOF RESTROOM CENTRIFUGAL1 DOWNBLAST 1600. 5 1398 BELT 1/6 120/10 8.5 4,7.8,9 EF 2 COOK 70 ACE-B NEW ROOF RESTROOM CENTRIFUGAL DOWNBLAST 160 0. 5 1398 BELT 1/6 120/10 8.5 4.7.8.9 EF DU50HFA NEW ROOF PIZZA HOOD ROOF MOUNTED UPBLAST 1, 200 0.75 1,423 DIRECT 1/2 115V/10 14.4 1,2,3,4,5,E 3 1,389 EF 4DU85HFA NEW ROOF COOKLINE ROOF MOUNTED UPBLAST 1900 1. 0 DIRECT 3/4 115V/10 16.3 1.2.3.4.5.10 MAU 1 A2- G12 NEW ROOF COOKLINE ROOF MOUNTED r2500 1.0 962 DIRECT 1.5 115V/10 30 4.10 NOTES: O 1. PROVIDE9.5" HIGH VENTED ROOF CURB WITH VENT EXTENDER. 2. PROVIDE ALUMINUM GREASE TUBE AND GREASE TERMINATOR. 3. PROVIDE EXPLOSION PROOF MOTOR. 4. PROVIDE DISCONNECT SWITCH. 5. PROVIDE HINGED BASE KIT. 6. ELECTRICALLY INTERLOCK WITH RTU-2. 7. PROVIDE 9.5" ROOF CURB. 8. INTERLOCK WITH LIGHT SWITCH. 9. FURNISHED WITH BACKDRAFT DAMPER. 10. ELECTRICALLY INTERLOCK EF-4 WITH MAU-1. HOOD INFORMATION HOOD N0. MODEL LENGTH MAX. COOKING TEMP. EXHAUST PLENUM HOOD CONSTRUCTION HOOD CONFIG. ETL LISTING # UL COMPLIANCE TOTAL EXH. CFM RISERS END TO END ROW WIDTH LENG. DIA. CFM S.P. 1 3624 ND- 2 6 0.00 " 600 Deg 1200 14" 1200 0.253" 430 SS W re x se ALONE ALONE 102900319PRT-001 710 2ND-2- PSP- Where Exposed DIFFUSER SCHEDULE DIFFUSER SCHEDULE MARK AIR FLOW CFM MFR MODEL NECK SIZE PANEL SIZE DAMPER REMARKS MARK AIRFLOW CFM MFR MODEL NECK SIZE PANEL SIZE DAMPER REMARKS CD-1 400-600 KRUEGER RM1 12"0 22"0 MANUAL 1,2,3 RR-1 600 KRUEGER 56490 12"X12" 24"X24" MANUAL 1,2,3` CD-2 350 KRUEGER 51240 12"X12" 15"X15" OBD 1,2,3 RR-2 550 KRUEGER S580 16"X16" 18"X18" OBD 1,2.3 CD-3 400-600 KRUEGER 51240 j 12"X12" j 24"X24" j MANUAL j 1,2,3 j ER-1 j 100-160 j KRUEGER I S80 I 10"X10" j 12"X12" j 1,2,3 NOTES: 1. PAINT TO MATCH THE COLOR OF CEILING/SOFFIT. 2. FURNISH AND INSTALL PROPER DUCT TRANSITION COLLAR. 3. FURNISH AND INSTALL DUCT EXTRACTOR. AIR BALANCE SCHEDULE CALCULATATION UNIT OUTSIDE AIR RETURN AIR ISUPPLY AIR EXHAUST AIR PRESSURE RTU-1 1500 500 500 2000 1500' 2000 1500 500 RTU- 209EF- 1 160 160 EF-2 160 160 EF-3 1200 1200 W-4 1900 1900 MAU-1 1520 1520 1520 TOTAL 3520 2000 5520 3420 100 0 APPROVAL Riverside County Fire Department OffXe of Fire Marsl By. 'Oi-' i : J The approval of plans and specifications does not Permit the violation, deletion, omission or faulty Installation ofanyrequirementsofTitle24oranyLocalOrdinances. Construction shall remain accessible and exposed for inspection purposes until approved bytheFireDepartmentOUTDOORAIR VENTILATION CALCULATION 2016 CIVIC 1. CALCULATIONS BASED ON 2016 CAC. 2. CAPACITY :'' S BEEN INCLUDED IN THIS DESIGN. AREA OUTDOOR AIR RATE BASIS IS T USED. 3. OUTDOOF, 3R CALCULATION: PEC E OUTDOOR AIR RATE: 7.5 CFM/PERSON X 49 = 368 CFM IR OUTDOOR AIR RATE: 0.18 CFM/SF X•T".i, „ " LSIRN.ORE ll VISION Kt.- V i S' 1.7. DS ' -7- 1 v i 00 O Q U q. y 1 1 g C* j : r %0 O cd 1. 4 ; 3 U ¢ °` av c NU' w OLIL0 CU W Z W Q U 1 O" W Q J 0 b- __J O10 W QUW Z WW D Y W 00 D Ur'J O_ N W 1 O W the CD U V MECHANICAL NOTES & SCHEDULE 10/ 22/ 18 SCALE I DRAWN BY SEE PLAN STORE NO. M- 1 MECHANICALNOTES & SCHEDULES SCALE: NTS A MECHANICAL PLAN NOTES 1O (E)RTU-1.2 5-TON UNITS EACH MOUNTED ON ROOF W/DISCONNECT SNATCH & WEATHERPROOF GFCL O(N)KITCHEN EXHAUST DUCT MOUNTED VERTICALLY, TERMINATES TO (N)EXHAUST FAN MOUNTED ON ROOF. MAINTAIN MIN. 2% SLOPE GREASE DUCT SHALL BE ENCLOSED IN A FIRE RATED ENCLOSURE SEE DETAIL ON SHEET M-1. O ANSUL FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED IN COMFORMANCE WITH NFPA 96. OGREASE EXHAUST DUCT TO BE 16 GAUGE CARBON STEEL WITH LIQUID TIGHT WELDS. HOOD LIGHT SWITCH TO BE LOCATED ON FACE OF SYSTEM COMPARTMENT. OPERATION OF KITCHEN HOOD IS INTERLOCKED WITH KITCHEN EXHAUST FAN. O USE FLEXIBLE DUCT, THERMAFLEX TYPE MKF OR EQUIVALENT, CLASS 1. WITH 1-1/2• EXTERNAL INSULATION ON ALL ROUND SUPPLY AIR DUCTS ABOVE FINISHED CEILINGS.. PROVIDE 1/2- THICK DUCTUNER ON ALL RECTANGULAR SUPPLY, RETURN DUCTS MAKE-UP AIR DUCTWORK ABOVE THE CEILING WITH A MINIMUM OF 1• THICK, 1-1/2- LB. DENSITY (R-5.6) DUCT MAP WITH VAPOR BARRIER. MAINTAIN VAPOR BARRIER THROUGHOUT THE DUCT SYSTEM. SIZES SHOWN ARE CLEAR INSIDE DIMENTION; SHEET METAL SIZES SHALL BE INCREASED ACCORDINGLY. PROVIDE SPIN -IN DUCT CONNECTOR WITH BALANCING DAMPER AND LOCKING QUADRANT. 6O 6' DIA. RESTROOMS EXHAUST DUCT VENT TO ROOF. OMECHANICAL CONTRACTOR TO FIELD VERIFY THAT SUPPLY AIR DUCT RISER IS PROVIDED WITH DUCT SMOKE DETECTOR. PROVIDE DUCT SMOKE DETECTOR IF NONE EXISTING IS INSTALLED. 8- .(N)36' WIDE AIR CURTAIN; 1960 TO 14M FPM AT NOZZLE GENERAL NOTES 1. DUCT SMOKE DETECTORS SHALL BE LABELED BY AN APPROVED AGENCY, APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHALL FOR AIR DUCT INSTALLATION AND SHALL BE INSTALLED IN ADDORDANCE WITH THE MANUFACTURER'S APPROVED INSTALLATION INSTRUCTIONS (2016 CPC, SECT. 608.1) 2. AN AIR BALANCE TEST WILL BE REQUIRED TO VERIFY THE MINIMUM VOLUME OF OUTSIDE AIR TO COMPLY NTH THE T-24 CALCULATIONS, BEFORE THE FINAL APPROVAL OF THIS PROJECT. 3. HOODS, FILTERS, EXHAUST FANS, AND DUCTS SHALL HAVE A CLEARANCE OF AT LEAST 187 TO COMBUSTIBLE MATERIALS, 30 TO LIMITED COMBUSTIBLES MATERIAL, AND Cr TO NON-COMBUSTIBLE MATERIAL (2016 CMC SEC. 507.2). 4. LISTED EXHAUST HOODS SHALL BE INSTALLED IN ACCORDANCE WITH THE TERMS OF THEIR LISTINGS AND MANUFACTURER'S INSTALLATION INSTRUCTION (2016 CMC SEC. 510.4). 5. A PERFORMANCE TEST WILL BE REQUIRED TO VERIFY THE RATE OF AIRFLOW AND THE PROPER OPERATION OF THE EXHAUST AND MAKE-UP AIR FOR KITCHEN HOOD SYSTEM BEFORE THE FINAL APPROVAL OF THIS INSTALLATION. 6. AIR HANDLING DUCT SYSTEMS, EXCEPT GREASE EXHAUST DUCT SYSTEM, SHALL BE CONSTRUCTED, INSTALLED AND INSULATED AS PROVIDED IN CHAPTER 6 OF 2016 CMC. 7. PRIOR TO FINAL APPROVAL OF THE MECHANICAL PERMIT, A SMOKE DETECTOR SHUT-OFF TEST SHALL BE REQUIRED. 8 ONLY CO2 SENSORS THAT DIRECTLY TRACK THE CO2 LEVEL IN THE BREATHING ZONE ARE PERMITTED BY CEC FOR USE IN THE DEMAND CONTROLLED VENTILATION REQUIREMENT FOR T-24 COMPLIANCE 9. THE CO2 SENSOR MUST BE FACTORY CERTIFIED TO HAVE AN ACCURACY WITHIN +75PPM AT 600 AND 1000PPM CONCENTRATION WHEN MEASURED AT SEA LEVEL AND 25C(77F) FACTORY CALIBRATED OR CALIBRATED AT START-UP AND CERTIFIED BY THE MANUFACTURER TO REQUIRE CALIBRATION NO MORE FREQUENTLY THAN ONCE EVERY 5 YEARS. 10.THE INSIDE EDGE OF CANOPY TYPE COMMERCIAL EXHAUST HOOD SHALL EXTEND A HORIZONTAL DISTANCE OF NOT LESS THAN 6 INCHES BEYOND THE EDGE OF THE COOKING SURFACE OF ALL OPEN SIDES AND VERTICLE DISTANCE BETWEEN THE HOOD AND THE COOKING SURFACE SHALL NOT EXCEED 4 FEET. 11.EXHAUST OUTLET TERMINATION OF GREASE DUCT FROM HINGED UPBLAST FAN SHALL EXTEND THROUGH THE ROOF SHALL NOT BE LESS THAN 18 INCHES ABOVE THE ROOF AND THE FAN DISCHARGES NOT LESS THAN 40 INCHES ABOVE THE ROOF. 12.PROVIDE CERTIFIED AIR BALANCE REPORT FOR EXHAUST HOODS AND MAKE UP AIR PRIOR TO FINAL INSPECTION. NEW 4z4 O EA HANGER LOCKNUT & LOCKNUT W/ %USW END ANDFA CONPLY. E.N. W/WASHERS (TYP. A fjE) ROOF SHAG. 2'x )e I.G. STEEL HANGING ANGLE W/(4) 16d r NEW Z&48. I.G. W/ 12d AT 6' O.0 W/ NAILS NOT LOCATED WHIN Y OF PIN. NUT do LOCK NUT SPLICE SWILL BE LOCATED oiCONNECTION MIDWAY BETWEEN BLKG., IV. W/WASHERS (M.) E) T (TJI) HOOD MOUNTING CHANNEL HOOD/ 1 2 —• 1/2• DYl ALL THREADED ROD O ANGLE INTEGRALWITH EACH WOOD SUPPORT (TV) HOOD - SEE HOOD DRAWINGS HANGING ANGLE INTEGRAL WITH HOOD - SEE HOOD DRAWINGS EXHAUST HOOD - SEE HOOD DRAWINGS STEEL HANGING ANGLE FOR s e WOOOOLOCK CONNECTION e 1/2' DA, HEAVY DUTY NUT WASHER -OE ABOVE AN 1/2' DA. ALL THREAD ROD ONE EaOW HANGING ANGLE CONNECTED TO ROOF JOIST ANGLE Y THROUGH ANOTHER HANGING 2 HAS 40C ma FOR NOTE HOOD CONNECTION REFER TD HOOD MANUFACTURER'S SPECFCk=IS AND THE DRAWTINGS FOR ADDITIONAL CONSTRUCTION REQUIEI*M HOOD HANGING DETAIL NO SCALE DUCT SUPPORT DETAILS (SMACNA) 1-1I1 x 26 GAUGE STRAPS WITH 248 SMS EACH SIDE OF DUCT DUCT SUPPORT SPACING AS PER UMC Table 6f. ROOFIC2:LING JOIST MIKE ElHANGERSTRAPSCIYYBANDOF S I ® E so' MAX K IMISIONsNasMlcNi%Am DETAIL (TV) Evio UNLESS F00T OF Ow"E STRAP S PLACED MECHANICAL FLOOR PLAN ` is -- - Ian MIL SCALE: 1 /4" 1 1_O11 IMFAYBE HANGER LOOPS 5r DYl MAX RECTAIGUARDUCT ROM DUCT SIRAPHANCERS U 00 c O 0 Q U t en O -aen CM CUa N u IN 4 0 U M cu LLJ ON D Z w Q i U QQ 1 0 w N Q QWaJ~ Z OJOm- i QU wL dF... Z co H Y w co D Q j rn cn o W CDU WV V c I MECHANICAL PLAN 10/ 22/18 DRAWN BY 5EE PLAN STORE NO. as WM W. SEE SCHEDULES) V/0/Hz DIAMETER VARIES 10'-0' MIN. FROM I CIRC. BRKR. SEA 70 2' WOE ACOUSTICAL AIR INTAKES,tZ. Q STRL0URE AS ME METAL STRAPS FLEX01 DUCT S FT. LONG REMOVABLE FAN MANUR TO PROVIDE SECTION FOR EF LINE INTERNAL CIRCUIT VOLUME DAf1iAEIZ SERVICE, ETC. 1 2 VOLTAGE _ - J BREAKER. SUPPLY AIR DUCT I UP -BLAST FAN 8' HIGH (MIN.) LEVEL 666 4W ROOF CURB (BY G.C.) COOUNG TUBE LAG SCREW 6" O.C. AC AC AC CANT STRIP AND EACH SIDE 1 2 3 PROVIDE MFR. SEALANT A ROOFING (BY G.C.) HOOD FOR DUCT WRAPz f f AUTOMATIC BACK d d R ; 14 DRAFT DAMPERCEIUPIGINSULATEDWALLIIIIIIILOWVOLTAGEWIRING CURB OR NON- 00 COMBUSTIBLE FIELD BUILT CURB- 1. FVURN AIR REC•IM IWALLATiOPI2. ALL DUCE INSULA710N SWYl FY1NE A INKING SHALL BE OU DE 16 GA STEEL EXHAUST DUCT WITH EXHAUST AIR DUCT THERMOSTAT Q; FLAMuIE SPREAD OF NOT MORE THAN 25 DUCT. COMPLY ? NA L DUST WRAP PER DETAIL THIS SHEET RANDAS1IOKE-DENSf1Y NOT EXC®ING ELEC. CODE & N.F.P.A PROGRAMMABLE VERIFY EXACT WIRING PER 50 PER SECTION• AIR VELOCITY THROUGH DUCT 1' CLEAR (MIN.) FLEXIBLE CONNECTION. MANUFACTURER'S INSTRUCTION OD CONTROL NOT LESS THAN 1500 C.F.M. ALL AROUND DUCT BEFORE INSTALLATION. A CEILING DIFFUSER DETAIL B EXHAUST FAN DETAIL N CC) EXHAUST FAN DETAIL N CID RTU CONTROL DIAGRAM NON 1 /4' DIA. SET SCREW 1' x 1 /8" GALVANIZED STRAP SPOTWELD 15 GAUGE GALVANIZED I0[C CENTERLINE OF THERMOSTAT, SWITCH, OUTLET, CONTROL FINISHED THERMOSTAT LOCATION It9;1 a; RMOSTAT, fCH, LET, ITROL RECTANGULAR DUCT HANGER MINIMUM SIZE MAXIMUM PAIR OF PAIR OF PAIR OF PAIR OF HALF OF 10 FT. 8 FT. 5 FT. 4 FT. DUCT PERIM STRAP WIRE STRAP IRE STRAP WIREWIRESTRAPRODRODROD) ROD P/2-.30+ 22 10 GA. 22 10 GA. 22 12 GA. 22 12 GA. GA. 1351 GA. 1351 GA. 1061 GA. 1061 P/2=72* 18 3/8e 1(*x20 1/4' 1GA_ 1/4' 1/4' GA GA. DUCT SIZE CROSS STRAP HANGERS SECTION LIMITED TO 6 SQ. FT. NOTESO. 1. FOR HANGERS SIZE AND SPACING, TABLE ABOVE. 2. FOR UPPER ATTACHMENT TO BUILDING, SEE DETAIL L/M-3. FOR NON -GREASE DUCT INSTALLATION ONLY. 3. RECTANGULAR DUCT SUPPORT DETAIL 3M FIRE BARRIER DUCT WRAP 615+ 3' THICK 0" CLEARANCE TO CUMBUSTABLES H PERFORMANCE GREASE DUCT SYSTEM. INTALL 1 2 NGSTEELBANDI PER MANUFACTURER'S LISTING. LAMENT TAPE 1/2" DIAMETER 3' LONGITUDINAL HANGER ROD OVERLAP - ANG/ 2'x1 1/2'x1/8" d pig (d HOOD EXHAUS DUCT Ut p(R ACCESS HOLE- ACCESS FRAME - WELDED TO DUCT F 120V-1/ ( C BLADE S EclRcuTr 1/ouc"SSECTION A -A HANGER LOAD BREAKER-( DIAfETER I RATED 3/ 8' SQUARE ROD END BEARING FASTENER. LIGHTING 3/8* SQUARE ROD GASKET CIKcUIT. _ R E / 24 INCH DIA. MAX. p i f l A (WIRE HANGERS MINIMUM HANGER SIZES FOR ROUND DUCT DIA MAXIMUM WIRE ROD STRAP SPACINGDIA. 10" 12' ONE 12 1/4' 1' x 22 Ad- mm DIs. 3.7 m 6RE 2.75 min 6.4 mm TA4 x 0.85 11- 18" 12' TWO 12 1 /4` mm 1* x 22 lII ONE 8 GA 460 3.7 m W 4.27 6.4 mm 25.4 x 0.85 19- 24" 12' TWO 10 1/4' 1' x 22 610 mm 3.7 m f* 3.51 m 6.4 mm 9A4 x 0.85 NOT GASKET PERMITTED) LOCKNUT I I (I 1 INDICATING HANDLE NOTES: 1. FOR HANGERS SIZE AND SPACING, TABLE ABOVE. EF EF NOTE: REGULATOR ' PLAN 2. FOR UPPER ATTACHMENT TO BUILDING, SEE DETAIL L/M-2. 1 2 LOCK DAMPER DURING AIR BALANCE AND MA ADRANT TO RECORD AIR BALAN POSITION. 3. FOR NON -GREASE DUCT INSTALLATION ONLY. PROVIDE * HAT" SECTION AT QUADRANT FOR ALL EXTERNALLY INSULATED W DUCTWORK. PROVIDE FLUORESCENT COLORED MARKERS AT ALL VOLUME DAMPER LOCATIONS. EXHAUST FAN CONTROL WIRING MANUAL VOLUME DAMPER sou H ROUND DUCT SUPPORT DETAIL N 1NONE KEY NOTES: DUCT DURODYNE WELDED 1 HEAD PIN ( TYP) OPOF DUCT WRAP. SEE DUCT WRAP FROM TOP ENTIRE INSIDE DUCT THE HOOD TO 18" ABOVE ROOF SURFACE. VERTICAL EXHAUST SURFACE SPRAYED DETAIL SHOWN ON THIS SHEEP. DISCHARGE EF WITH ADHESIVE EXHAUST 3 O CONTRACTOR SHALL SLOPE THE EXHAUST DUCT TO I PIN - SPOT WELDED AIR DUCT NO LESS THAN 1 /4" PER LINER EXTEND MIN. 16 GA. WELDED S.S. FOOT. 24* EXHAUST DUCT ROOF DECK. z TO DUCTWORK (TYP) VENTED EXTENDED UNING I BASE t 18' 4"X6' I OGREASEDUCTSHALLBECONSTRUCTEDWITHgTYP. OF 2- 10 10 GAUGEWOOD 16 GAUGE GALVANIZED SHEEP METAL WITH o t eo (E) BUILT-UP ROOF. I SCREW. WELDED SEAMS. N EXTEND LIMITED COMBUSTIBLE OR l .•/{ TJI. TYPICAL. NONCOMBUSTIBLE CEILING MATERIAL 18' SHEET METAL SfWIP BEYOND OUTER EDGE OF THE DUCT. 1 3 WG GREASE DUCT SYSTEM MUST (TO SEAL DUCT AT POM OF PENETRATION) BE ACCESSIBLE FROM DUCT METAL SHELD/ COLLAR ENTRY TO DISCHARGE; 1 2 !3 4 5 LEADING EDGES PROVIDE OPENINGS IN SUPPLY RISER SPRAYED COMPLIANCE PER 2013 CMC EXHAUST RISER LUME DAMPER WITH ARABOL510.3..4 HANGING ANG 18 7 2 3/4" THE EXHAUST OUTLET GYPSUM BD. CEILING TILES DUCT LINER DETAIL SCALE NONE DUCT STRAP ATTACHMENT 10 T CnPS Sty G HALL BEETETFROM ADJACENT FRO UILDINGS, PROPERTYALSERIES E26 6 24 NON. FAN LINES OR AIR INTAKE, 3 TYPE CHEN"OWG. D. SECANOPY LIGHT 1 * Hi. 108' FAN BASE PAB'l D® FEET ABOVE ANY AIR FIXTURE 2-FAN PLATES (LEFT &RIG" INTAKE LOCATED WITHIN 10 METAL STUD WALLS WITH 5/8'GYP. CURB PLATE 2 - CURB PLATES ( LEFT & RIGHT) FEET IS ALLOWED do 40 BOARD WALL CONSTRUCTION AND 1` MI . GREASES N CLOOM LEFT) z- WHIZ BOLTS 6-WHIZ NUTS INCHES AWAY FROM ANY WALL. MINERAL WOOL BATT OR CERAMIC REMOVAB CUP FAN KET.® 22 GA. S/S BACKING SHEET METAL SCREWS 24-#14x3WSCREWS COVERS ENTIRE BACK 48• MAX _ MIN. 18" FROM GYP. 80. AREA OF HOOD. CEILING TO TOP OF HOOD. MIN O DETAIL - A' O THE HOOD SHALL HAVE A COOKING SURFACE 78" AFF REFERENCE S CLEARANCE OF AT LEAST 3" FROM METAL STUD WALLS WITH ASSEMBLE FAN PLATE WITH CURB PLATE AS SHOWN ON PIC. 1 GYP. 8D. (AS SHOWN). AND PIC. 2 (IF PARTS ARE NOT ASSEMBLED) MATERIALS WITHIN 3* OF THE T'i ffiQZ HOOD MUST BE NUT NON- COMBUSTIBLE. 1/4" DW ALL I I OP THREAD ROD 16 GA. ACCESS COVER 3M INFORMATION O INSULATIO PERFORMANCE PINS WELDED TO 3M BARRIER DUCT WRAP 615+ HAS BEEN ACCESS COVER TESTED IN ACCORDANCE WITH THE FOLLOWING: 3M FIRE BARRIER ASTM E 2336 ASTM E 119 DUCT WRAP 15A ASTM C 518 ASTM E 136 ASTM E 84 ASTM E 814 p UL 2221 SPEED CUPS a ICC- ES AC 101 F) ISO 6944 - 85 SPOOL PIECES CODE ACCEPTANCE PER ASTM E-2336 FOR THREADED NFPA 96 2008 EDITION RODS. INTERNATIONAL MECHANICAL CODE 2009 EDITION ALUMINUM TAPE SF °- AT AL EXPOSED 3M FIRE BARRIER 10OX N/S 1/4' DIA EDGESSIUCONE SEALANT AND 3M FIRE BARRIER WING NUTS 1003 S/L SILICONE SEALANT e HOOD EXHAUST ( GREASE) DUCT DETAIL N o WHIZ NUT WHIZ BOLT FAN CURB PLATE CURB PLATE FAN RB RIGHT) PLATE (LEFT) PLATE e(RIGHT) ( LEFT) e) SEE DES AIL`A' FOR POSITIONING FAN PLATE ON FAN BASE. LINE UP FAN BASE EDGE TO INSIDE EDGE OF FAN PLATE AS SHOWN ON PIC. 3. l ATIENim LABEL FAN BASE INSTALLER MUST FAN BASE EDGE READ LABEL NEAR DISCONNECTSWfTCHI MESSAGE ON LABEL: INSTALLER SHOULD e SUPPLY ENOUGH INSIDE EDGE OF FAN PLATE ELECTRICAL CORD TO LET FAN MAKE COMPLETE SCREW THE FAN PLATE TO THE FAN BASE USING SWING' 12) # 14 X 3/4' LG. SHEET METAL SCREWS. NOTE: IF THE SCREWS HIT THE CURB, THEN RUN THE SCREWS FROM INSIDE THE FAN BASE, ALWAYS BE SURE THAT SCREWS ADD CHAIN DO NOT INTERFERE WITH CURB WHEN FAN SWINGS SEE PIC. 4. RESTRAINTAT COMPLETION OF RUB INSTALLATION RUNSCREWFAN BASE FROM FROM OUTSIDE INSIDE CURB UQ SCREW THE CURB PLATE TO THE CURB USING 112) # 14 X 314' LG. SHEET METAL SCREWS. TIGHTEN NUT AND BOLT ASSEMBLY, ENSURE FAN SWINGS PROPERLY. HINGE KIT INSTALLATION SCALE NONE M IN 4X4 BEAM W/ SIMP A- 35 0 4X4 2x4 SLEEPER C TOP OF TRUSS BOTTOM CHORD 1/ 2.0 THREADED RODS U.N. O. SUPPORT BRACKET 048" O.C. BY HOOD MFGR. Ys; KITCHEN HOOD SECTION DETAIL Lox 4 THK. x 0'-3' 048' O.C. WXO X 3 Yt" LAG SCREW TO BM. 0 4x4 W M W/SNP A-35 Ek SIM M e SU3M L ( E) TRUSS BOTTOM CHORD 1/ 2.0 THREADED RODS U.N. O. SUPPORT BRACKET 048` O.C. BY HOOD MFGR. KITCHEN HOOD A& 2x4 SLEEPER W/ 15d__r `TRUSS IDM CHORD ` ` JOIST AW4E, TYP. 06' O.C. TO TRUSS BOTTOM CHORD 1/ 2 0 THREADED 6Roos U.N. O. SECTION HOOD SEISMIC BRACING KITCHEN HOOD HANGING DETAILS MSa cu M cu Lj ON Ld - w Q i U QQ O N w Q Q O J L.tt a L J ~ OJJO_ j U J Ww Ld o LLJF- z ~ 00 Y w U v Z y>• I C) 1 O N N tL7 W 1 O W U W U V I MECHANICAL DETAILS 10/ 22/ 18 Jw DMWN BY SEE PLAN STORE NO. Mww. w. M- 3 1tYAAn TVBrADIIAfPrA1T — /w&Jl9D4 9&09 MAX EXHAUST PLENUM TOTAL HOOD CONFIG. TOTAL RISER (S) END TO ROW HOOD NO. TAG MODEL LENGTH COOKING SUPPLY HOOD CONSTRUCTION TEMP. EXH. CFM WIDTH LENG. HEIGHT DIA. CFM VEL S.P. CFM END 1 3624 IT (r 00 12W 4' 14' 1200 1123 0.253" 0 43OWher SExposetl ALONE ALONE 2 5424 8' 0' 600 1000 4• 14' 1900 1777 0.777' 1520 S ALONE ALONE ND-2-PSP-F WhereO I vnnn T1TEInl2e/AMTn1T FILTER LIGHT UTILITY CABINETS) FIRE HOOD HOOD TAG WIRE FIRE SYSTEM ELECTRICAL SWITCHES SYSTEM NGIN TYPE SIZE MODEL# QUANTITYNO. TYPE QTY. HEIGHT LENGTH EFFICIENCY ®7 MICRONS QTY. TYPE GUARD LOCATION SIZE PIPING WGHT 1 Light 234 1 SS Baffle with Handles 4 16' 16" 30% 3 Screw In Compact NO well Mnt 12'k36)Q4• Ansul R102 3.0 SC-121110MA YES LBS1Fan 2 erCeptratebFilter 5 20' 18' lte85% See Fr Spec. 3 L55 Series E26 NO YES 444 LBS TAG OPTIONNO. 1 FINISHED BACK- ISLIREV INSTALL 72.00' Long, ( Filters to the fronQ HOOD DTirDFADA,rvn Q7TD11-Y Dl_Ti'11TTTLOC' 9 RISER (S) HOOD NO TAG POS. LENGTH WIDTH HEIGHT TYPE WIDTH LENG. I DIA CFM I S.P. MUA 12' 28' 760 0218' 2 Front O6' 18• 6' MUA 1 12- 28• 760 0.216- CAT 5 CABLE FROM CONTROL TO PANEL ROOM TEMPERATURE SENSOR O FAN CONTROL 24" INTERFACE ON HOOD I ANSUL SUPPLY LINE TO HOOD ANSUL DETECTION LINE TO HOOD REMOTE MANUAI PULL STATION REMOVABLE S S . SERVICE DOOR OEM RELEASE/ BRACKET ASSEMBL) u IDNISCedsaswlnconlpauFYlormrentelllo ® UTILITY C BINET SHOULD BE MOUNTED MECHANICAL GAS VALVE FLUSH WITH THE FINISHED CEILING LL JPALL MOUNTLTD UTILITY CABIN'T 3HP 7s" aF.F. INSYTALLLD BY HOOD INSTALLER 14• 111- tsr ® ANSUL R-102 WET CHEMICAL EldmM weer DUCTTEMPSENSOR FIRE SUPPRESSION SYSTEM J_ FACTORY PREMED CONDUIT FROM O FIRE SYSTEM MICRO -SWITCH TO 7SUPPLY FAN SHUT -DOWN RELAY PLAN VIEW — Hood #1 6' 0.00" LONG 3624ND-2 ® R ELECTRICAL PANEL WITH FAANN STARTERSlOVERLOADS AND SUPPLY FAN SHUT -DOWN RELAY. IL014• lw v 54• U. L Lilted L55 Series E25 Canopy UgM Fbdure - High Ternp Auw* 28• 28' PRIM 18' 12• ,r 001 1 48' 48' 2A• - I - 46' Ir o-NanJB' o.o6roD PLAN VIEW — Hood #2 8' 0.00 LONG 5424ND-2-PSP—F EXHAUST RISER HANGING ANGLE 20' CAPTRATE SOLD FILTER WITH HOOK 3- INTERNAL STANDOFF IT IS THE RESPONSIBILITY OF THE ARCHITECT/OWNER TC ENSURE THAT THE HOOD CLEARANCE FROM LIMITED -COMBUSTIBLE AND COMBUSTIBLE MATERIAL IS IN COMPLIANCE WCTF LOCAL CODE REQUIREMENTS GREASE DRAM WITH REMOVABLE CUF VERIFY REVISIONS EXHAUST RISER W. A SCREW IN COMPACT FLUORESCENT BULB, L55 HANGING ANGLE SERIES E26 CANOPY LIGHT FIXTURE -HIGH T- BAR CEILING TEMP ASSEMBLY, INCLUDES CLEAR THERMAL Q ANDSHOCKRESISTANTGLOBE4• i R; SIS HOOD CLOSURE Br oTHERs A SS BAFFLE WITH HANDLES AND HOOI( 21 NOM. a m W FINISHED BACK O O O O FLUE FROM OVEN g00000 0 4U' Nip INTO HOOD DISTANCE FROM GREASE DRAIN J CC, CTONG FILTER SURFACE iS WITH REMOVABLE CUP O Q w oo a W O 4 VERIFY PIZZA STONE PIZZA OVEN W U. E V OPtbV Z O 0 7 0 GO 11m Y, r 11I - 0 s y aa 0 0 L55 SERIES Eta CANOPY LIGHT FDCTURE - HIGH TEMP ASSEMBLY, INCLLABS CLEAR THERMAL AND SHOCK RESISTANT GLOBE (1.55 FDaUR15 ATTACHING PLATES SIMPLY RISER WITH VOLWE DAMPER 23. 5% OPEN STAPAXSS co o ve• L/— STEEL PERFORATED PANEL W F— D N a col 2 w U jW LU Y W 0 J J Z 1 O J W 0oLuo a DATE: 5/1/2019 D> f 6J: 3813692 DRAUSITN SCALE: 3/ 4' 1'-0" MASTER DRAVRNG SHEET NO. 1 BUILDINGCITY OF LAKE ELSINORE DIVISION ti Eav'ru" s00 n r1 0 U E u a c G - 4 • M CisU M UQ ° a o uw 0 0cu l/-- J) LL J Cd L, J V ' Z LLJ Q i U O L LIN0KIjQLLIJ 1—t O J J 0 Pq J QUW oWW L, J WM Y U( p(4Q rn Z rn I C N W N I[) OU W W 1 N M HOOD DETAILS A2( DATE JOB NO 10/ 22/18 STALE DRAWN BY SEE PLAN STORE NO. Dw ww. No. M- 4 1 FAN 03 A2-G12 -SUPPLY FAN 1. UNTEMPERED SUPPLY UNIT WITH 1r BLOWER IN SIZE 02 HOUSING 2. EVAP COOLER (LPD CELDEIO - WANTAKE HOOD WUEZ FILTERS 3. DOWN DISCHARGE •AIR FLOW RIGHT-> LEFT 4.120V WIRING CONNECTION TO ENERGIZE EVAPORATIVE COOLERS FROM UNTEMPERED SUPPLY FANS. NOTE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT DISCHARGE UNLESS OTHERWISE SPECIFIED. DO NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT. SUGGESTED STRAIGHT DUCT SIZE IS 10' x 16' x 54' LONG, SLOWER DISCHARGE CURB -/ 7 LIFTING LUG Go 3311 aim 1r EQUIPMENT CURB 31' — ROOF OPENING r SMALLER THAN CURB DIMENSION. PITCHED CURBS ARE AVAILABLE 0» FOR PITCHED ROOFS. 0• SPECIFY PITCH: 1r EXAMPLE: 7/12 PITCH = 30' SLOPE 7 15/1Mr '' j r O 1 19' 01 ire 20' I WATER DRAIN 4D3M' 15314' I I I I AIRFLOW f8' 5 3" ' 5 L - O 1- 412' r FLEX CONDUIT FOR FIELD WIRING 129 7UB' 781/4' 401/3' 33,Ar AIRFLOW AIRFLOW LPD CELDEK AIRFLOW FILTER/CONTROL 433W SERVICE DISCONNECT ACCESS DOOR 38 3W SWITCH BLOWERMOTOR ACCESS DOOR 24• SERVICE CLEARANCE REa e5 01R'NPT • I I WATER INLET MINIMUM WATER FILTER REQUIRED ADJUSTABLE STRAIGHT DUCT PROVIDED BY PLUMBER LEG 1' 31' L_ I MW.1S' - 0 W 04 Q vJ U W 7 cm y D o U w Q LLi a) w w Y W 0 J J Z i 0 J 0) U W 0 O W0 aco Q DATE: 5/1 /2019 DWG.#: 3813692 DRAWN AHJ-86 SCALE: 3/4' 1'-0' MASTER DRAWING SHEET NO. 3 T FL E L O ULDu u a U 1--I 00 r-I c O Q 1 4rA to N - M i•.1 O -a oA M cd 0 M Ud° a 1 o W N u be in o0 i M 37036 Exp. 9-30-20 U Un LLJ Z LLJ Q U Q N W Q O Qj a- O JO W~C:) QU W LL] W LLj U MT Z 4T I Co n N MJ7 O LMJ ck: W VW V V N M HOOD DETAILS 10/22/18 SCALE DRAWN BY SEE PLAN STORE NO. DRAWING No. LEGEND SYMBOL ABBR. DESCRIPTION W S OR W SOIL OR WASTE ABOVE FLOOR OR GRADE W S OR W SOIL OR WASTE BELOW FLOOR OR GRADE GW GW GREASE WASTE ABOVE FLOOR OR GRADE GW GW GREASE WASTE BELOW FLOOR OR GRADE V V SANITARY VENT GV GV SANITARY GREASE VENT DCW DCW DOMESTIC COLD WATER UNDERGROUND PIPE DHW DHW DOMESTIC HOT WATER DHWR DHWR DOMESTIC HOT WATER RETURN D D INDIRECT DRAIN LINE CD CD CONDENSATE DRAIN G FUEL GAS TP TP TRAP PRIMER CWV CWV COMBINE WASTE AND VENT BELOW FLOOR OR GRADE DIRECTION OF FLOWpop P.G. PRESSURE GAUGE W/PETE COCK G.C. GAS COCK P.R.V. PRESSURE REDUCING VALVE D4 -- SOV SHUT-OFF VALVE FCO FLOOR CLEANOUT WCO WALL CLEANOUT D DOWN r' RISE 1I F-- UNION x SLOPE IN DIRECTION OF FLOW 0 WHA WATER HAMMER ARRESTOR POC POINT OF CONNECTION POD POINT OF DISCONTINUATION RPBP REDUCED PRESSURE BACKFLOW PREVENTER ABV ABOVE AFF ABOVE FINISHED FLOOR AP ACCESS PANEL BEH BEHIND BEL BELOW CFH CUBIC FEET PER HOUR CI CAST IRON CLG CEILING CONN CONNECTION CONT CONTINUATION COTG CLEANOUT TO GRADE COYB CLEAN -OUT IN YARD BOX CW COLD WATER DEMOLITION FIXTURES DP DISABLED PERSON DTL DETAIL EX EXISTING FDC FIRE DEPT. CONNECTION FFE FINISHED FLOOR ELEVATION FLR FLOOR FIR FROM FSH FIRE SPRINKLER HEAD GR GRADE HC HANDICAP HDR HEADER IE INVERT ELEVATION MH MANHOLE RI&C ROUGH -IN AND CONNECT SOV/YB SHUT-OFF VALVE IN YARD SOX TYP TYPICAL VTR VENT THROUGH ROOF I APPLICABLE CODES 1 2016 CALIFORNIA BUILDING CODE (CBC) & CALIFORNIA FIRE CODE (CFC) 2016 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. 2016 CALIFORNIA MECHANICAL CODE (CMC) PART 4, TITLE 24 C.C.R. 2016 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. 2016 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 C.C.R. 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART11, TITLE 24 CCR. GENERAL ROTES AND SPECIFICATIONS 1 FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT & FACILITIES NECESSARY TO FURNISH, FABRICATE, DELIVER, STORE & INSTALL ALL WORK NOTED ON THE DRAWINGS AND/OR SPECIFIED HEREIN. 2 WORKMANSHIP: THE WORK SHALL BE ACCOMPLISHED IN A THOROUGH & MANNER SATISFACTORY TO AND MEETING THE APPROVAL OF THE ARCHITECT. 3 MATERIALS : ALL MATERIALS, APPLIANCES & EQUIPMENT SHALL BE NEW & THE BEST OF THEIR RESPECTIVE KIND, FREE FROM ALL DEFECTS AND OF THE MAKE, BRAND AND QUALITY SPECIFIED. 4 SITE INSPECTION : CONTRACTOR SHALL VISIT THE SITE OF WORK PRIOR TO SUBMISSION OF HIS BID AND THOROUGHLY FAMILIARIZE HIMSELF WITH THE WORKING CONDITIONS AND EXACT NATURE OF THE WORK. SUBMISSION OF A BID ACKNOWLEDGES FULL RESPONSIBILITY FOR FURNISHING A COMPLETE & FUNCTIONAL SYSTEM. NO CHANGES IN CONTRACT WILL BE MADE TO ACCOMMODATE OR ALLOW EXTRA FUNDING FOR ANY OMISSIONS WHICH RESULTS FROM A FAILURE TO THOROUGHLY MAKE THE EXAMINATION. 5 CODES AND PERMITS : ALL PLUMBING FIXTURES/EQUIPMENTS, INSTALLATION, ETC. SHALL CONFORM TO ALL APPLICABLE CALIFORNIA CURRENT CODES AND ORDINANCES, INCLUDING CALIFORNIA TITLE 24. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND INSPECTIONS. 6 AS -BUILT : CONTRACTOR SHALL PROVIDE A COMPLETE SET OF AS -BUILT TRANSPARENCIES WITH ALL CHANGES NOTED THEREON AT THE COMPLETION OF THE PROJECT. 7 GUARANTEE : CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE ALL LABOR AND MATERIAL ON ALL WORK AGAINST DEFECTS IN WORKMANSHIP & MATERIALS FOR A PERIOD OF 1 YEAR. 8 SUBMITTALS : CATALOG INFORMATION & CUTS OF ALL EQUIPMENT AND DEVICES SHALL BE SUBMITTED FOR REVIEW (SIX COPIES OF EACH). 9 COORDINATION : THE DRAWINGS ARE DIAGRAMMATIC & INTENDED TO SHOW SCOPE. CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES TO PROVIDE THE BEST ARRANGEMENT OF ALL DUCT, PIPES, CONDUIT, STRUCTURE, ETC. 10 CUTTING AND PATCHING : ALL CUTTING & PATCHING OF THE EXISTING STRUCTURE SHALL BE PROVIDED UNDER OTHER SECTIONS OF THE WORK. PROVIDE ALL NECESSARY REQUIREMENTS TO THE PROJECT SUPERINTENDENT. 11 CLEANUP : UPON COMPLETION OF THE WORK UNDER THIS SECTION THE CONTRACTOR SHALL REMOVE ALL SURPLUS MATERIALS, EQUIPMENT & DEBRIS INCIDENTAL TO THIS WORK AND LEAVE THE PREMISES CLEAN AND ORDERLY. 12 ALL HOT WATER SUPPLY AND RECIRCULATION PIPING SHALL BE INSULATED AS FOLLOWS : PIPE SIZE (INCHES) INSULATION THICKNESS (INCHES)(K=0.27 OR LESS) 1/2',3/4' & 1" 1' 1-1/4- THRU 6' 1-1/2' 8' AND LARGER 2' 13 SOIL, WASTE AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON. NO -HUB SOIL PIPE AND FITTINGS TO CONFORM TO C.I.S.P. STANDARD 301.72., UNLESS 14 HOTREDCSLD ATER PIPING SHALL BE TYPE "L" HARD DRAWN COPPER TUBING WITH WROT COPPER FITTINGS. BRAZE ALL JOINTS WITH HARRIS STAY-SILV-O-LEAD-FREE BRAZING ALLOY. UNLESS APPROVED OTHERWISE. 15 SLOPE ALL CONDENSATE DRAIN LINES AT 1 %. 16 SLOPE ALL SANITARY SEWER PIPING MINIMUM 2%. UNLESS APPROVED OTHERWISE. 17 SLOPE ALL STORM DRAIN PIPING MINIMUM 2%. UNLESS APPROVED OTHERWISE. 18 BASE SHELL DRAWINGS WITH LATEST REVISIONS PROVIDED BY OWNER SHALL APPLY TO THESE DRAWINGS. UNLESS APPROVED OTHERWISE. 19 WRAP ALL CAST IRON PIPE AND FITTINGS IN AND BELOW SLAB WITH 20 MIL POLYETHYLENE WRAP AND 6" MINIMUM ENVELOPE OF CLEAN SAND ALL AROUND PIPE IN ACCORDANCE WITH ANSI/AWWA STANDARD C105/ A21.5-82. 20 FIRE SAFE ALL PIPING PENETRATIONS THROUGH FIRE RATED WALLS, FLOORS, AND CEILINGS WITH NELSON 3-HOUR CLK. FSP, OR CMP UL LISTED FIRE SAVING PER MFG.'S DIRECTIONS. 21 PLUMBING CONTRACTOR SHALL PROVIDE ALL PLUMBING SERVICES REQUIRED BY THE AIR CONDITIONING CONTRACTOR (CONDENSATE DRAINS, WATER SERVICE, ETC.) REFER TO THE MECHANICAL PLANS FOR ANY PLUMBING SERVICES REQUIRED. 22 CONDENSATE PIPING SHALL BE INSULATED WiTH 3/8- FOAM PLASTIC PIPE INSULATION. 23 EACH PLUMBING VENT SHALL TERMINATE NOT LESS THAN TEN FEET FROM OR AT LEAST THREE FEET ABOVE ANY WINDOW, DOOR, OPENING, AIR INTAKE OR VENT SHAFT. 24 CLEAN -OUTS SHALL BE INSTALLED AS PER SEC. 707 & 719 OF THE CALIFORNIA PLUMBING CODE-2016. ALL HORIZONTAL VENT LINES BELOW SLAB SHALL HAVE CLEANOUTS ABOVE GROUND PER CODE. 25 PROVIDE WATERTIGHT FLASHING WHEREVER PIPES PASS THRU EXTERIOR WALLS, ROOF AND FLOORS. 26 PROVIDE FELT WITH METAL BACKING VIBRATION ISOLATION SLEEVES OR PADS AT ALL PIPE HANGERS OR SUPPORTS AND ALL POINTS WHERE PIPING COMES IN CONTACT WITH ANY PORTION OF THE STRUCTURE. APPLIES TO ALL WATER AND WASTEPIPING. 27 LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. CONTRACTOR SHALL VERIFY EXACT LOCATIONS AND DEPTHS OF EXISTING UTILITIES PRIOR TO STARTING WORK OF THIS SECTION. MAKE REQUIRED ADJUSTMENTS TO CONNECT TO EXISTING UTILITIES. IF INDICATED POINTS OF CONNECTION CANNOT BE MADE TO EXISTING UTILITIES AS FOUND, THE CONTRACTOR SHALL, BEFORE CONTINUING, NOTIFY THE ARCHITECT PRIOR TO INSTALLING ANY WORK WHICH MAY BE AFFECTED. 28 IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VERIFY AVAILABLE SPACES FOR INSTALLING THE WORK. 29 VALVES SHALL BE NIBCO. JENKINS, WALWORTH, STOCKHAM OR EQUAL. SERVICE PRESSURE SHALL BE SUITABLE FOR SERVICE INTENDED. 30 PROVIDE HANGERS AND SUPPORTS AS REQUIRED. PLUMBERS TAPE AND WIRE ARE NOT ACCEPTABLE. 31 CONTRACTOR SHALL AFFIX A MAINTENANCE LABEL TO ALL EQUIPMENT REQUIRING ROUTINE MAINTENANCE AND SHALL PROVIDE THREE COPIES OF MAINTENANCE AND OPERATING MANUALS TO THE OWNER. 32 CONTRACTOR SHALL ARRANGE FOR AND PAY FOR ALL UTILITY METERS AND UTILITY CONNECTIONS. 33 NO HOLES, NOTCHES, BLOCK OUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS UNLESS DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER. 34 THE SEISMIC SHUT OFF SHALL BE INSTALLED SHALL BE MOUNTED RIGIDLY TO THE EXTERIOR OF THE BUILDING OR STRUCTURE CONTAINING THE FUEL GAS PIPING. 35 ACCESSIBLE WATER HAMMER ARRESTERS SHALL BE INSTALLED FOR QUICK -ACTING VALVES. LOCATION AND METHOD OF INSTALLATION SHALL COMPLY WITH THE MANUFACTURER' S RECOMMENDATION. 36 WRAP THE BUILDING UNDERGROUND COPPER COLD WATER LINE (5 FEET SECTION) WITH VINYL TAPE. 37 CONTRACTOR SHALL COMPLY WITH CPC 2016 CHAPTER 3 SECTION 306 & 307 REGARDING POINT OF DISCHARGE, CHAPTER 6 SECTION 608.3. 608.4 & 608.5 REGARDING PRESSURE RELIEF AND CHAPTER 7 SECTION 704, 710, 711, 713 & 714 REGARDING BUILDING SEWER SYSTEM. NON- RESIDENTIAL GREEN BUILDING STANDARDS 1. WASTE MANAGEMENT: THE CONTRACTOR MUST SUBMIT TO THE ENGINEERING DEPARTMENT OR OTHER AGENCY THAT REGULATES CONSTRUCTION WASTE MANAGEMENT A WASTE MANAGEMENT PLAN THAT OUTLINES THE ITEMS LISTED IN CGC 5.408.1.1. 2. RECYCLING: A MINIMUM OF 50% OF CONSTRUCTION WASTE IS TO BE RECYCLED. CGC 5. 408.1. DOCUMENTATION SHALL BE PROVIDED TO THE ENFORCING AGENCY WHICH DEMONSTRATES COMPLIANCE. CGC 5.408.1.4. 3. RECYCLING: THE PLANS THAT AN IDENTIFIED, READILY ACCESSIBLE AREA SHALL BE PROVIDED THAT SERVES THE ENTIRE BUILDING FOR COLLECTING RECYCLING, SUCH AS PAPER, CARDBOARD, GLASS, PLASTICS, METALS, ETC. CGC 5.410.1. 4. DOCUMENTATION: A BUILDING -SYSTEMS MANUAL" AS LISTED IN CGC 5.410.2.5 SHALL BE DELIVERED TO THE BUILDING OWNER OR REPRESENTATIVE AND THE FACILITIES OPERATOR. FURTHER, THE "SYSTEMS MANUAL" SHALL CONTAIN THE REQUIRED FEATURES LISTED IN CGC 5.410.2.5.1. 5. POLLUTION CONTROL- DURING CONSTRUCTION, ENDS OF DUCT OPENINGS ARE TO BE SEALED, AND MECHANICAL EQUIPMENT IS TO BE COVERED. CGC 5.504.3. 6. POLLUTION CONTROL- VOC'S MUST COMPLY WITHE THE LIMITATIONS LISTED IN SECTION 5. 504.4 AND TABLE 4.504.1. 5.504.4.1, 5.504.4.2, 5.504.4.3 AND 5.504.4.5 FOR: ADHESIVES, SEALANTS, PAINTS AND COATINGS, CARPET AND COMPOSITION WOOD PRODUCTS. CGC 5.504.4. 7. POLLUTION CONTROL: MECHANICALLY VENTILATED BUILDINGS SHALL PROVIDE REGULARLY OCCUPIED AREAS WITH AIR FILTRATION MEDIA FOR OUTSIDE AND RETURN AIR THAT PROVIDES AT LEAST A MERV OF 8. MERV 8 FILTERS SHALL BE INSTALLED PRIOR TO OCCUPANCY. CGC 5.504.5.3 8. PRIOR TO FINAL INSPECTION. THE LICENSED CONTRACTOR, ARCHITECT OR ENGINEER IN RESPONSIBLE CHARGE OF THE OVERALL CONSTRUCTION MUST PROVIDE TO THE BUILDING DEPARTMENT OFFICIAL WRITTEN VERIFICATION THAT ALL APPLICABLE PROVISIONS FROM THE GREEN BUILDING STANDARDS CODE HAVE BEEN IMPLEMENTED AS PART OF THE CONSTRUCTION. CGC 102.3. PLUMBING FIXTURE SCHEDULE ROUGH - IN SIZE SYMBOL FIXTURE REMARKS W V DCW DHW AMERICAN STANDARD NO. 0355.012 'LUCERNE", WALL HUNG LAVATORY WiTH 3 HOLE DRILL, CHICAGO e LAVATORY (ACCESSIBLE) 2' 2 1/2" 1/2 • FAUCET MODEL NO. 3400-ABCP AND LEONARD THERMOSTATIC MIXING VALVE MODEL NO. 170-LF-BRKT. 1 SETTING HOT WATER OUTLET AT 100F. CONTRACTOR SHALL PROVIDE GRID DRAIN, P-TRAP, AND P- TRAP SAFETY COVER. MAX. FLOW RATE OF 0.5GPM AT 60 PSI. HOT WATER SWILL BE LIMITED TO A MAXIMUM TEMPERATURE OF 11VF. WC AMERICAN STANDARD NO. 3339.128, "CADET 3 FLOWISE" ELONGATED WATER CLOSET (ACCESSIBLE) 4" 2" 3/4" EVERCLEAN SIPHON ACTION JETTED BOWL VITREOUS CHINA FLUSH TANK WATER 1 CLOSET W/ OLSONITE SEAT NO. 95SSC OPEN FRONT LESS COVER. LOW UR 1 URINAL ( ACCESSIBLE) 2' 2" 3/4' AMERICAN STANDARD NO. 6590.525, "WASHBROOK FloWise" ULTRA HIGH EFFICIENCY URINAL VITREOUS CHINA WITH SELECTRONIC URINAL FLUSH VALVE. LOW CONSUMPTION 0.125 GPF. HB HOSE BIBB (REST ROOM) 3/4" ACORN 8104-SSLF W/ VACUUM BREAKER & REMOVABLE LOOSE KEY NO. HANDL eFLOOR DRAIN 3' 2" 1/2- ZURN NO. Z-415S-P, CAST IRON, COMPLETE WITH ROUND NICKEL -BRONZE TOP, CLAMPING COLLAR, TRAP PRIMER CONFECTION AND P-TRAP 1NO. 1901, 6"-B" DEEP, SQUARE CAST IRON ACID RESISTANT ENAMELED, eZURN-- FLOORSINK2' 2" BOTTOM ALUMINUM DOME STRAINER W/ NICKEL BRONZE RIM. GRATE TOP & WITHOUT TRAP PRIMER CONNECTION. BEING USED AS INDIRECT WASTE RECEPTOR FOR THE KITCHEN EQUIPMENTS. ZURN NO. 1901. 6"-8" DEEP, SQUARE CAST IRON ACID RESISTANT ENAMELED, FS q2) FLOOR SINK 2" 2- 1/2" BOTTOM ALUMINUM DOME STRAINER W/ NICKEL BRONZE RIM, GRATE TOP & WITH TRAP PRIMER CONNECTION. BEING USED AS WASTE RECEPTOR FOR WATER RHEATER. PPP MODEL #PR-500 W/ J.R. SMITH COVER. COMPLETE WITH )i- COPPER TPTRAP PRIMER 1/2_ TYPE "L" PIPE TO RECEPTOR (INSTALL PER MANUFACTURER'S 1 RECOMMENDATION). ACCESS PANEL SHALL BE PROVIDED. AMERICAN STANDARD NO. 7745.811, CAST IRON SERVICE SINK WITH REMOVABLE MSMOP SINK 3' 2' 3/4" 3/4" VINYL RIM GUARD & 3" P-TRAP WITH FLAT GRID DRAIN MODEL NO. 7721.038. 1 CHICAGO FAUCET NO. 540-LD897SWXFCP. ET 1 EXPANSION TANK AMTROL ST-12-C; THERM-X-TROL 6.4 GALLONS BFP 1 BACKFLOW PREVENTER ASSEMBLY LINE WATTS SERIES LF009 BACK FLOW PREVENTER. ACCESS PANEL SHALL BE PROVIDED. SIZE WSM 1 WATER SUB -METER 2" NEPTUNE SUB -WATER METER MODEL NO. T-10 WiTH NEPTUNE REMOTE FLOW RATE MONITORING TRICON SMARITROL INSTRUMENTATION. ACCESS PANEL SHALL BE PROVIDED. O 1 WAIL CLEANOUT SEE PLAN ZURN MODEL NO. Z-1446-BP-VP-G W/ CAST IRON BODY, POLISHED STAINLESS STEEL COVER AND VANDAL RESISTANT SCREWS. THESE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC, DEPICTING FUNCTION AND PLACEMENT. PROVIDE OFFSETS IN PIPING AND CHANGES IN FIXTURE LOCATIONS AS NECESSARY TO CONFORM TO STRUCTURAL AND ARCHITECTURAL REQUIREMENTS AND TO AVOID OBSTRUCTIONS. CHANGES TO ACCOMMODATE INSTALLATION OF THIS WORK WITH OTHER WORK, IN ORDER TO MEET ARCHITECTURAL OR STRUCTURAL CONDITIONS, SHALL BE MADE WITHOUT ADDITIONAL COST TO OWNER. GAS BOATER HEATER SCHEDULE MARK SERVICE MANUFACTURER TANK CApACpy INPUT RATE RECOVERY TEMPERATURE RISE A 50TF TANK SIZE HOT WATER OUTLET WEIGHT REMARKS DIA ( IN) HT (IN) MODEL NO. GALLONS) BTUH) GPM) CF) LBS) BRADFORD- WHITE U-75T-80R-3N, 75 GALLON, 75,000 BTUH WH i HOT WATER KiTCHEN EQUIPMENT BRADFORD- WHITE U- 75T-8OR-3N 75 75,000 120 259 GAS WATER HEATER. SET HOT WATER TEMPERATURE AT 12U F. ADD MIXING VALVE AND SEPARATE HW PIPING FOR DIFFERENT TEMP SETTING AS NEEDED. PUMP SCHEDULE MOTOR MARK SERVICE MANUFACTURER FLOW TOTAL REMARKS RPM WATTS VOLTS PH HZ MODELNO. GPM) HEAD FT) cP HOT WATER 8 & G MODEL INSTALL PER MANUFACTURER'S RECOMMENDATION. i CIRCULATING PUMP NBF-12/LW OR EQUAL 8 7 28M 55 115 1 60 PROVIDE TC-1 AUTOMATIC TIME KIT & AQ-1/2 AQUASTAT & TiME CLOCK SOLENOW GAS SHUT-OFF VALVE GAS MARK SERVICE LOCATION MANUFACTURER MODEL NO. PRESS IN PSI) PRESS OUT PSI) CAPACITY CFH) RNARKS Sv KITCHEN GAS GAS DOWN IN WALL TO INSTALL & SIZING OF SOLENOID VALVE PER MANUFACTURER'S RECOMMENDATION. 8 EQUIPMENT PIZZA OVEN, STONE HEARTH ASCO 8042 OR EQUAL 8' WC 8" WC 350 CONTRACTOR SHALL VERIFY & COORDINATE WITH MANUFACTURE TO PROVIDE THE BEST PERFORMANCE OF VALVE TO ACCOMPLISH THE REQUIREMENT IN FIELD. EARTHQUAKE GAS SHUT-OFF VALVE GAS MARK SERVICE LOCATION MANUFACTURER PRESS IN PRESS OUT CAPACITY ROAARKS MODEL NO. PSI) PSI) CFH) INSTALL EARTHQUAKE GAS SHUT-OFF VALVE PER MANUFACTURER'S Eov i EARTHQUAKE SHUT- OFF DOWNSTREAM OF GAS METER PACIFIC SEISMIC PRODUCT VT-314 OR 8 WC 8 WC 590 RECOMMENDATION. CONTRACTOR SHALL VERIFY & COORDINATE WITH MANUFACTURE TO PROVIDE THE BEST PERFORMANCE OF VALVE TO ACCOMPLISH THE REQUIREMENT IN FIELD, PIPE SCHEDULE MATERIALS SERVICE LOCATION vim¢ v oVQ s v 2 QQQ FITTINGS v . Q J O O p QZ C.) Q ABV. FLR. HARRIS BRIDGiT LEAD FREE SOLDERED FITTINGS WATER BEL FLR. HARRIS BRIDGiT LEAD FREE SOLDERED FITTINGS, UP TO 4" BEL FLR. 0 PVC PIPE & FITTINGS, 5" & GREATER WASTE (SANITARY) ABV. FLR. PROVIDE TYLER 2-BAND NO -HUB COUPUNGS BEL FIR. PROVIDE TYLER 4-BAWD NO -HUB COUPLINGS STORM DRAIN ABV. FLR. PROVIDE TYLER 4-BAWD NO -HUB COUPLINGS BEL FIR. PROVIDE TYLER 4-BAND NO -HUB COUPLINGS OVERFLOW DRAINVENT (SANITARY) ABV. FLR. PROVIDE TYLER 2-BAND NO -HUB COUPLINGS BEL FLR. PROVIDE TYLER 2-BAND NO -HUB COUPLINGS INDIRECT INSIDE 0 LEAD FREESOLDERED FITTINGS OUTSIDE 0 LEAD FREESOLDERED FITTINGS WASTE CONDENSATEINSIDE 0 LEAD FREESOLDERED FITTINGS, INSULATED OUTSIDE 0 LEAD FREESOLDERED FITTINGS, INSULATED DRAIN INSIDE0 SCH.. 40 ABS PIPE FITiiNGS GAS BEL GRADE P.E. PIPE AND FITTINGS W/ ELECTRIC FUSION JOINTS PLUMBING FIXTURE UNITS FIXTURE TYPE NO. OF FIXTURES WATER LOAD WASTE LOAD WATER FU PER FIXTURE FIXTURE CW FU FIXTURE HW FU TOTAL WATER FU CW+HW) WASTE FU PER FIXTURE TOTAL WASTE FU WATER CLOSET 2 2.5 5 5 4 8 LAV 2 1 21 2 4 2 4 HAND SINK 3 1 3 3 6 2 6 PREP SINK 1 4 4 4 8 INDIRECT 3 COMP 1 3 3 3 6 INDIRECT MOP SINK 1 31 3 3 6 3 3 GLASS WASHER 1 4 4 4 INDIRECT FLOOR DRAIN 3 4 12 FLOOR SINK 3 4 12 ICE/BEVERAGE/ TEA 3 1 3 3 URINAL 1 5 5 5 4 4 TOTAL 28 19 47 49 WATER CALCULATIONS STREET PRESSURE: 60 PSI MIN. 70 PSI MAX. METER SIZE: 2 INCH 50 GPM FLOW MATERIAL: PVC MAX. VET. ( CW): 8 FPS MAX. VEL ( HW): 5 FPS COLD WATER 12" METER LOSS (PSI) 1 PSI 2 12' STATIC PRESSURE LOSS (PSI) 5.208 PSI 3 RESIDUAL PRESSURE REQUIRED (PSI) 25 PSI 4 PRESSURE REGULATING VALVE (PSI) 15 PSI S BACKFLOW PREVENTER (PSI) 0 PSI 6 TOTAL LOSSES (PSI) 46.208 PSI 7 MINIMUM WATER PRESSURE (PSI) 60 PSI 8 PRESSURE AVAILABLE FOR FRICTION PSI 13.792 PSI 9 ACTUAL LENGTH OF SYSTEM (FT) 100 FT 10 DEVELOPED LENGTH (130A OF ITEM 9) (FT) 130 FT it AVERAGE PRESSURE DROP (PSI/100 FT) IITEM 8/ ITEM 101 X 100 W.6 PSI/1W PIPE SIZE CW SYSTEM HW SYSTEM TANK FU F.V. FU GPM FU GPM 1/2" 3 0 3 3 3 3/4" 12 0 9 8 7 i" 28 0 1 19 16 12 - 1-1/ 4" 56 14 31 28 19 1-1/ 2" 103 35 44 46 27 2" 254 132 76 119 48 CONNECTED GAS LOAD SCHEDULE MARK ITEM CONN. SIZE INPUT CFH CITY. SUBTOTAL CFH WH 1, N)WATER HEATER 1/2" 75 1 75 WATER HEATING LOAD (CFH): 75 VE 0 EN FR -RYE ROTISSERIE ROTISSERIE 1" 3/ 4' 1/2" 3 07 150 2 1 SO 2 4 150 COOKING LOAD ( CFH): 714 RTU-1, 2 RTU-1,2 1 3/4"1 721 21 144 IF TOTAL DEV. LENGTH = 125 FEET TOTAL CFH: 933 CONNECTED GAS LOAD SCHEDULE 1 GAS PIPING SIZED FOR THE TOTAL CONNECTED LOAD 125 FT. FROM METER TO FARTHEST CONNECTION, WITH 0.6 SPECIFIC GRAVITY, 0.5" PRESSURE LOSS IS MIN. PIPE SIZE OF TWO INCHES. 2 GAS PIPING SHALL BE THREADED UNLESS OTHERWISE REQUIRED BY CODE. 3 GAS PIPING SHALL BE TESTED IN ACCORDANCE WITH IFGC SECTION 406 USING 30 PSI OF AIR (IFGC 406.1). 4 GAS BURNING EQUIP. SHALL BE INSTALLED PER NFPA #58 AND NFPA #96. HOT WATER CALM LATIONS ITEM EQUIPMENT QTY. GPH SUB TOTAL 1 .AV 2 5 10 2 -IAND SINK 3 5 15 3 z COMP 11 45 45 4 'VIOP SINK 1 15 15 6 ASSWASHER 1 11.66 11.66 8. ALLOWANCE FOR SINGLE SERVING UTENCILS - 80% 111 RECOMMENDED WATER HEATER SIZE: BTU/HR OUTPUT = TOTAL GPH X 8.34 X DEGREE RISE / THERMAL EFF. TOTAL GPH: 111 DEGREE RISE: 60 THERMAL EFF: 0.8 BTU/HR OUTPUT: 69,385 KW(=BTU/ HR/3412): 20 U 00 Cd O U N C% O - a cd 0 M V¢ a I~ MMM4 J)d O C uW O t. M 37036 Exp. 9- 30-20 cu Ln cu Ld n Z W Q U QQ O . NW Q Ld 0 4 0 EL J ,.._, QJOm_ j J W Q U W LLJ Zc:) W Ldu000_1 a Z Qa I N N 6" W I O W C=Id UW VUPLUMBING NOTES & SCHEDULES Q OF LAKE ELSINORE I i DATE JOB NO BUILDINGIVI I 1012- 2-118 ED IRESCALE DRAWN BY5EE PLAN PLUMBING SCHEDULE. DETAILS & NOTES SCALE: NTS WASTE & VENT PLUMBING PLAN GENERAL NOTES scm E. A. NO PLUMBING PENETRATIONS SHALL BE MADE THROUGH GREASE FILTER PANS ON ROOF. FLOOR PLAN NOTESILCOORDINATEPLUMBINGROUGH -IN AND CONNECTION REQUIREMENTS WITH KITCHEN EQUIPMENT CONTRACTOR E) 4"W SANITARY SEWER POC. PRIOR TO ROUGH -IN WORK. 1D C- RIM OF FLOOR DRAINS SHALL BE LOCATED 1 /2" BELOW INSTALL 1 /2"TP TO RESTROOM FD. FINISHED FLOOR LEVEL. SLOPE FLOOR TO DRAINS. D. REFER TO PLUMBING SPECIFICATIONS FOR FURTHER INFORMATION C)3/4" CONDENSATION PIPE DRAINS TO NEAREST FS. AND REQUIRMENTS FOR PLUMBING CONTRACTOR. PROVIDE INDIRECT CONNECTION W/ AIR GAP LEADING TO ADJACENT FS. E. COMPLY WITH HEALTH DEPARTMENT REGULATIONS. PROVIDE CLEARANCE FOR CLEANING BEHIND AND UNDER EXPOSED PIPING ROUTE WALK-IN COOLER CONDENSATE DRAIN LINE AS HIGH AS AS REQUIRED BY HEALTH DEPARTMENT. CONFORM TO HEALTH POSSIBLE AND ALONG WALLS AS SHOWN. INSULATE ALL CONDENSATE DEPARTMENT REQUIREMENTS FOR LOCATIONS OF FLOOR SINKS. PIPING AND PITCH A MINIMUM OF J" PER FOOT IN THE DIRECTION OF F. PROVIDE ITEMS AND WORK AS REQUIRED TO COMPLETE THE FLOW. SEAL ALL COOLER WALL PENETRATIONS WATER TIGHT AND COVER INSTALLATION OF PLUMBING SYSTEMS TO FIXTURES AND EQUIPMENT: EACH WITH AN ESCUTCHEON PLATE. PROVIDE FULL SIZE TRAP AND TRAPS, STRAINERS, GAUGES, GAS AND WATER PRESSURE EXTEND ABOVE FLOOR AND BEHIND EQUIPMENT FOR AN INDIRECT REGULATORS, FLEXIBLE CONNECTIONS, STOP VALVES, UNIONS, CONNECTION TO ADJACENT FS. ETCETERA. PROVIDE AND CONNECT PLUMBING PIPE FROM ROUGH -INS TO ITEMS AS SHOWN, SPECIFIED, AND REQUIRED. 0 3-COMP INDIRECT DRAIN TO NEAREST FS, SEE CONNECTION DETAILS G. CONTRACTOR IS RESPONSIBLE FOR CONFORMANCE TO ALL ON P-3. LOCAL CODES. H. CLEAN FAUCET AERATORS AND PIPE STRAINERS BEFORE TURNING BUILDING OVER TO OWNER. WH CW/HW \ 16 FU) 1 "HW T FU) T "CW 4 J ( 12 FU) 3/40CW,.. 3/4"CW/HW 1 nHW , MOP - URL 75CFGH ---------- (1 /6 FU) now x 2" GAS ;1 OC7\ a ''I 33CFH 58CFH Q x, x HS 1 /2"CW/HW0 - x1' HS /2 CW/HW 0 144CFH 1 "G UP TO ROOF_ OVEN 1"G 107CFH wG 1w50CFHH—------- 14CFH wGG 20CFH 72 CFH T24pG - I ---- J t WC 3/4"CW r LAV 1 /2"CWAm/ ' \ 7 FU) - \ 3/i7'H t > T"f--------------------I," t w 1 FU) ! i I LAN 1 /2"CW/HW ! j WC 3/4» CW ' 11 i i 4 FU) ( 53/4wCW is 3/4 X.. x.. y x; t =. C i X, hr; r WATER & GAS PLUMBING PLAN scm KEY NOTES N)2-G POC; VERIFY THE EXACT LOCATION OF NEW GAS METER IN FIELD .AND PROVIDE LINE SIZE EARTHQUAKE GAS SHUT—OFF VAL:V,.. Q3/4" G. DN. IF BALL ROUGH —IN do CONNECT TO GAS WATER HEATER T0I LINE SIZE GAS SHUT—OFF VALVE 1-1 /2"CW POC :PITH WATER SHUT—OFF VALVE IN ACCESS PANEL VIF. ROUGH —IN do CONNECT TO BEVERAGE DISPENSER AN. UEVERAGE ICE MAKER HEAD. INSTALL MOP g W/ BFP. CARBONATED SYSTEM SOFT DRINK DISPENSER. ICE MACHINE do TEA BREWER WATER LINES (MUST BE NON —COPPER WATER LINES AFTER RPP DEVICE) SHALL HAVE APPROVED REDUCE PRESSURE PRINCIPLE(RPP) DEVICE OR OTHER DEPARTMENT APPROVED ANTI-SIPHONAGE DEVICE ITrC)FLAKE-ELSINORE Ul0 N CU 1 00 cd o O CNI 0% t Mai y U O -a Ate° cd U M 0% U° av a N WH u* woluCM Il) N LIJ ON Z LLi i U 1 ON LL. I Q Lj 0 J I —I J H p-10 PQ Ld W Q W WLd f-- I Y LZ ppIDQOi o N In W N L O WU W U Vq j 1 PLUMBING PLAN 10/22/ 18 1= v SCALE DRAWN BY 5EE PLAN TYPICAL FIXTURE 0 1" HW OUT 1" CW IN 1" HW OUT ELMDOR/STONEMAN, MODEL PIPE THRU ROOF SHUT-OFF VALVE COLD WATER SUPPLY 1/4 TURN BALL 1100-4 SEALANT SHALL BE VALVE APPLIED AROUND PIPE OPENING INSTALL (3) VANDAL- THRU COUNTER FLASHING PROOF SET SCREWS INSULATED PIPING CHECK VALVE ASME T&P RELIEF FOR WATER TIGHT SEAL TRAP PRIMER FINISHED VALVE. TERMINATE THERMAL WALL DISCHARGE FULL SIZE EXPANSIONAPPLYPERMASEALWATER OF VALVE CONNECTION PROOFING COMPOUND TANK TO MOP BASIN VACUUMAROUNDPIPE, COUNTER FLASHING SLEEVE & FLASHING FLOOR DRAIN FIXTURE DRAIN BACKING PLATE RELIEF ADJACENT FOR WATER TIGHT SEAL.. BY VALVE GAS TANK TYPE 2" MIN. CONTRACTOR DIELECTRIC WATER HEATER SEAMLESS LEAD FLASHING OVER " 12 MIN. FINISHED FI- OFF -SET GRID STRAINER UNION (TYP) FOR SEISMIC APPLICATIONS: STEEL REINFORCED BOOT BOOT PROVIDE 1/8" THICK X 2"W. 22 HEIGHT 8" MIN. BUILT-UP ROOFING 5" MIN. 1/2" (SOFT 'K" COPPER TRAP PRIMER FITTING NO OJOIN SSUN ER FLOOR) Z WATER GA. STEEL STRAP SECURED TO HEATER 3/8" THICK X 6"W. STEEL PLATE PLATFORM ANCHORED TO MINIMUM (4) SEE PIPE N STUDS 2"0 ANCHOR BOLTS P-TRAP' OR LAG SCREWS ( NUTS AND PARALLEL TO BOLTS FOR STEEL STUDS) FLOOR WATER HEATER SHALL 1. FLOOR DRAINS & FLOOR SINKS SHALL BE PROVIDED W / STRAPPED TO THE TRAP PRIMERS WITH ACCESS PANELS BUILDING AT THE 2. ALL PIPE PENETRATIONS SHALL HAVE ESCUTCHEONS FAUCET 1/3-POINT TOP AND BOTTOM ,. PIPING THROUGH 14 DRAIN TRAP PRIMER 11 HEATER DETAIL i 1NTs. NT s. N s- ROOF DETAIL DETAIL WATER FROM CW SUPPLY 1/2"CW TAKE -OFF ISOLATION TO HEATER, NO TOP OF BRANCH BALL VALVE INTERVENING MAIN VALVES SHUT OFF VALVE. (TYP.) ISOLATK)N VALVE EXTERIOR WALI- LEFT/RIGHT NIPPLE HOT WATER COLD WATER PIPE PIPE. WELDED STEEL TRAP PRIMER VALVE EXPANSION TANK WITH LEFT/RIGHT OFF -SET STRAINER. POLYPROPYLENE LINING,,. FDA APPROVED FOR VACUUM BREAKER COUPLING PORTS WATER —f NIDOMESTICUNION: PROVIDE UNIONJI VALVE P-TRAP' WITH CN:IFSERVICEDIELECTRIC REQUIRED FOR MOUNTING HEIGHT FOR REMOV 1'-0" PER 20 FT OF4" DCW OM ABV8-5/8 SECURED ESCUTCHEON DISSIMILAR METALS TP LENGTH W/ VACUUM O ®eOUTLETRBELWR1/2" TIP LINE TO TRAP INTEGRAL NORMALLY CLOSED FILL TANK WITH AIR PRESSURE TO BUTYL ACCESS PANEL ® PRIMER INLET CONNECTIONS CONCEALED A FLOOR DRAIN. TYPSTOPSOLENOIDVALVEMATCHWATERDIAPHRAGMLOCATION NOTE: PRESSURE, THEN FINISH FLOOR PROVIDE AND INSTALL HANDY -SHIELD P-TRAP (DRAIN) SAFEEY OPEN VALVE COVER (PART #3012) AND WHEELCHAIR OFFSET TAILPEICE COVER STAINLESS STEEL BOX PART #3042) ON LAVATORY. COLOR SHALL BE IVORY. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. MAKE PIPE JIBLOCKINGDOORNOTE: ELECTRICAL CONNECTION ACCESS PANELS SHALL PROVIDE AND INSTALLL HANDY -SHIELD VALVE AND WATER SUPPLY SAME SIZE AS TANK FITTING. FOLLOW FIRE RATED ACCESSEPANLELJO BE FIRE RATED WHEN SAFETY COVERS ON LAVATORY. IVORY COLOR. HANDY -SHIELD PART MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION REQUIRED AT FIRE REQUIRED. 3022 PROCEDURE. VERIFY PROPER OPERATION WHEN PER 2010 COC. SE INSTALLED. RECESSED HOSE BIBB SCALE EMERGENCY GAS SHUT—OFF VALVE SCALE SCALE SCALE TRAP PRIMER IN ACCESS SCALE N.T.S. N.T.S. N.T.S. N.T. N.T.S. ASSEMBLY DETAIL 15 IN ACCESS PANEL DETAIL 12 ADA LAVATORY COMPLIANCE 8 EXPANSION TANK DETAIL 5 PANEL DETAIL 2 COUNTERSUNK CLEAN -OUT PROVIDE SCREWED WASTE OR VENT TO COUNTER-SINK WITH HEAVY DUTY ABOVEPLUGBRONZEPLUGFOR FLANGED HOUSING AND CLEANOUT TEE Oj COVER , "J.R. SMITH" 4253 FINISHED MOUNT TOP OF BOX FLUSH WITH TAPPED THREAD & TEE PLUMBING WALL OR 3 COMP SINK VENT GRADE _ FINISHED GRADE I} ALLCOMPOUND COLUMN REFER TO ACCESS HOUSING & ESCUTCHEON PLATE FLOOR PLANS COVER SET FLUSH NSTALL CAULKING I III=I r AT PROVIDE WITH FINISHED FERRULE AND RAISED SURFACE. INSTALL IN PLUGIIIWATERPROOFINGHEADSCREW IN POT SINK, SCULLERY SINKS, CONCRETE FL FLOOR, SIDEWALKS AREAS WHERE SURFACE DISHWASHING SINKS, COMMERCIAL AND DRIVES MI IE DISHWASHING MACHINES AND OTHER SAME SIZE AS 24"x 18"x 6' SIMILAR FIXTURES SHALL BE II I II II I I I I II RISER MAIN WITH 4" ==' " CONCRETE PAD OR CONNECTED DIRECTLY TO SEWER LINE. LENGTH AS ins &WSPEYAMEMAXIMU EQUIREDAFLOORDRAINSHALLBEPROVIDED CAST-IRON RISER 4" THICK LONG SWEEP A DIRECTION END OF LINE OR — SIZE AS MAIN WITH i • ADJACENT TO THE SINK. THE CONCRETE RI TEMP EARTH FILL COMBINATION WYE OF FLOW SEE PLANS }•.• "c= 1 A 1 OF FLOOR FIXTURE SHALL BE LOCATED AT THE PAD AROUND RISER FOR AND EIGHTH BEND FOR SIZE r•.- CONCRETE AROUND SEWER SIDE OF FLOOR DRAIN THERE IN RUN OF MAIN AND ; ' s ? FITTING FOR ANCHOR FLOOR DRAIN AN SHALL BE NO OTHER FIXTURES ROUTISUPPORTDOUBLE1+7, BETWEEN THEM PER CPC SECTION PIPING •'• PIPING CLEANOUT FITTING FLOWNOTE: Y!. SEE PLANS FOR PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SIZE MAIN AND SANITARY WASTE BRANCHES NOT SERVED WITH A FLOOR ROUTING OF PIPING TO GREASE WASTE PROVIDE 1/8 SEWER PIPE (TYP.) CLEANOUT: LOCATED ABOVE FIXTURE FLOOR RIM WITHIN 4'- 0" OF FLOOR. CONSULT LOCAL CODES FOR OTHER NOTE: IAPMO LISTED 2-WAY ONLY BEND AT END WCO REQUIREMENTS. OF LINE ( SCALE SCALE SCALE SCALE 3 COMPARTMENT SINK CONNECTION DETAIL 13 CLEANOUT TO GRADE DETAIL 9 WALL CLEANOUT DETAIL 6 TWO—WAY 6EANOUT DETAIL 3 N.T.S. N.T.S. N.T.S. N.T.S. 1/ 2 GRATE OR 3/4 GRATE 7" DIA FINISH FLOORING POLISHED BRONZE BRONZE TAPER THREAD PLUG 7 VANDALPROOFT [-WITH COUNTER SUNK HEAD FLUSH WITH SEALANT NICKEL BRONZE STRAINER 12 SQ. IN. r • FLOOR LI 2" FINISHED FLOOR I FREE AREA CONCRETE SLAB OR FINISHED FLOOR e .. 45' WYE AND )6 BEND DOME STRAINER 1 1/2- V PIPE FITTING OR WASTE LINE LENGTH TO SUIT STANDARD ROUGH FS DRAIN COMBI FITTING C.I. BODY 2" WASTE PIPE TAIL PIECE I r, P- TRAP GRATE I FLOW FLOW SEE PLANS FOR SIZE MAIN AND ROUTING OF BODY - SMOOTH PIPING INTERIOR WALL SURFACE NOTE: NOTES: CLEAN - OUT TO BE J.R. SMITH MODEL 1. PROVIDE VENT UNDER SLAB. CONTINUE 4023S SERIES OR EQUAL INSTALLATION TO NEAREST WALL '1S SHOWN AND UP TO SHALL BE FLUSH WITH SURROUNDING VENT STACK. PROVIDE TRAP SEAL HUB OUTLET FLOOR SURFACES PROTECTION. 2. WASTE SIZE PER SCHEDULE SCALE SCALE FLOOR CLEANOUT DETAIL 10 FLOOR DRAIN DETAIL 7 FLOOR SINK DETAIL 4 NTES- N.T.S. s- uITY L R w-n* V I 3 ci- D cu Ln cu Lv 0N Z Lil Q U QQ O N Lli Q J n 1 I _ H OJp( J W U C:) WL,J ZWM H Y W u'- 4 Q O Z o I o w I c W cmUv i PLUMBING DETAILS 10/ 22/18 SCALE DRAWN BY 5EE PLAN STORE NO. DRAWING W. PLAN CHECK NOTES 1 PROVIDE MULTI -LEVEL LIGHTING CONTROLS AS REQUIRED BY SECTION 130.1(b). 2 PROVIDE AUTOMATIC DAYLIGHTING CONTROL TO COMPLY WITH THEFOLLOWINGINSTALLATIONANDOPERATIONSREQUIREMENTS. FOR LUMINAIRES IN PRIMARY SIDELIT DAYLIT ZONES, AUTOMATIC DAYLIGHTING CONTROLS SHALL BE INSTALLED AND CONFIGURED TOOPERATEACCORDINGTOALLOFTHEFOLLOWINGREQUIREMENTS: PHOTOSENSORS SHALL BE LOCATED SO THAT THEY ARE NOT READILY ACCESSIBLE TO UNAUTHORIZED PERSONNEL, AND THE LOCATION WHERE CALIBRATION ADJUSTMENTS ARE MADE TO AUTOMATIC DAYLIGHTING CONTROLS SHALL NOT BE READILY ACCESSIBLE TO UNAUTHORIZED PERSONNEL. ACCESS TO CONTROLS CAN BE LIMITED BY PLACING LOCKS OR SCREWS ONENCLOSURESONENCLOSURESORUNDERACOVERPLATESOATOOLORKEYISNEEDTOGAINACCESS. ram+` S(Override) = LIGHTING OVERRIDE SWITCH, AT FRONT DOOR. TC = LIGHTS TIME CLOCK WITH OVERRIDE ON/OFF CONTROL DESIIGp NON EMERGENCY LIGHTING CIRCUITS SHALL BE CONTROLLED BY 24 HR TIME CLOCK THROUGH MULTI -POLE CONTACTOR. OVERRIDE SWITCH TIME CLOCK 42- HOUR TIMER SWITCH 120V AC TS r— C LTG CKT TO LIGHTS LTG CKT p---- TO LIGHTS LTG CKT TO LIGHTS LTG CKT TO LIGHTS LTG CKT TO LIGHTS LTG CKT TO LIGHTS LIGHTING CONTROL DIAGRAM GENERAL. NOTES 1. ALL CABLES ARE #12AWG CU IN 3/4" EMT U.O.N.. HASH MARKS INDICATE HOT AND NEUTRAL CABLE COUNT. INCLUDE ADDITIONAL #12 GROUND CONDUCTOR. 2. NEUTRAL SHARING BETWEEN 2 OR MORE CIRCUITS IS NOT ALLOWED UNLESS A MULTI —POLE BREAKER IS USED. 3. ALL EXIT SIGNS SHALL BE UNSWITCHED. ALL LIGHTING WITH EMERGENCY BATTERY BACK UP OR INVERTER POWERED SHALL BE SWITCHED BUT WIRED SUCH THAT A POWER FAILURE WILL CAUSE THE LIGHTS TO GO ON REGARDLESS OF LIGHTING CONTROLS. PROVIDE SEPARATE CONDUIT & BOXES FOR EMERGENCY INVERTER CIRCUIT. PROVIDE UNSWIfCHED HOTSFOROUTAGESENSING. 4. LABEL JUNCTION BOXES OF THE PANEL AND CIRCUIT USED TO FEED THELIGHTINGFIXTURES. AS BUILTS SHALL REFLECT AND SHOW THE CIRCUITUSEDBYEACHFIXTURE. PROVIDE UPDATED PANEL SCHEDULE ONPANELBOARDUSED. 5. ALL NEW LIGHTING FIXTURES, LIGHT SWITCH COVERPLATES, EXIT SIGNS SHALL MATCH ARCHITECTURAL DECOR. PROVIDE PRODUCT SUBMITTAL FORARCHITECTANDOWNERAPPROVAL. 6. LIGHT FIXTURES IN CONTACT WITH INSULATION SHALL BE U.L. LISTED FOR THERMAL BARRIER OR BE PROVIDED WITH 3' MINIMUM CLEARANCE. 7. LIGHTS AND PANELS SHALL NOT BE RECESSED IN FIRE RATED ASSEMBLIES UNLESS BOXED WITH EQUIVALENT CONSTRUCTION. 8. ALL WIRING AND LAMPS IN HIGH TEMPERATURE HOOD OR IN OTHER AREAS SUBJECT TO HIGH TEMPERATURES SHALL BE RATED FOR THATUSAGE. 9- COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO ROUGH —IN. VERIFY EXACT LOCATIONS AND MOUNTING HEIGHTS FOR ALL FIXTURESANDDEVICESPRIORTOROUGH —IN. 10. PROVIDE SEPARATE SWITCH AND SEPARATE OVERRIDE BUTTONS FOR EACHZONE. 11. ROUTE ALL LIGHTS THROUGH LIGHTING CONTROL PANEL EXCEPT THOSE WITH OCCUPANCY SENSOR CONTROLS. PROVIDE LC&D BLUE BOX OR EQUAL. PANEL SHALL BE PROGRAMMED TO AUTOMATICALLY SWEEP OFF ALL LIGHTING AFTER BUSINESS HOURS. COORDINATE FINAL LOCATION WITH ARCHITECT. PROVIDECOMPATIBLEOVERRIDESWITCHES. 12• PROVIDE NEUTRAL AT ALL LIGHTING CONTROLS. 13. PROVIDE EMERGENCY LIGHTS TO PROVIDE A MINIMUM OF 1 FOOTCANDLE FOR 90 MINUTES AT FLOORLEVEL FOR EMERGENCY EGRESS. KEY NOTES j OVERRIDE SWITCH. O NOT USED. LIGHTING CONTROL SHALL BE LIGHTING CONTACTOR AND ASTRONOMICAL TIME CLOCK. NOT USED. SECONDARY DAYLIg4T ZONE O CONNECT EMERG AND EXIT SIGNS TO ROOM LIGHTING CIRCUIT, AHEAD OF SWITCH/DIMMER. NOT USED. O7 PROVIDE LED CEILING MOUNTED ABOVE WALK—IN COOLER FOR MAINTNANT. RIMARY DAYLIGHT ZONE SYMBOLS LIST I 120V 10 20A GROUNDING TYPE COMMERCIAL GRADE DUPLEX RECEPTACLE 120V 10 20A GROUNDING TYPE COMMERCIAL GRADE DUPLEX GFI RECEPTACLE, PROVIDE GFI TYPE AT ALL FOOD/BEVERAGE PREPARATION AREAS, KITCHEN, EXTERIOR LOCATIONS, AND WITHIN 6' OF ALL SINKS. E)- SPECIAL RECEPTACLE, GROUNDING TYPE WITH VOLTAGE/PHASE/AMPERAGE RATINGSASINDICATED Sm MOTOR RATED 120V DISCONNECT SWITCH 3/4" CONDUIT - W/CABLES (COUNT PER HASH MARKS). SIZE #12 U.O.N.. ABSENCE OF HASH MARKS INDICATES 2#12 U.O.N.. BRING SEPARATE NEUTRALFOREACHINDIVIDUALCIRCUITUNLESSMULTI -POLE BREAKERS ARE USED. PROVIDE AN ADDITIONAL #12 (OR LARGER AS NOTED) GROUND PER CONDUIT. COPPER ONLY, THHN/THWN, CABLE MIN. RATING 70' OR AS NOTED. Now NEW PANELBOARD. SEE SINGLE -LINE DIAGRAM FOR DETAILS AND SPECIFICATIONS. O THERMOSTAT BY MECHANICAL, ELECTRICAL TO PROVIDE 3/4"C-W/ CONTROL CABLES AND FINAL CONNECTION. ECG' FUSED HEAVY DUTY DISCONNECT JO Q J-BOX VAPOR PROOF LIGHT TELEPHONE LINE ( SINGLE GANG DEVICE RING REQUIRED ) W/CONDUIT TO TBB a DATA LINE ( SINGLE GANG DEVICE RING REQUIRED ) W/CONDUIT TO DATA P.O.C. 0 2-HOUR AFTER HOURS LGHTINGOVERRIDE SWITCH, PROVIDE CONDUIT/CABLE TOLIGHTINGCONTROLPANEL WS WATTSTOPPER DW-200 DUAL RELAY COMBINATION WALL SWITCH/OCCUPANCYSENSOR OS WATTSTOPPER DUAL RELAY CEILING OCCUPANCY SENSOR So MANUAL LIGHT TOGGLE SWITCH 2OA, 125V, RATED. LETTER INDICATES SWITCHLEG. MANUAL LIGHT TOGGLE SWITCH 2OA, 125V RATED. 3-WAY LCFIIIIIIIIIIIIIIIIii LIGHTING CONTROL PANEL INV COMPACT EMERGENCY INVERTER DL DAYLIGHT ZONE ..SENSOR, INTEGRATE INTO LIGHTING CONTROL SYSTEM. DM DIMMER BANK: a,b,c... INDICATE DIMMER, NUMBER OF LETTER INDICATE NUMBER OFDIMMERS. WMINAIRE SCHEDULE TAG SYMBOL MANUFACTURER MODEL NUMBER VOLTS LAMPS WATTS MOUNTING L1 LUNERA LIGHTING 24G6-40K-10V—IN 2'X4') 120 1) 4OW LED 40 GRID RESTORATION GLASS FILAMENT HARDWARE LIGHTING: INDUSTRIAL CAGE PENDANT 6806.0284, POLISHED NICKEL 120 1) `IOW TUNGSTEN 40 PENDANT` LIGHTING: INDUSTRIAL CAGE PENDANT L3 O RESTORATION7 6806.0527 PN W/ BULBRITE NOS40-1910 HARDWARE #134-019 120 3) 4OW TUNGSTEN 120 PENDANT ` L4 O H2721CAT HALO CAN LAMP: 26W LED TRIM 493WBS06 120 1) 26W LED 26 RECESSED COOPER LIGHTING GU24W—SP LAMP ECO—PAR-38—GU24-15—WW-50 120 15W PAR 38 LED 15 SURFACE W Y UTHONIA LIGHTING TRACK AND LED HEADS i 120 15W PAR 38 LED 15 SURFACE X MULE LIGHTING EXIT SIGN MDC—I—G—A—A 120 2) 3W LED INCLUDED S SURFACE EXE MULE LIGHTING EXIT SIGN MDC—I—G—A—A 120 2) 3W LED INCLUDED 6 SURFACE EM LITHONIA LIGHTING s REMARKS USE BATTERY BACK—UP OPTION FOR EMERGENCY LK;HT. BATTERY PACKS SHALL PROVIDE FULL LUMEN OUTPUT FOR A MINIMUM OF 90 MINUTES. BOTTOM OF FIXTURE 0 8' A.F.F. BOTTOM OF FIXTURE • 10' A.F.F. RECESSED CAN WITH DIMMING CAPABILITY. PROVIDE BACKUP BATTERIES FOR EMERGENCY FIXTURES AS INDICATED. BATTERY PACKS SWILL PROVIDE FULL LUMEN OUTPUT FOR A MINIMUM OF 90 MINUTES. PAINT LAMPHOLDER TO MATCH ROOF DECK/SCRIM. USE CEMRAL OR LOCALIZED INVERTER SYSTEM FOR EMERGENCY BACK-UP. WALK—IN COOLER LIGHT EXIT SIGN WITH 90 MINUTE BATTERY BACKUP 2) HEAD EXIT SIGN / EMERGENCY EGRESS COMBINATION WITH 90 MINUTE BATTERY BACKUP m L O U L 4 LI U Z L,J U Q ON Ld LLI 40- H ZH OJO Q u - W LLII- o lZ (y)Y U 0J v 0 S cr W C LLJ UW U V LIGHTING PLAN STORE NO. DRAWING NO. E1.0 PANEL "A1" (EXISTING) 0 VOLTSA20/208V PHASE: 3 MIN, A.I.C. RATING: 42,000A MAIN: M.L.O. MOUNTING: SURFACE WIRE: 4 BUSSING: 400 AMP LOAD 1'IA-VA B-VA C-VA_ BKR CT` CTIBKR A -VA B-VA C-VA * LOAD HOLDING CABINET-87 K 1700 15/1 1 21 2011 720 R RECEPTACLES ROOF TOP REC R l 540 23/1 3 4" 2011 180 R OFFICE RECEPTACLES KITCHEN 52.1 K I 800 23/1 5 6s 2011 720 R OFFICE RECEPTACLES LIGHTING CONTROL PANEL R ` 200 23/1 7 8 20/1 360 R OFFICE RECEPTACLES MIXER 19 K ; 1140 23/2 9 10 20/1 600 K DECK OVEN-36 K I 1140 11 12 i 200 K SHUNT TRIP HOT WATER HEATER R 816 2311 13 141- 2011 SPARE REVERSE OSMOSIS SYSTEM R 180 2311 15 16 20/1 1 1200 R KITCHEN ITEMS FIRE SUPPRESSION_ R 200 23/1 17 181 20/1 1080 R RECEPTACLES REFRIG CASE 85 R! 1100 23/1 19 120 100/3 6365 P PANEL A2 J BEV DISPENSER-56 K 672 23/1 21 22 6097 P SPARE 23/1 23 24 6228 P W/l COOLER CONDENSER M 1500 23/2 25 26. 20/1 1100 R WARMER M 1500 271 28 15/1 1128 K REFRIG CASE-49 ICEMAKER-57 K 4404 2312 29 30i 15/1 9361 K SANDWICH CASE-45 K I 1404 31 32 1511 360 K SANDWICH CASE-43 ICE TEA BREWER-61 K K 1800 600 23/1 23/1 33 35 34 i 36 15/1 30/2 1056 K SANDWICH CASE-44 BAG-N-BOX-13 2300 K HEATED DOUGH PRESS-33' 23/1 371 381 1 2300 K POS RECEPTACLE R 180 23/1 1391 1401 20/1 1 3601 1RIRECEPTACLES POS RECEPTACLE R 180 23/1 41 421 15/1 396 K FOOD WAMER-60 PHASE TOTALS: 17925 16633 15184 50742 =TOTAL CONNECTED LOAD,VA FOR DEMAND LOAD SEE BELOW) _. PHASE AMPERES: i149,31 138.5, 134.8 DEMAND LOAD CALCULATION: NOTES: L=LIGHTING LOADS: 1.25 X 3829 4786 VA C=CONTINUOUS LOADS, OTHER: 1.25 X 0 0 VA M=MOTOR LOADS (INCL LGST): 1.00 X 8221 8221 VA LARGEST, VA: 0.25 X 3000 750 VA R=RECEPTACLES: 1ST 1OK: 1.00 X 10000 10000 VA BALANCE: 0.50 X 2416 1208 VA K=KITCHEN LOADS: QTY: 18 0.65 X 26276 17079 VA N=NONCONTINUOUS LOADS, OTHER: 1.00 X 0 0 VA P=PANEL, INCL. IN ABOVE) - TOTAL N.E.C. DEMAND LOAD = 42044 VA = 116.7 AMPERES PANEL A2 NEW VOLTS 120/206 PHASE: 3 A.I.C. RATING: 42,000A MAIN: MLO M01 INITIN('-RI IRFA( F- WIRE' 4 FUl_I_Y RATED BUSSING' 125A LOAD A -VA B-VA C-VA BKR CT CT BKR A -VA B-VA C-VA * LOAD DINING RM LTS iL 650 20/1 1 2 201 200 L TIME CLOCK & COVTACTOR DINING RM LTS L 285 20/1 3 4 20.'1 1000 L STORE SIGNAGE DINING RM LTS_- - _... .. REST RM LIGHTS L T 500 240 20/1 20/1 5 7 6! 20'1 8 201 1 150 500 L L W/l COOLER LIGHTS/HTR KITCHEN HOOD LIGHTS ITCHEN LIGHTS LVITCHENHOODEF-3 i M 304 20/1 9 10 20111100 R SHOW WINDOW RECEPT 1208 20/1 11 12 2011 1'00 R SHOW WINDOW RECEPT KITCHEN HOOD EF-4 M 1265 20/1 13 14 201 1100 iR SHOW WINDOW RECEPT KITCHEN HOOD MAU-1 im 1748 2511 15 161 201 1000 M AIR CURTAIN - - ROTISSERIE K SHU NT TRIP ,K 200 880 20/1 17 19 181 20211201 __ 1600 K K GLASSWASHER 21 221 201 660 K KEG DISPENSER 23 25 24 20'1 26 201 700 700 K K REFRIGERATOR ICHILLER 27 28 31 1321 33 34 35 36 37 381 SPARE 39 41 4 01 42 1 PHASE TOTALS: 16365 6097 6228 18690 =TOTAL CONNECTED LOAD,VA (FOR DEMAND LOAD SEE BELOW) 51-917PHASEAMPERES: - 53.0 50.8 51.9 DEMAND LOAD CALCULATION: L=LIGHTING LOADS: 1.25 X 3829 = C=CONTINUOUS LOADS, OTHER 1.25 X 0 = CESSED DUPLEX M=MOTOR LOADS (INCL LGST): 1.00 X 5221 = ETS @ +72" A.F.F LARGEST, VA: 0.25 X 1748 = TV MONITORS R=RECEPTACLES: 1ST 1OK: 1.00 X 3300 = BALANCE: 0.50 X 0 = K=KITCHEN LOADS: CITY: 5 0.70 X 6340 = N=NONCONTINUOUS LOADS, OTHER: 1.00 X 0 = P=PANEL, INCL. IN ABOVE) TOTAL N.E.C. DEMAND LOAD = A A 4786 VA 0 VA 5221 VA 437 VA 3300 VA 0 VA 4438 VA 0 VA 18182 VA = 50.5 AMPERES FAI GENERALNOTES 1. ALL 120V 15A & 20A CIRCUITS IN THE KITCHEN AND,ALL OTHER FOOD & BEVERAGE PREPARATION AREAS SHALL HAVE GROUND FAULT PROTECTION. PROVIDE GFCI RECEPTACLES. PROVIDE GFCI CIRCUIT BREAKERS FOR ALL HARD WIRED CIRCUITS. THIS INCLUDES APPLICABLE CIRCUITS IN THE KITCHEN, B.O.H. AND DINING AREAS. 2. ALL RECEPTACLES WITHIN 6' OF A SINK OR OTHER WET LOCATION SHAD_ BE GFI TYPE. 3• ALL GFI RECEPTACLES SHOULD BE ACCESSIBLE. WHERE THEY ARE NOT, PROVIDE GFI BREAKER IN LIEU OF GFI AT RECEPTACLE. 4- SEE NOTES ON SHEET E1 AND KITCHEN PLANS FOR ADDITIONAL REQUIREMENTS. 5. SHARING NEUTRALS BETWEEN 2 OR MORE CIRCUITS IS ONLY ALLOWED WHERE MULTIPOLE BREAKERS ARE USED. 6• PROVIDE GROUND WIRE PER CEC 2016 IN EACH BRANCH CIRCUIT FEEDER. 7. PROVIDE READILY ACCESSIBLE MEANS OF DISCONNECT FOR ALL ELECTRICAL POWER WITHIN UNE OF SIGHT OF EQUIPMENT. CODED NOTES 1< ELECTRICAL PANELS. SEE SINGLE-UNE DIAGRAM FOR SPECIFICATIONS. 2 PROVIDE FIRE ALARM PULL STATION BOX. 3 WALK-IN COOLER/FREEZER MAY REQUIRE ADDITIONAL ELECTRICAL CONNECTIONS. USE PROVIDED CIRCUITS. SEE MANUFACTURER'S INSTALLATION MANUAL. OPROVIDE SHUNT TRIP BREAKERS FOR OVEN AND HOOD LIGHTS AND INTERCONNECT WITH THE FIRE PROTECTION SUPPRESSION CONTROL PANEL FOR AUTOMATIC SHUT -DOWN DURING A FIRE. OINTERLOCK ROOFTOP MAKE-UP AC UNIT WITH FIRE SUPPRESSION SYSTEM TO PROVIDE SHUT -DOWN DURING AFIRE. INTERLOCK HOOD EXHAUST FAN TO STAY ON DURING A FIRE. PROVIDE CONTROL CABLES AS NEEDED. INTERLOCK GAS SHUT OFF WITH FIRE SUPPRESSION SYSTEM FOR AUTOMATIC SHUT OFF DURING A FIRE. 6 PILOT LIGHT SWITCH FOR HOOD EXHAUST FAN, MAKE-UP AIROUNIT (MAU) FAN(S) AND HOOD LIGHTS. PROVIDE CONTROL CABLING AS REQUIRED. VERIFY EXACT LOCATION WITH THE ARCHITECT. 7 PROVIDE ISOLATED GROUND FOR POS CIRCUITS. 8 INTERLOCK EXHAUST FAN WITH REST ROOM LIGHTS. 9 CONNECT WALK IN COOLER TO COMPRESSOR PER MANUFACTURER'S RECOMMENDATIONS. COORDINATE COMPRESSOR'S ROOF LOCATION WITH THE ARCHITECT. 10 ROOF TOP WP/GFI RECEPTACLE. , ki SINGLE LINE DIAGRAM CITY OF LAKE GENERAL NOTES B U I L IN 1. PROVIDE GFI BREAKERS FOR ALL 120V 15A AND 20A HARD G WIRED CIRCUITS TO EQUIPMENT IN FOOD AND BEVERAGE` RNAl- PREPARATION AREAS AS APPLICABLE IN THE KITCHEN, DINING AND B.O.H.. 2. PROVIDE MUTTI-POLE BREAKERS FOR ANY MULTI -WIRE BRANN CIRCUITS UTILIZING A SHARED NEUTRAL CONTRACTOR To FIELD VEPoFY EXISTING BUILDING MAIN SWITCHBOARD AND FEEDER BREAKER SIZE TO THIS SUITE s cr-' No. Ell 09/30/20 cly. t4CTR 9jFOF CALU U U W Z _ W Q i U J O J H OJO J T Q UpqL'J F-WW W (y) U 0J a N 4 o W C O W U W ULLJU 0- m I 1®1 DRAWN BY STORE NO. DRAlI11INC NO. E2,0 E Q U I P M E N T S C H E D U L E NO QTY EQUIPMENT CATEGORY MANUFACTURER MODEL NUMBER W U- C Z n w Ld Z o Of Z D C_ Q I.- Y >> Ld Q i X D a J Q U1-1 OfZ U wQ z z 1 1 AIR CURTAIN, UNHEATED CURTRON AP-2-36-1-SS X 120 1 X 88 5-15P 1 3 1 WATER HEATER GC AO SMITH BTH-120 X 6.2 120 1 X VFY 3 6 1 FAX MACHINE OWNER X 15A 120 1 X 58 6 7 1 COMPUTER OWNER X 15A 120 1 X 58 7 8 1 COMPUTER PRINTER OWNER X 15A 120 1 X 58 8 9 1 COPIER OWNER X 15A 120 1 X 58 9 13 1 BAG IN THE BOX RACK & REGULATORS VENDOR X 5.0 120 1 X 84 13 19 1 30 QT. MIXER GLOBE SP30P X 15 220 1 2.0 1 X 48 19 28 1 WALK-IN COOLER KOLPAK X 6.0 120 11 X 1 1112 28 29 1 REFRIGERATION POWER PAK KOLPAK PC099TS X 8.5 208-230 1 1.0 X 48 29 33 1 DOUGH PRESS, MANUAL DOUGH EXPRESS DTX M 218 X 11.66 2.2K 208 1 X 30 6-30P 33 36 1 PIZZA OVEN, GAS WOOD STOVE FD-9660-RFGLR-IR X 5.0 120 1 X 12 36 37 1 EXHAUST HOOD (PIZZA OVEN) CLASS 11 CAPTVAIR X 3.0 120 1 X 104 37 40 1 OSMOSSIS SYTEM W/WATER FILTER EVERPURE EV9970-07 X 15A 120 1 X 84 40 42 1 FIRE SUPPRESSION SYSTEM CAPTVAIR ANSUL X X 84 42 43 1 48" SANDWICH TOP REFER W/ 4 DRAWER 3 MIGALI C-SP-48-18BT X 2.9 115 1 0.2 X 18 5-15P 43 44 1 48" SANDWICH TOP REFER (SAUCE) MIGALI C-SP-48-18BT X 7.8 115 1 0.33 X 18 5-15P 44 45 1 48" SANDWICH TOP REFER (TOPPINGS) MIGALI C-SP-48-188T X 7.8 1.11 115 1 1 0.33 IXI 18 5-15P 45 49 1 U/C AIR CURTAIN STRUCTURE CONCEPTS CO33R-UC X 11 110-120 1 0.38 X 6 5-15P 49 50 1 EXHAUST FAN CAPTVAIR X 11 115 1 0.75 X ROOF 50 52 2 POS SYSTEM OWNER X 15A 120 1 X STUB 52 52.1 3 ORDER PRINTER OWNER X 5A 120 11 IX 1 74 52.1 56 1 BEVERAGE DISPENSER VENDOR X 8.0 120 1 X 14 56 57 1 ICE MAKER W/O BIN MANITOWOC IY-1106A X 13 4.2 208 0.4 120 1 1 X X 78 30 5-15P 57 60601WARMER, FOOD, ELECTRIC APW 86090 X 61 1 ICE TEA DISPENSER/BREWER OWNER X 15A 120 1 X 14 VFY 61 85 1 BEER TAP COOLER MICRO MATIC MDD68 X 4.6 120 ill 0.2 1 IX 1 14 5-15P 185 GENERAL NOTES C 00 1, ALL WORKS AND MATERIALS SHALL COMPLY WITH THE 26. OUTLETS SHALL COMPLY WITH ADA REQUIREMENT, MIN. 45. STRAIGHT FEEDER, BRANCH CIRCUIT, AND CONDUIT RUNS N 2016 CALIFORNIA ELECTRICAL CODE (CEC) AND THE MOST 15" A.F.F MEASURED FROM BOTTOM OF OUTLET BOX, SHALL BE PROVIDED WITH SUFFICIENT PULL BOXES OR O LATEST AND STRINGENT APPLICABLE CODE OR UNLESS NOTED OTHERWISE. SWITCHES SHALL BE JUNCTION BOXES TO LIMIT THE MAXIMUM LENGTH OF ANY UREGULATION. MOUNTED AT t 48" A.F.F. MEASURED FROM TOP OF SINGLE CABLE PULL TO 100 FEET AND CONDUIT BENDS 3. OUTLET BOX, UNLESS NOTED OTHERWISE REQUIRED BY CODE. PULL BOXES SHALL BE SIZED PER E C EQUIPMENT AND MATERIALS SHALL BE LISTED, LABELED CODE OR AS INDICATED ON DRAWINGS. LOCATIONS 2 AND INSTALLED PER RECOGNIZED ELECTRICAL TESTING 27. CONTRACTOR SHALL VERIFY THE EXISTING CONDITIONS IN SHALL BE DETERMINED IN THE FIELD OR AS INDICATED v, LABORATORY. THE FIELD BEFORE BID AND INFORM THE ENGINEER IN ON THE DRAWINGS. WRITING OF ANY OBSERVED DISCREPANCIES. O DESIGN DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL 46. MAXIMUM NUMBER OF CONDUCTORS IN OUTLET OR M 4. BE FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION 28.ALL EXPOSED OR DAMP LOCATION OR LARGER THAN 2 JUNCTION BOXES SHALL CONFORM TO THE CALIFORNIA 0 CONDITIONS WILL PERMIT. ALL NEW CONSTRUCTION SHALL BE GALVANIZED THICKWALL THREADED RIGID METAL ELECTRICAL CODE, ARTICLE 370-6, BUT IN NO CASE n A j NO FABRICATIONS SHALL BE CONSIDERED AS MEANS AND CONDUIT WITH INSULATED BUSHINGS. SHALL CONTAIN MORE THAN THE FOLLOWING NUMBER OF enr METHODS AND SHALL NOT INCORPORATE ADDITIONAL COST. 12 AWG CONDUCTORS FOR THE SIZE OF BOX U y NOTHING ON THE DESIGN DRAWINGS SHALL BE DEEMED 29. RUN ALL WIRES IN CONDUIT CONCEALED WHEREVER INDICATED. THE MINIMUM SIZE OUTLET OR JUNCTION t.., POSSIBLE IN TO BUILDING LINES. EXPOSED RACEWAY IN BOX PERMITTED IN A WALL IS FOUR INCHES SQUARE BY VASTOVIOLATETHELATESTANDMOSTSTRINGENTSTAIRWELLEQUIPMENTROOMSETC. SHALL TIGHTLY 1 X INCHES DEEP. 5. APPLICABLE CODES OR REGULATIONS. ANY ERROR, CONFORM TO BUILDING OUTLINES SO AS TO BE AS 4" SQUARE BY 1 X" D = 9 CONDUCTORS COMISSIONORDESIGNDISCREPANCYONTHEPLANSSHALLINCONSPICUOUSASPOSSIBLE. 4" SQUARE BY 2 1/8" D = 13 CONDUCTORS] BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL 4 11/16" SQUARE BY 1 D = 11 CONDUCTORS v a ENGINEER FOR CLARIFICATION OR CORRECTION. 30. USE STEEL THREADED COMPRESSION FITTING ONLY. NO 4 11/16" SQUARE BY 2 1/8" D = 18 CONDUCTORS a N 6. OPENINGS FOR ELECTRICAL PENETRATIONS THROUGH FIRE DIE CAST OR SET SCREW TYPE. ALL OUTLET BOXES CONTAINING MORE THAN ONE DEVICE RESISTANCE RATED WALLS, PARTITIONS, FLOORS OR 31. CONDUIT SHALL COMPLY WITH THE REQUIREMENTS OF SHALL BE GANGED. TWO DEVICES DOUBLE GANGED, W O CEILINGS SHALL 8E FIRE STOPPED USING APPROVED UNDERWRITER'S LABORATORIES. MINIMUM. 7. METHODS AS DETERMINED BY CODE OR REGULATION. 47. WORKING SPACE SHALL BE MAINTAINED FOR ELECTRICAL PROVIDE" SHALL MEAN ITEMS TO BE FURNISHED, 32. CONDUIT SHALL BE RIGID GALVANIZED STEEL IN EQUIPMENT PANELS, DISCONNECT SWITCHES, CIRCUIT 8. INSTALLED AND CONNECTED BY CONTRACTOR. CONCRETE SLAB, EXPOSED LOCATIONS AND WET LOCATIONS. BREAKERS, CONTROLLERS, AND CONTROL ON HEATING AND AIR-CONDITIONING EQUIPMENT PER NEC 110.26. GROUNDING SHALL BE IN FULL COMPLIANCE WITH NATIONAL ELECTRICAL CODE. 33. CONDUIT SHALL BE SUPPORTED ACCORDING TO CODE. 48. LIGHT FIXTURES IN CONTACT WITH INSULATION SHALL BE U.L. LISTED FOR THERMAL BARRIER OR BE PROVIDED UNDERGROUND CONDUITS SHALL 8E SCHEDULE 40 PVC 34. ALL EMPTY CONDUITS SHALL INCLUDE PULL WIRE. WITH 3" MINIMUM CLEARANCE. LIGHTS AND PANELS SHALL Qt,FESS10 O ! g, WITH SCHEDULE 80 PVC BENDS AND PVC COATED GRS 35. RACEWAYS RUNNING THROUGH BU EXPANSION NOT BE RECESSED IN FIRE RATED ASSEMBLIES UNLESS 8lj r Fy CONDUIT RISERS. ALL UNDERGROUND PVC CONDUITS ING JOINTS SHALL BE EQUIPPED WITH JCPANSION FITTINGS. BOXED WITH EQUIVALENT CONSTRUCTION. o y SHALL CONTAIN A GROUND CONDUCTOR AND SHALL BE 10. SIZED PER CODE REQUIREMENT. 35. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL 49. ALL. CONDUITS SHALL BE CONCEALED WITHW THE Ell ELECTRICAL PANEL LOCATIONS WITH OTHER EQUIPMENT IN BUILDING STRUCTURE TO AS GREAT AS AN EXTENT AS xp, 09/30/2 PANELS SHALL BE PANELBOARD WITH BOLT -ON TYPE ORDER TO MAKE SURE THE PANELS ARE MOUNTED WITH POSSIBLE. ALL EXPOSED CONDUITS SHALL BE MINIMUM tQTR 11. CIRCUIT BREAKERS. LOAD CENTERS NOT ALLOWED. ENOUGH CLEARANCE IN FRONT AND STAY CLEAR FROM 6 OFF THE FLOOR AND 3/4 FROM THE WALL USING ADJACENT EQUIPMENT BEFORE ROUGH -IN PER CEC. STANDOFF BRACKETS. CONDUITS CANNOT BE INSTALLED OF CAUL FUSED DISCONNECTS SHALL BE FUSED PER NAMEPLATE NOTIFY ARCHITECT/ENGINEER OF ANY PROBLEM BEFORE ACROSS ANY AISLE WAY, TRAFFIC AREA OR DOOR UNLESS NOTED OTHERWISE. INSTALLATION. OPENING. MULTIPLE RUNS OR CLUSTERS OF CONDUITS SHALL BE FURRED IN OR ENCASED IN AN APPROVED EQUIPMENT GROUNDING" (ALL NON -CURRENT CARRYING 37. BEFORE THE ELECTRICAL WORK IS CONSIDERED SEALED ENCLOSURE. c METAL PARTS OF EQUIPMENT ENCLOSURE AND RACEWAY SYSTEM) SHALL BE SOLIDLY INTERCONNECTED TO THE COMPLETE, THE CONTRACTOR SHALL RE -TEST ALL 50. EXPOSED CONDUITS WITHIN THE BUILDING SHALL BE IMC O SYSTEMS AND BE RESPONSIBLE FOR ANY AND ALL WHERE 8' AFF AND BELOW. ELECTRICAL "SYSTEM GROUND" AS PROVIDED BY THE REPAIRS TO (E) DISTRIBUTION PANELBOARD AFFECTED Q N A QSERVICEENTRANCEANDFOREACHGROUNDEDBYTHEWORKOFTHISPROJECT. DEMAND LOADS SHALL 51. FLEXIBLE CONDUIT MAY BE USED FOR FINAL 4W {rSEPARATELYDERIVEDSYSTEMTHATISINSTALLED. BE BALANCED ACROSS THE PHASES IN THE FOLLOWING CONNECTIONS TO MECHANICAL EQUIPMENT AND LIGHTINGRESISTANCETOGROUNDSHALLNOTEXCEED25OHMS. MANNER: FIXTURES. A. UPON THE COMPLETION OF THE FINAL LOAD TO A 12. CONDUCTORS SHALL BE COPPER TYPE THHN/THWN, 600V LIGHTING OR DISTRIBUTION PANELBOARD, THE 52. FURNISH AND INSTALL COMPLETE ADEQUATE AND STURDYINSULATIONUNLESSNOTEDOTHERWISE. CONTRACTOR SHALL ENERGIZE, TURN -ON, OR HAVE SUPPORT FOR ALL PARTS OF THE RACEWAY SYSTEM. RUNNING. EACH LIGHTING FIXTURE, MOTOR, ETC., SERVED 13. WIRING DEVICES SHALL BE SPECIFICATION GRADE. FROM THE PANELBOARDS, AND USING A CLAMP -ON TYPE 53 ALL CONDUITS MUST BE SUPPORTED WITH MATERIALS AMMETER CHECK THE LOAD ON EACH PHASE. SPECIFICALLY MADE FOR THIS PURPOSE. DO NOT USE 14. FLEXIBLE CONDUIT MAXIMUM 24" SHALL BE USED FOR B. IF THE LOADS ON ANY PHASE ARE OUT OF BALANCE, WIRE HANGERS. USE MALLEABLE IRON CONDUIT CLAMP, FINAL CONNECTION TO MOTORS, OTHER VIBRATING THE CONTRACTOR SHALL REARRANGE THE WIRING TRAPEZE SUPPORTS OR CADDY FASTENERS. MULTIPLE EQUIPMENT AND IN EXPOSED GARAGE AREAS. CONNECTIONS TO SUBFEED OR BRANCH CIRCUIT RUNS SHALL BE SUPPORTED BY 'UNISTRUT' OR UBREAKERSUNTILTHELOADSONEACHPHASEAREINAPPROVEDSUBSTITUTE. y) 15. EXPANSION COUPLINGS SHALL BE USED AT BUILDING BALANCE. InEXPANSIONJOINTS. U38. ALL PANELBOARDS AND SWITCHBOARDS SHALL BE FULLY 0i16. NON METALLIC BUSHINGS OR INSULATED METALLIC RATED. SERIES RATING IS NOT ALLOWED. W BUSHINGS SHALL BE PROVIDED FOR ALL CONDUIT TERMINATIONS 39. CIRCUIT BREAKERS WITH FRAME SIZE 400 AMP OR Z LARGER SHALL BE 100 PERCENT RATED. W 17. CONTRACTOR SHALL COORDINATE AND VERIFY MECHANICAL U EQUIPMENT CONTROL AND WIRING REQUIREMENTS WITH 40. ALL EQUIPMENT FOR EXTERIOR APPLICATION SHALL HAVE Q Q MECHANICAL CONTRACTOR BEFORE CONSTRUCTION. WEATHERPROOF ENCLOSURE. lilN 18. ROMEX CABLE NOT ALLOWED. 41. IT IS THE INTENT OF THE PLANS AND SPECIFICATIONS 0 < Q WTHATACOMPLETEANDWORKABLEELECTRICAL 19. IT IS THE INTENTION OF THE DESIGN DRAWINGS TO COVER INSTALLATION BE PROVIDED BE PROVIDED FOR ALL THE ALL THINGS REQUIRED TO MAKE A COMPLETE AND EQUIPMENT DESCRIBED OR SHOWN AS BEING IN THIS OPERATIVE SYSTEM. CONTRACTOR SHALL FURNISH ALL CONTRACT. FURNISH ALL LABOR AND TOOLS NECESSARY J 0OQU p JLABORMATERIALS, EQUIPMENT, OR MISCELLANEOUS AND FURNISH ALL INSTALL ALL APPARATUS, MATERIALS W SERVICE REQUIRED TO ACCOMPLISH THIS RESULT. AND EQUIPMENT IN A FASHION COMPLYING WITH ALL rT1 APPLICABLE CODES, INCLUDING ITEMS REQUIRED BUT NOT c) LJ W 20. PROVIDE PULL BOXES AS NECESSARY OR WHEN REQUIRED NORMALLY SHOWN, SUCH AS LAMPS, HANGERS, BY CODE. BRACKETS, CLAMPS, COUPLINGS, BOXES, CONNECTORS Ld QaANDHARDWARE. U r, J 21. NOTES AND SCHEDULES LISTED ON DRAWINGS OF OTHER SECTIONS OF THIS PROJECT WITH REFERENCE TO 42. FOR ALL EXISTING CIRCUITS THAT ARE TO REMAIN AND ELECTRICAL CONTRACTOR OR ELECTRICIAN APPLY TO THIS TO BE USED FOR BOTH EXISTING: AND NEW ELECTRICAL SECTION OF CONTRACT. ELECTRICAL WORK NOTED ON DEVICES AND LIGHT FIXTURES, CONTRACTOR SHALL HVAC, KITCHEN AND PLUMBING DRAWINGS TO BE DONE REPLACE THE EXISTING CONDUCTOR WITH NEW UNDER THIS SECTION. CONDUCTORS FOR THE ENTIRE CIRCUIT. 22. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR 43. ALL WORK DEMOLISHED SHALL BE' REMOVED FROM THE THE COORDINATION OF ALL LIGHTING EQUIPMENT AND PREMISES EXCEPTED ITEMS TO BE REUSED OR RETURNED CONTROL DEVICES WITH CEILING AND WALL TYPES, PRIOR TO OWNER OR AS THE GENERAL ,.CONTRACTOR SHALL CAP TO ORDERING LIGHTING EQUIPMENT. AND FLUSH OFF BEHIND FINISH SURFACES ALL i PROJECTING ELECTRICAL OUTLETS.; DEFER TO o i o 23. SUBSTITUTION OF ANY MATERIAL OR EQUIPMENT SHALL BE ARCHITECTURAL DEMOLITION PLAN FOR ADDITIONAL 5 N c APPROVED BY ARCHITECT BEFORE INSTALLATION. REFER INFORMATION. TO ARCHITECTURAL REFLECTED CEILING PLAN AND OTHER W ARCHITECTURAL DRAWINGS AS REQUIRED FOR 44. CONTRACTOR SHALL PROTECT ALL EXISTING SYSTEMS COORDINATION. WHICH ARE TO REMAIN, INCLUDING BUT NOT LIMITED TO: VOICE, DATA, FIRE ALARM, SECURITY SYSTEMS. ALL 24. EXACT LOCATION OF HVAC, KITCHEN AND PLUMBING OUTLETS, HARDWARE, CONDUIT AND CONDUCTORS TO BE CL i EQUIPMENT THAT REQUIRE ELECTRICAL CONNECTIONS ARE SECURED FROM ANY DAMAGE. CONTRACTOR SHALL TEST N M SHOWN ON THE MECHANICAL, KITCHEN AND PLUMBING ALL OUTLETS, HARDWARE, CONDUIT AND CONDUCTORS DRAWINGS. PRIOR TO COMMENCEMENT OF WORK, AND PROVIDE A WRITTEN REPORT TO OWNER/ARCHITECT, INDICATING ANY 25. ALL EXPOSED CONDUIT LOCATED IN INTERIOR AREAS FAILURES OR DAMAGE TO OUTLETS, HARDWARE, CONDUIT SHALL BE PAINTED TO MATCH EXISTING WALL SURFACE. OR CONDUCTORS. KITCHEN EQUIP SCHEDUL GENERAL NOTES CITY OF LAKE ELS,, I IVY ICE DATE ioBNo V ti r n 10/22/18 lip 1SCALE DRAWN BY STORE N0. DRAWING W. E38-0 STATE OF CALIFORNIA INDOOR LIGHTING CEC-NRCC4.TI-01-E (Revised 04116) CALIFORNIA ENERGYCOMMISSIC CERTIFICATE OF COMPLIANCE NRCC-LT-01-E Indoor Lighting (Page 1 of 6) Project Name: Pieology, Lake Elsinore, CA °atO Prepared:03-22-2017 A. General Information Climate Zone: C Conditioned Floor Area: 1939 sf 10 Unconditioned Floor Area: Building Type: D Nonresidential High -Rise Residential Hotel/Motel El Schools Q Relocatable Public Schools El Conditioned Spaces Unconditioned Spaces Phase of Construction: New Construction Addition 0 Alteration Method of Compliance: Complete Building j 0 Area Category Tailored Project Address: B. Lighting Compliance Documents (select yes for each document included) 6 Fordetoded instructions on the use of this and o8 Energy Efficiency Standards compliance documents referto the Nonresidential Manual published by the California Energy Commission. YES NO COMP. DOC. TITLE 0 NRCC-LTI-01-E Certlfk:ate of Compliance. All Pages required on plans for all submittals. OQ 0 NRCC-LTI-02-E Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals. Oe 0 NRCC-LTI-03-E Indoor Lighting Power Allowance O 0 NRCC-LTI-04-E Tailored Method Worksheets 0 NRCC-LTI-05-E Line Voltage Track Lighting Worksheets 0 D NRCC-LTI-06-E Indoor Lighting Existing Conditions STATE OF CALI=ORMA INDOOR LIGHTING CEC-NRCC-LT01-E (Revised 04r16) CERTIFICATE OF COMPLIANCE CALL=ORNIA ENERGY.COMISSION_- N RCC-LTI-01-E Indoor Lighting (Page 2 of 6) Project Name: pieology, Lake Elsinore, CA Date Prepared 03-22-2017 C. Summary of Allowed Lighting Power Conditioned and Unconditioned space Lighting must not be combined for compliance - -- Indoor Lighting Power for Conditioned Spaces Indoor Lighting Power for Unconditioned Spaces Watts Watts Installed Lighting Installed Lighting 01 NRCC-LTI-01-E, Table H, page 5 1569 NRCC-LTI_-01-E, Table H, page 5 02 Portable Only for Offices NRCC-LTI-01-E, Table G, page 4 Minus Lighting Control Credits03MinusLightingControlCredits NRCC-LTI-02-E, page 2 NRCC-LTi-02-E, pap 2 Adjusted Installed Lighting Power I = 0 Adjusted Installed Lighting Power 1569 row 1 plus rowminus row 3) row 1 minus row 3) Complies ON-Y if Installed <_ Allowed (Box 04 < Box 05) Allowed Lighting Power 2 - _ -- Complies ONLY if Installed s Allowed (Box 04 < Box 05) 1 Allowed Lighting Power Conditioned NRCC-LTI-03-E, page 1 Unconditioned NRCC-LTI-03-E, page- 1 05 Alterations with replacement luminairesthat have at least 2045 Alterations with replacement luminaires that have at least 50/ 35°plower power compared to the original existing luminaires, i 50/35%lowe- power compared to the orig nal existing luminaires, may instead use the allowed wattage from NRCCATl-06, page 2 i may instead use the allowed wattage from NRCC-LTi-06, page 2 D. Declaration of Required Certificates of Installation Declare by selectine ves for all of the Certificates that will be submitted. (Retain conies and verifv forms are completed and siened.I YES NO Form/Title 0) 0 NRCI-LTI-01-E - Must be submitted for all buildings ^ - Field Inspector NRCI- LTI-02-E - Must be submitted for a lighting control system, or for an Energy Management Control Systen (EMCS), L J Field Inspector to be recognized for compliance. Qe 0 NRCI- LTI-03-E - Must be submitted for a line -voltage track lighting integral current imiter, or for a supplementary Field Inspector overcurrent protection panel used to energize only line -voltage track lighting, to be recognized for compliance. 0 NRCI- LTI-04-E - Must be submitted for two interlocked systems serving an auditorium, a convention center, a Field Inspector conference room, a multipurpose room, or a theater to be recognized for compliance. 0 NRCI-LTI-05-E - Must be submitted for a Power Ad'Lstment Factor PAF to be recognized for compliance. 1 (PAF) p f Field Inspector i F, p NRCI- LTI-06-E - Must be submitted for additional wattage installed in a video conferencing studio to be recoglized for Field Inspector compliance. CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance April 2016 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance April 2016 STATE OF CALIFORNIA INDOOR LIGHTING CECAIRCC4LTI41- E (Revised 04118) CALIFORNIA ENERGY COMMISSION STATE OF CALFORNIA INDOOR LIGHTING CEC• NRCC.LTI-01-E (Revised 04i16) CERTIFICATE OF COMPLIANCE CALIFORNIA ENERGYCOMMiSSION NRCC- LTI-01-E CERTIFICATEOFCOMPLIANCENRCC-LT-01-E Indoor Lighting Page 4 of 6) Indoor Lighting Page 5 of 6) Project Name: Pleology, Lake Elsinore, CA Date Prepared:03.22-2037 Project Name: Pieology, Lake Elsinore, CA Date Prepared. 03-22-2017 G. Installed Portable Luminaires in Offices - Exception to Section 140.6(m) This section shall be filled out ONLY for portable luminaires in offices (As defined in §500.1). All other planned portable luminaires shall be documented on next page of this compliance document This section is used to determine if greater than 0.3 watts of portable lighting is planned for any office j - Fill out a separate line for each different office. Small offices that are typical (having the same general and portable lighting) maybe grouped together. This allowance shall not be traded between offices having different lighting systems. Office Portable Luminaire Schedule Office Installed Portable Luminaire W/ft' Office Location Field Inspector 01 02 03 04 05 06 07 08 09 10 Installed If G06 f, 0.3, r Z portable 19Watts enter Identify Office area in 33Cr luminaire s m per zero, GOS x G07) which these portable v N m. Complete Luminaire Description watts in square luminaires are Installed i. e., LED, under cabinet furniture mounted Watts per It °, this office ri foot If G06 > 0.3, direct/ indirect) Luminaire GO2 x G03) GO4 / GOS GO6-0.3) 0 0 O O 0 o O O 0 o O O 0 0 O O 0 0 0 0 Enter sum total of all pages Into NRCC-LTI- Total installed portable luminafre watts that are greater than 0.3 W/W per office: 01-E; Page 2 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance STATE OF CALIFORNIA INDOOR LIGHTING - LIGHTING CONTROLS April 2016 Im CEC- NRCC-LTI-02-E (Revised 01118) CALIFORNIA ENERGY COMMIKION T CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E Indoor Lighting -Lighting Controls (Page 1of 3) r° J`ttN`""Pieoklgy, Lake Elsinore, CA pa 03-22-2017 A. Mandatory Lighting Control Declaration Statements (Indicate if the measure applies by checking yes or no below.) YES NO Control Requirements Lighting shall be controlled by self-contained lighting control devices which are certified to the Energy Commission according to the Title 20 Appliance Efficiency Regulations in accordance with Section 110.9. O Lighting shall be controlled by a lighting control system or energy management control system in accordance with §110.9. An Installation Certificate shall be submitted in accordance with Section 130.4(b). One or more Track Lighting Integral Current Limiters shall be installed which have been certified to the Energy Commission in accordance with §110.9 and 130. 0. Additionally, an Installation Certificate shall be submitted in accordance with Section 130.4(b). A Track Lighting Supplementary Overcurrent Protection Panel shall be installed in accordance with Section 110.9 and Section 130.0. Additionally, an Installation Certificate shall be installed in accordance with Section 130.4(b). O All lighting controls and equipment shall comply with the applicable requirements in §110.9 and shall be installed in accordance with the manufacturer's instructions in accordance with Section 130.1. e) O All luminaires shall be functionally controlled with manual ON and OFF lighting controls in accordance with Section 130.1(a). General lighting shall be separately controlled from all other lighting systems in an area. Floor and wall display, window display, case display, ornamental, Q and special effects lighting shall each be separately controlled on circuits that are 20 ampsor less. When trade lighting is used, general, display, ornamental, and special effects lighting shall each be separately controlled; in accordance with Section 130.1(a)4. The general lighting of an enclosed area 100 square feet or larger, with a connected lighting toad that exceeds 0.5 watts per square foot shall meet the multi - level lighting control requirements in accordance with Section 130.1(b). e) O All installed indoor lighting shall be equipped with controls that meet the applicable Shut -OFF control requirements in Section 130.1(c). 6) Q Lighting in all Daylit Zones shall be controlled in accordance with the requirements in Section 130.1(d) and daylit zones are shown on the plans. Q Lighting power In buildings larger than 10,000 square feet shall be capable of being automatically reduced in response to a Demand Responsive Signal in accordance with Section 130.1(e). Before an occupancy permit is granted for a newly constructed building or area, or a new lighting system serving a building, area, or site is operated for Q O normal use, indoor lighting controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in accordance with Section 130.4.(a). The controls required to meet the Acceptance Requirements include automatic daylight controls, automatic shut -OFF controls, and demand responsive controls. A Separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Ugh ting Schedule is on,'y for. R1 CONDiTIONED SPACE UNCONDITIONED SPACE H. Indoor Lighting Schedule and Field Inspection Energy Checklist Lil Luminaire Schedule Installed Watts Location Field Inspector 1 01 02 03 04 05 06 07 C8 How wattage was I determined v o A Complete Luminaire Description d E r 8 u E m , 5 c n o xw( i.e, 3 lamp fluorescent troffer, W W c E 2 m Primary Function area in which Z m F32T8, one dimmable electronic ballast) u w w Z - i- 3 these luminaires are installed Pass Fail Ll 20LED Dimmable 40 n 5 Ki cinch Q 0-1L2 LED Pendant, dimmable 40 i] l 6 240 4 407 Dining Area Dining Area Kitchen/ Rest rm C L C Q C' L3 Pendant LED Dimmable 120 V L4 LED Downlight, dimmable 11 37 LS LED Pendant, dimmable 11 Q 22 42 0 o Dining Area C Q C0 C INSTALLED WATTS PAGE TOTAL Enter sum total of al pages into F71539 156gINRCC-LTI-01 E; Page 2 A CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance STATE OF CALIFORNIA INDOOR LIGHTING - LIGHTING CONTROLS CEC- NRCC-LTI-02-E (Revised 0111 B) CERTIFICATE OF COMPLIANCE Indoor Lighting - Lighting Controls a, lccc Nar+e: Pieology, Lake Elsinore, CA April 2016 CALIFORNIA ENERGY COMMISSION NRCC- LTI-02-E Page 2 of 3) 03- 22-2017 A separate document must be filled out for Conditioned and Unconditioned Spaces. This page is used only for the following: CONDITIONED SPACES UNCONDITIONED SPACES B. Mandatory and Prescriptive Indoor Lighting Control Schedule, PAF Calculation, and Field Inspection Checklist PAF Credit Calculation t a Standards Complying With ' r n N all that apply, or leave empty o N X ° c d n Lighting Control Schedule if Exempted) Led ) n ° T n 01 02 03 04 1 05 06 ' 07 09 1 091 10 31 12 13 14 15 Type/ Description of Lighting Control ( i.e.: occupancy sensor, q Lotion in Building Locationautoatic time switch, of o 1 o 0 0 m N is dimmer, automatic daylight, Units W etc...) Dining Area Manual dimmer 0 ^ C, , Kitchen Manual dimmer, Oa sensor 0 , Q Rest rms Occupancy Sensor 0 "D 00 O F 0 !C 0 ControlCreditPAGETOTAL (Sum of Column 13): IF MULTIPLE PAGES ARE USED, ENTER SUM TOTAL OF Control Credit for all pages HERE (Sum of all Column 13): Enter Control Credit total into NRCC-LTI-01-E; Page 1 1. 1. § 130.1(a) = Manual area controls; §130.0(b) = Multi Level, • §230.1(c) = Auto Shut -Off, §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive, §140.6(d) _ Additional lighting controls installed to earn a PAF,- §240.6(d) = Prescriptive Secondary Sidelit Daylight Controls. 2. Check Table 140.6-A for correct Factor. PAFs shall not be traded between conditioned and unconditioned spaces. Asa condition to earn a PAF, an Installation Certificate is also required to be ftlfed out signed, and submitted. STATE 0= CALI=ORNIA - INDOOR LIGHTING CEC- NRCC LTI-0t•c tRevis Od116} CALIFORNIA ENERGYCOM tSSION CERTIFICATE OF COMPLIANCE NRCC-LTI-01-E Indoor Lighting (Page 3 of 6) Project Name: oieology, Lake Elsinore, CA Data PmPared:03-22-2017 E. Declaration of Required Certificates of Acceptance its Declare by selecting yes for all of the Certificates of Acceptance that will be submitted. (Retain copies and verify farms are completed and signed.) YES NO FORM/TITLE NRCA- LTI-02-A - Must be submitted for occupancy sensors and automatic time switch controls. 13 Field Inspector NRCA- LTI-03-A - Must be submitted for automatic daylight controls. Field Inspector E) NRCA-LTI-04-A - Must be submitted for demand responsive lighting controls. 13Field Inspector C) C NRCA-LTI-05-A - Must be submitted fo- institutional tuning power adj,Jstment factor (PAF). A Separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for: 1 CONDITIONED SPACE UNCONDITIONED SPACE j F. Indoor lighting Schedule and Field Inspection Energy Checklist The actual indoor lighting power listed on the next 2 pages includes udesall installed permonent and planned portable lighting systems. When Complete Building Method is used for compliance, list each different type of lurrina(re on separate lines. When Area Category Me:hod or Tailored Method is used for compliance, list each different type of luminaire by each different function area on separate lines LJ Also include trade lighting in schedule, and subnit the track lighting compliance document (NRCC-LTI-05-E) when line -voltage track lighting is installed CA Building Energy Efficiency Standards - 2016 Nonresidertial Compliance STATE OF CALIFORNIA INDOOR LIGHTING CEC-NRCC- LTI-01-E (Revised 04116) _ CERTIFICATE OF COMPLIANCE April 2016 W'sm a NRCC-LTI- 01-E Indoor Lighting ( Page 6 of 6) Project Name: Pieology, Lake Elsinore, CA Date P1ePared: 03-22-2017 DOCUMENTATION AUTHOR' S DECLARATION STATEMENT 1. 1 certifv that this Certificate of Compliance documentation is accurate and complete. Documentation tuthor Name: Minh Tran Oocomentalasignature:nAuthorsignature: UCompany: CDI sgrutlae Date' 03-22-2017 Ad*ess: CEA Catirtca"n ldentiGbn (if appkWe): 1652C Bake Parkway, Suite 100 citv'iiatelzip: Phone: Irvine, CA 92618 RESPONSIBLE PERSONS DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business a Professions'I' f i i em design identified n this Certificate of Com iance ig andCodetoaaepRresponsibilityorthebuklngdesignocystp a led oPI responsible designer). 3. The energy features and performance specifications. materials, components, and manufactured devioesfor the building design or system design identified on this Cetifiate of Compliance confcrm to the requirements of Title 24, Part 1 and Part 6 of theCalifomia Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, ca culations, plans and specifications submitted to the enforcement agencyfor approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. ) inderstand that a completed sipped copy ofthis Certificate of Complance is required to be included with the documentation the builder arovidesto the building owner at occupancy. Responsible De%ner Name- NeSpoHble Wegner signaurre: Minh Trar company' CDI Date03- 22-2017 i a 9rtre 3. literate' .. 16520 Bake Parkway, Suite 100 E-17378 rt}Kiate/Zip Phone Irvine, CA 92618 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance STATE OF CALIFORNIA INDOOR LIGHTING - LIGHTING CONTROLS CEC-NRCC-LTI- 02-E (Revised 01116) CERTIFICATE OF COMPLIANCE _ Indoor Lighting- Lighting Controls Pieology, Lake Elsinore, CA CA pate aae303_ 22- 2017 April 2016 MISSION NRCC-LTI : 2 Page 3 of 3 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate cur", ` :_omplete. Documentation Author Name: .__.-. Minh Tran e Docmntation Aeetor Siputoe: Company: CDI signature Date: 03-22-2017 Addiew 16520 Bake Parkway, Suite 100 CEA :ettikabon Wenti6casonlirapplicile): Gry/StateiGp• Irvine, CA 92618 I RESPONSIBLE PERSOWS DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: II 1. The information provided on this Certificate of Compliance is true and ce;frect. 2. ]am eligible under Division 3 of the Business and Professions Code to accept responsibility fo :he building design or system design identified on this Certificate of Compliance responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate fi te of Complianceareconsistent with theinformationprovided on othty appiable otlrnpliantx documents, worksheets, calculaticns, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a c*inpleted signed copy of this Certificate of Compliance is required to be included wth the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: Minh Tran Reegonsble DeagrierSgrueirt: Dale Company CDI Sgrrd: 02-22-2027 AndrPSt:16520 Bake Parkway. Suite 100 tKese. E-17378 C,q!Ytate/Zip' -- Irvine, CA 92618 Phone: U 1 00 cis % 0 r. 0 0 Q Cd U E 1 rA H 0' O f fP' 1 U - a ^ N C C N W %0 0 i OdY -%'s d - tic M 01. 1 W GN Z LLI Q U tee- < 1 O N[ W W 0 CL J O- 10 J w U W oWW WCMHY 00 U O vs Zrn 1 N L5 N I ea i O U W V V I TITLE 24 I ale CIF H a - h, E ELSI rz ra 11 -18RAE=: a E DRAWN BY Uri l c' i Ice tad STORE NO. DRAWING W. CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January2016 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 E4,0 STATE OFCAUFOMA INDOOR LIGHTING POWER ALLOWANCE CEC-NRCC-LTI-03-E(Revised "16 CALIFORNIA ENERGYGOMIAIS51ON CERTIFICATE OF COMPLIANCE NRCC-LT1-03-E Certificate of Compliance - Indoor Lighting Power Allowance (Page '-Of 4) j proJett Name: Dateprepared: Pieology, Lake Elsinore, CA 03-22-2017 - A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for: CONDITIONED spaces UNCONDITIONED spaces A. SUMMARY TOTALS OF LIGHTING POWER ALLOWANCES If using Complete Building Method for compliance, use only the total in column (a) as total allowed building watts. If using Area Category Method, Tailored Method, or a combination of Area Category and Tailored Method for compliance, use only the total in column (b) as the total allowed building watts j a) lbl 01 Complete Building Method Allowed Watts. Documented in section B of NRCC-LTI-03-E (below on this page) 0 02 Area Category Method Allowed Watts. Documented In section C-1 of NRCC-LTI-03-E (below on this page) 2045 03 Tailored Method Allowed Watts. Documented in section A of NRCC-LTI-04-E i TOTAL ALLOWED BUILDING WATTS. Enter number into correct cell on NRCC-LTI-01, Page 2, Row 1 0 2045 Check here if building contains both conditioned and unconditioned areas. B. COMPLETE BUILDING METHOD LIGHTING POWER ALLOWANCE 01 02 03 04 TYPE OF BUILDING (From §140.6 Table 140.6-8) WATTS PER ft2 X COMPLETE BLDG. AREA ALLOWED WATTS 0 Total Area: Total Watts. Enter Total Watts into section A, row 1(Above on this page) 0 C -1 AREA CATEGORY METHOD TOTAL LIGHTING POWER ALLOWANCES ( Watts Total from section C-2.1 2045 Total from section C-3. Total Watts. Enter Total Watts Into section A, row 2 (Above on this page). 12045 For Alterations Only -Reduced lighting power option (Total Allowed Watts x 0.85). Enter this value into section A, row 2 if using this option. CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance STATE OF CALIFORNIA INDOOR LIGHTING POWER ALLOWANCE Apr12016 is CEC-NRCC-LT143-E (Revised 0416) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-03-E Certificate of Compliance - Indoor Lighting Power Allowance (Page 4 of 4) PWJe:tNp *:Pieotogy, Lake Elsinore, CA DaOeDrg fG 03-22-2017 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. DocamentadonAuthor Name: Minh Tran Dotumenation author signature: hA eorngarry: CDI sig"ture Date: 03-22-2017 Address.16520 Bake Parkway, Suite 100 crA cerd6cation Idend6cadon (ilappiad&): citygtate/zip: IrWne,CA 92618 Phone: RESPONSIBLE PERSONS DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of Calfornia: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. S. I will ensure that a completed signed copyof this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible De*xw Name: Minh TrainReWwsarle Designer sgrsture: comparnv' CDI Date scorned. D3-22-2017 Address' 16520 Bake Parkway, Suite 100 License. E-17378 ciryJstate/Zip: Irvine, CA 92618 mom; CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance Apri12O16 STATE OF CALIFOFWIA INDOOR LIGHTING POWER ALLOWANCE CEC-NRCC-LTI-03-E (Reviwd "16) CERTIFICATE OF COMPLIANCE Certificate of Compliance_ Indoor Lighting Power Allowance Pieokogy, Lake Elsinore, CA A separate page must be filled out for Corditioned and Unconditioned Spaces. This page is only for: CONDITIONED spaces LJ UNCONDITIONED spaces F 03-22-2017 MISSION NRCC-LTI-03-E Page 2 of 4) C -2 AREA CATEGORY METHOD GENERAL LIGHTING POWER ALLOWANCEa Do not Ind ude portable lighting for offices. Portable lighting for offices shall be documented only in Section G of NRCC-LT -01-E. Separately list lighting for each primary function area as defined in §100.1 of the Standards. j 01 02 03 04 AREA CATEGORY (From §140.6 Table 140.E-C) WATTS ALLOWED Location in Building Primary Function Area per Table 140.E-C PER ftz X AREA (ft) _ WATTS Kitchen Food Prep Area i.2 808 i 969.6 Rest rms Rest rms 06 138 82.8 Dining Area Dining Area 10 993 9S3 C C, C 0 C. C 0 C e 0 TOTALS 1939 Enter sum total Area Category allowedwatts into section C-1 of NRCC-LTI-03-F (this compliance document) 2045 WATTS CA Building Energy Efficiency Standards-2016 Nonresidential Compliance April 2016 STATE OF CALI=OFWA INDOOR LIGHTING POWER ALLOWANCE CEC-%RCC-LTI-03-E (ReAsec "16) CALIFORMA ENERGYCOMMISSDh CERTIFICATE OF COMPLIANCE NROC-LTI-03-E Certificate of Compliance - Indoor Lighting power Allowance Page 3 of 4) cr- -!4ac •. Dace [•seer_ Pieology, Lake Elsinore, CA 03-22-2017 j A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for: CONDITIONED spaces UNCONDITIONED spaces C-3 AREA CATEGORY METHOD ADDITIONAL LIGHTING WATTAGE ALLOWANCE (from Table 140.6-C Footnotes) 01 02 i 03` 04 05 06 07 ALLOWED Additional Wattage WATTS Primary i Sq Ft or ; Watts Allowance Description(s) and Quantity of Special Total Design Smallerof Function Linear ft Allowed (02 x 03) z LuminaireTypes in each Primary Function Area Watts 0A or 06 0 r 0 0 I 0 - --- -- _ _-`-- 0 0 0 0 0 0 0 0 I 0 F 1 0 TOTALS -Enter into TOTAL AREA CATEGORY METHOD ADDITIONAL ALLOWANCES - Section C-1 1. Use linear feet only for additional allowarce for white board or chalk board. All other add tional Area Category allowances shall use watts per square foot 2 . Additiona watts are available only when allowed according to the footnotes on bottom o` Table 140.6-C, which include: Specialized task work; Ornamental lighting; Precision commercial and industrial work: Per linear foot of white board or chalk board; Accent, display and feature lighting; and Mdeocon(erencing studio lighting.. 3 Luminaire classification and wattage shal be dete-mined in accordance with §130.0(c) of the Standards. CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance April 2016 F 00 0 U E O W NO col 0 >' en U av CC no N ino o k ICU M Ln 0 W D W W Q U 1 ON W QW Q J H—I a- J Z OJO J J QU W F—oWt W M' W (y) Irk Y U 0J w Z via 1 O W o C W W U U LLJ 1 N of TJTLE 24 CITY ,) A ie Its ua No 10/22/18 wry i: ++ Au a is $. r art .7 PLG tJl{I'11.'1, E ff erg jyWi:L3Cy .' #fe9N ¢e.nS:S3 L_$Y] STORE NO. E5,0 I MECHANICAL FLOOR PLAN SCALE: 1/4" = V-0" RADIUS MECHANICAL PLAN NOTES 1O (E)RTU-1,2 5-TON UNITS EACH MOUNTED ON ROOF W/DISCONNECT SWITCH & WEATHERPROOF GFCI. O (N)KITCHEN EXHAUST DUCT MOUNTED VERTICALLY; TERMINATES TO (N)EXHAUST FAN MOUNTED ON ROOF. MAINTAIN MIN. 2% SLOPE. GREASE DUCT SHALL BE ENCLOSED IN A FIRE RATED ENCLOSURE. SEE DETAIL ON SHEET M-1. O ANSUL FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED IN COMFORMANCE WITH NFPA 96. 40 GREASE EXHAUST DUCT TO BE 16 GAUGE CARBON STEEL WITH LIQUID TIGHT WELDS. HOOD LIGHT SWITCH TO BE LOCATED ON FACE OF SYSTEM COMPARTMENT. OPERATION OF KITCHEN HOOD IS INTERLOCKED WITH KITCHEN EXHAUST FAN. O USE FLEXIBLE DUCT, THERMAFLEX TYPE MKF OR EQUIVALENT, CLASS 1, WITH 1-1/2" EXTERNAL INSULATION ON ALL ROUND SUPPLY AIR DUCTS ABOVE FINISHED CEILINGS.. PROVIDE 1/2" THICK DUCTLINER ON ALL RECTANGULAR SUPPLY, RETURN DUCTS, MAKE-UP AIR DUCTWORK ABOVE THE CEILING WITH A MINIMUM OF 1" THICK, 1-1/2° LB. DENSITY (R-5.6) DUCT WRAP WITH VAPOR BARRIER. MAINTAIN VAPOR BARRIER THROUGHOUT THE DUCT SYSTEM. SIZES SHOWN ARE CLEAR INSIDE DIMENTION; SHEET METAL SIZES SHALL BE INCREASED ACCORDINGLY. PROVIDE SPIN -IN DUCT CONNECTOR WITH BALANCING DAMPER AND LOCKING QUADRANT. 6O 6" DIA. RESTROOMS EXHAUST DUCT VENT TO ROOF. OMECHANICAL CONTRACTOR TO FIELD VERIFY THAT SUPPLY AIR DUCT RISER IS PROVIDED WITH DUCT SMOKE DETECTOR. PROVIDE DUCT SMOKE DETECTOR IF NONE EXISTING IS INSTALLED. 8O (N)36" WIDE AIR CURTAIN; 1960 TO 1450 FPM AT NOZZLE. GENERAL NOTES 1. DUCT SMOKE DETECTORS SHALL BE LABELED BY AN APPROVED AGENCY, APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHALL FOR AIR DUCT INSTALLATION AND SHALL BE INSTALLED IN ADDORDANCE WITH THE MANUFACTURER'S APPROVED INSTALLATION INSTRUCTIONS (2016 CPC, SECT. 608.1) 2. AN AIR BALANCE TEST WILL BE REQUIRED TO VERIFY THE MINIMUM VOLUME OF OUTSIDE AIR TO COMPLY.WITH THE T-24 CALCULATIONS, BEFORE THE FINAL APPROVAL OF THIS PROJECT. 3. HOODS, FILTERS, EXHAUST FANS, AND DUCTS SHALL HAVE A CLEARANCE OF AT LEAST 18" TO COMBUSTIBLE MATERIALS, 3" TO LIMITED COMBUSTIBLES MATERIAL, AND 0" TO NON-COMBUSTIBLE MATERIAL (2016 CMC SEC. 507.2). 4. LISTED EXHAUST HOODS SHALL BE INSTALLED IN ACCORDANCE WITH THE TERMS OF THEIR LISTINGS AND MANUFACTURER'S INSTALLATION INSTRUCTION (2016 CMC SEC. 510.4). 5. A PERFORMANCE TEST WILL BE REQUIRED TO VERIFY THE RATE OF AIRFLOW AND THE PROPER OPERA11ON OF THE EXHAUST AND MAKE-UP AIR FOR KITCHEN HOOD SYSTEM BEFORE THE FINAL APPROVAL OF THIS INSTALLATION. 6. AIR HANDLING DUCT SYSTEMS, EXCEPT GREASE EXHAUST DUCT SYSTEM, SHALL BE CONSTRUCTED, INSTALLED AND INSULATED AS PROVIDED IN CHAPTER 6 OF 2016 CMC. 7. PRIOR TO FINAL APPROVAL OF THE MECHANICAL PERMIT, A SMOKE DETECTOR SHUT-OFF TEST SHALL BE REQUIRED. 8. ONLY CO2 SENSORS THAT DIRECTLY TRACK THE CO2 LEVEL IN THE BREATHING ZONE ARE PERMITTED BY CEC FOR USE IN THE DEMAND CONTROLLED VENTILATION, REQUIREMENT FOR T-24 COMPLIANCE. 9. THE CO2 SENSOR MUST BE FACTORY CERTIFIED TO HAVE AN ACCURACY WITHIN +75PPM AT 600 AND 1000PPM CONCENTRATION WHEN MEASURED AT SEA LEVEL AND 25C(77F) FACTORY CALIBRATED OR CALIBRATED AT START-UP AND CERTTEIED BY THE MANUFACTURER TO REQUIRE CALIBRATION NO MORE FREQUENTLY THAN ONCE EVERY 5 YEARS. 10.THE INSIDE EDGE OF CANOPY TYPE COMMERCIAL EXHAUST HOOD SHALL EXTEND A HORIZONTAL DISTANCE OF NOT LESS THAN 6 INCHES BEYOND THE EDGE OF THE COOKING SURFACE OF ALL OPEN SIDES AND VERTICLE DISTANCE BETWEEN THE HOOD AND THE COOKING SURFACE SHALL NOT EXCEED 4 FEET. 11.EXHAUST OUTLET TERMINATION OF GREASE DUCT FROM HINGED UPBLAST FAN SHALL EXTEND THROUGH THE ROOF SHALL NOT BE LESS THAN 18 INCHES ABOVE THE ROOF AND THE FAN DISCHARGES NOT LESS THAN 40 INCHES ABOVE THE ROOF. 12.PROVIDE CERTIFIED AIR BALANCE REPORT FOR EXHAUST HOODS AND MAKE UP AIR PRIOR TO FINAL INSPECTION. NEW 4x4 0 EA HANGER NUT &LOCK NUT W/ 'LUS44' EA. END AND CONNECTION PLY. E.N. W/WASHERS (TYP. E) ROOF SHTG. 2'x3'x5' LG. STEEL HANGING' ANGLE W/(4) 16d NEW 2x6x48" LG. W/ 12d AT 6" O.0 W/ NAILS NOT LOCATED WITHIN 3" OF PIN. NUT & LOCK NUT AM SPLICE SHALL BE LOCATED CONNECTION no nm*-- -1aMAY BETWEEN BLKG., TYP. W/WASHERS (TYP') upw ".) ( E) TRUSS MEMBER (TJI) HOOD MOUNTING at CHANNEL ON 2 HOOD/ HANGING 1/2" DIA. ALL THREADED ROD ANGLE INTEGRALWITH EACH HOOD SUPPORT (TYP.) HOOD - SEE HOOD DRAWINGS HANGING ANGLE INTEGRAL WITH HOOD - SEE HOOD DRAWINGS EXHAUST HOOD - SEE HOOD DRAWINGS STEEL HANGING ANGLE FOR o WOODBLOCK CONNECTION o 1/2' DIA. HEAVY DUTY NUT WASHER -ONE ABOVE AN 1/2' DIA. ALL THREAD ROD ONE BELOW HANGING ANGLE CONNECTED TO ROOF JOIST ANGLE 1," THROUGH ANOTHER HANGING 2 STEEL HANGING ANGLtMR " NOTE: HOOD CONNECTION REFER TO HOOD MANUFACTURER'S SPECIFICATIONS AND THE ARCHITECTURAL/STRUCTURAL DRAWINGS FOR ADDITIONAL CONSTRUCTION REQUIREMENTS. HOOD HANGING DETAIL NO SCALE DUCT SUPPORT DETAILS (SMACNA) 1 NTS 1-1/2" x 26 GAUGE STRAPS WITH 2A SMS EACH SIDE OF DUCT DUCT SUPPORT SPACING AS PER UMC Table 6-E. ROOFICEILING JOIST LAKE ELS1 D . HANGER STRAPS 60"MAX. 1 OF D I N I E G 1 S1LSfR, LOAD RATED 1sFASTENERS UNLESS FOOT OF STRAP IS PLACED UNDER A BOTTOM SCREWS 1" MIN. SCREWS MAY BE OMITTED IF HANGER LOOPS 50" DIA. MAX. RECTANGULAR DUCT ROUND DUCT STRAP HANGERS oj m U-) oj W 0*) z W Q U O LLJN CZQLJ J H OJ ED — QUPAW Wry cD W LZMHW U Co D J o 01) N Ln Y ca U LLJLLWO F— MECHANICAL PLAN DATE JOB NO 10/22/18 "---- SCALE DRAWN BY SEE PLAN STORE NO. 7 DRAWING N0. M-2