HomeMy WebLinkAboutMINTHORN STREET 18520_14-00001268CITY OF
Lake Elsinore Fire Protection Planning
130 S. Main St. • Lake Elsinore, California 92530
951) 674-3124 Ext. 225 • Fax (951) 471-1491
Dbloom@Lake-Elsinore.Org
LA-1U LSINORE
DREAM E XT REME PERMIT
PERMIT NO: 14-00001268 DATE:
JOB ADDRESS • 18520 MINTHORN ST
DESCRIPTION OF WORK . : FIRE SERVICES
OWNER
ADVANCED INV
4741 E HUNTER AVE STE C
ANAHEIM, CA 92807
A.P.# ....
OCCUPANCY . .
CONSTRUCTION .
VALUATION . .
377-151-045 1
CONTRACTOR
5/19/14
OWNER
SQUARE FOOTAGE .
GARAGE SQ FT . .
FIRE SPRNKLR .
ZONE
0
0
M-1
FIRE SERVICES
QTY UNIT CHG
1.00 X 168.0000 LE FIRE MISC
ITEM CHARGE
168.00
FEE SUMMARY
PERMIT FEES
FIRE SERVICES
TOTAL
CHARGES
168.00
168.00
PAID
00
00
DUE
168.00
168.00
ecer: CaNIEFE Type: IF ll-wer: 1
ii 5/19/111 19 Receipt nu: 5Z76
2014 icy
EP BJILDINE PENT
1.00
Tarr mew:
at 0-EDc
Fran date: 5/19/14
00
177357
S159.03
ii1TE: 13:00:00
City of Lake Elsinore
Fire Services Division
Post in Conspicuous place
on the job
You must furnish PERMIT NUMBER and the
JOB ADDRESS for each respective inspection:
Approved plans must be on job
at all times:
Inspection request (951) 674 -3124 ext. 225
Please read and initial
L 1 am Licensed under the provisions of Business and professional Code Section 7000 et seq. and
my license is in full force.
2. I,as owner of the property,or my employees w /wages as their sole compensation will do the work
and the structure is not intended or offered for sale.
3. l,as owner of the property,am exclusively contracting with licensed contractors to construct the
project.
4. I have a certificate of consent to selfinsure or a certificate of Workers Compensation insurance
or a certified copy thereof.
5. I shall not employ any person in any manner so as to become subject to Workers Compensation
Laws in the performance of the work for which this permit is issued.
Note: If you should become subject to Workers Compensation after making this certification,
Code Approvals Date Inspector you must forthwith comply with such provisions or this permit shall be deemed revoked.
Sprinkler System Start Time Finish Time
SK01 UG Thrust Block PrePour
SK02 Underground Rough/Hydro
04 ;. _ S diliY 'Underground Flush
SK05 Weld Inspection
SK06 Overhead Rough /Hydro
SK99 !Overhead Final
SK08 High Pile Storage (FPE)
SK09 In -Rack Sprinklers
SK 10 Hose Racks
SK03 .Title 19 Verification
SK07 Bell /Main Drain /CMTC
Hydrant System
l- -
Date Inspector
HSO 1 U.G. ; Thrust Block Pre -Pour
I4S02 Underground Rough /Hydro
HSO3 Underground Flush
1S9 Final/Signs /CMTC
Knox System Date Inspector
K.S01 Knox Rapid Entry
fire Alarm Systems Date inspector 1 1 1
FA01 Fire Alarm Wiring Insp.
FA02 Fire Alarrn Function Test
FA03 Fire Alarm 24 Hr Battery
FA99 Fire Alarm Final
FA05 Sprinkler Monitoring
Fuel Storgae Tanks . Date Inspector
FT01 Underground Tank (S)
FTO2 Aboveground Tank (S)
FT03 Fuel Dispensers Only
Building Inspections Date Inspector
FT99 T/1 Final
FS99 Shell Final
Misc. Inspections Date Inspector
MIO I Spray Booths
i
MI02 Hood/Duet Suppression
M103 High Pile /Rack Storage
MI04 H.P. Vents /.Access /Corr.
MI05 Haz -Mat Verification
M106 Other: eANN), r“er A- to %e4 1,4 Ptir,1
CITY OF ., Lake Elsinore Fire Protection Planning
i Ccr 1 30 S. Main St. • Lake Elsinore, California 92530Lri" Jl (951) 674 -3124 Ext. 225 • Fax (951) 471 -1491
Dbloom @Lake- Elsinore.Org7 -- DREAM EXTREME.
41/(
a,8. °v PERMIT APPLICATION FORM
Permit No. /L/ — 0
Project Address: 0 r-1 Or n
Project Name: Of-a /)(1! 1 nc _-
I understand that afte the second submittal and after
Ski CSC' failed inspections that additional fees will be required.
Date: a-5 i 5 — k`f
Contact Information
CONTACT PERSON: Company Name. 1 QC,
E -mail Address: 040 6) ot-c'a V0kR. (Ow)
Plan Review T e Check a.r •ro •riate items
Commercial A Industrial Residential Special Event Other
Building Building Tenant Improvement High Fire Area Underground Water
Sprinkler System TI Sprinkler System Sprinkler Monitoring Fire Alarm System
Hood & Duct Suppression System Other Suppression System Spray Booth Cell Site
High Pile /Racks Other:
Storage Tank Submittals: Dispensers Only Above Ground Underground
1st Submittal Official Use Only
Received Date: a- Reviewed by: PC Review Date:
Plans: Approved Denied Letter Attached: Yes No Job Card Included: Yes No
Called for Pick -Up: Picked -Up Date: By
DateDate Applicant Sign
2nd Submittal Official Use Only
Received Date: Reviewed by: PC Review Date:
Plans: Approved Denied Letter Attached: Yes No Job Card Included: Yes No
Called for Pick -Up: Picked -Up Date: By:
DateDate
Resubmittal Fee Paid Date:
Applicant Sign
3rd Submittal Official Use Only
Received Date: Reviewed by: PC Review Date:
Plans: Approved Denied Letter Attached: Yes No Job Card Included: Yes No
Called for Pick -Up: Picked -Up Date: By:
Date Applicant SignDate
Resubmittal Fee Paid Date:
Visit us at www.lake- elsinore.org
Lake Elsinore Fire Protection Planning Fees
These are Flat Fees but there may be additional
resubmittal & inspection fees based on corrections.
Resubmittal & Reinspection Fee $168.00
Checks or Money Orders are to be made payable to:
City of Lake Elsinore
Plans are reviewed in the order they are received.
Plan Review /Inspection
Plan
Sets
Fee
Building 2 1,056.00 ( <50K)
528.00 each add 50K
Tenant Improvement Building 2 696.00
Tenant Improvement Building (Under 5,000 sq. ft.) 2 348.00
West r System Plans 2 614.00
Fire Sprinkler (per head) 3
100) $614.00
100- Riser) $921.00
Tenant improvement Sprinkler 3
20 or less) $307.00
21 -100) $614.00
100- Riser) $921.00
Residential Sprinkler 3
Plan Check $454.00
Insp. $210.00
Fire Alarm System 3
672 (1 -10 Ini. Dev)
1008 (11 -20 Ini. Dev)
1344 (20< Ini. Dev)
Sprinkler Monitoring System 3 454.00
Suppression Systems 3 454.00
Cell Tower Review (Generator /Batteries) 3 348.00
Abovegrould Fuel Storage Tank (first tank) 3 584.00
Each additional tank 168.00
High Pile or Rack Storage 3 348.00
Fire Flow Report 1 178.00
Technical Report — (FPE /Haz -Mat) 2 1008.00
Items not listed above are on a sliding scale starting at 168.00 - Up
Single Family Residential Review 2 75.00
After hours Inspections 168.00 per /hr. 2 hr.
min. (When available)
PAINTINGArea DRILLINGANDCLEANINGAreaWELDINGAreaFITTINGArea
AFAKORI WELDING INC. 18520 MINTHORN ST. LAKE ELSINORE CA, 92520
Gases stored within the premises as follows:
Acetylene dissolved, 4 tanks (110 c.f. ea.)
Oxygen compressed, 6 tanks (3 ea. at 150 c.f. and 3 ea. at 275 c.f.)
Compressed gas N.O.S. (75% argon, 25% carbon dioxide), 7 tanks (4 ea. at 300 c.f. and 3 ea. at
200 c.f.)
Argon compressed, 3 tanks (60 c.f. ea.)
Propane, 3 ea. forklift size tanks and 1 ea. small one.
Welding and cutting processes performed at premises as follows:
Flux cored arc welding, (FCAW)
Gas metal arc welding, mig (GMAW)
Tungsten inert gas welding, tig (GTAW)
Arc welding (SMAW)
Oxy- acetylene torch cutting.
CAL~
FIRE
SINCE fees
RIVERSIDE OU ` FIRE DEPARTMENT
IN COOPERATION WITH
THE CALIFORNIA DEPARTMENT OF FORESTRY AND FIRE PROTECTION
2300 Market St., Ste. 1 50 0 Riverside, California 92501
951) 955 -4777 • Fax (951) 955 -4886
77 -933 Las Montanas, Palm Desert, CA 9221 1
760) 863 -8886 ® Fax (760) 863 -7072
Inspection Hotline (951) 955 -5282
www.rvcfire.org
HOT WORK OPERATING PERMIT
PERMIT #: 14 -1 268 DATE OF ISSUE: 6 -6 -2014
JOB: AFAKORI WELDING
ADDRESS: 18520 MINTHORN, LAKE ELSINORE
To: LUZ AGREDA TENANT: AFAKORI INC
PHONE: 95 1 -245-1 707
E -MAIL: INFO @AFAKORI.COM
REVIEWED BY D. BLOOM DATE.' 6- 6-2014
up el
TERMS AND CONDITIONS
THIS PERMIT CONSTITUES PERMISSION TO MAINTAIN, STORE, USE OR HANDLE
MATERIALS, OR TO CONDUCT PROCESSES WHICH PRODUCE CONDITIONS
HAZARDOUS TO LIFE OR PROPERTY; OR TO INSTALL EQUIPMENT USED IN
CONNECTION WITH SUCH ACTIVITIES PROVIDED THE FIRE DEPARTMENT
CONDITIONS LISTED BELOW ARE MET AND MAINTAINED IN ACCORDANCE WITH
CALIFORNIA FIRE CODE, APPLICABLE REFERENCED STANDARD, AND /OR
CONDITIONS OF APPROVAL AS SET FORTH BY THIS DEPARTMENT. SUCH
PERMISSION SHALL NOT BE CONSTRUED AS AUTHORITY TO VIOLATE, CANCEL.
OR SET ASIDE ANY OF THE PROVISIONS OF THIS OR ANY OTHER CODE. THIS
PERMIT SHALL NOT TAKE THE PLACE OF ANY LICENSE REQUIRED BY LAW.
PERMIT APPLICANTS AND THE APPLICANTS' AGENTS AND EMPLOYEES SHALL
CARRY OUT THE ACTIVITIES AS LISTED BELOW IN COMPLIANCE WITH THE
INTERNATIONAL FIRE CODE AND OTHER LAWS OR REGULATIONS APPLICABLE
THERETO, WHETHER SPECIFIED OR NOT, AND IN COMPLETE ACCORDANCE
WITH APPROVED PLANS AND SPECIFICATIONS. SAID CALIFRNIA FIRE CODE
SHALL BE 2013 EDITION AS ADOPTED BY THE LAKE ELSINORE MUNICIPAL CODE.
THIS PERMIT SHALL BE KEPT ON THE PREMISE(S) DESIGNATED ABOVE AT ALL
TIMES AND SHALL BE POSTED IN A CONSPICOUS LOCATION ON THE PREMISE(S)
AND SHALL BE SUBJECT TO INSPECTION AT ANY TIME ON DEMAND OF AN
OFFICER OF THE FIRE DEPARTMENT OR ANY PEACE OFFICER OR OTHER
PERSONS AS DESIGNATED BY THE CHIEF OF THE FIRE DEPARTMENT.
1
SPECIFIC OPERATING REQUIREMENTS AND CONDITIONS
Hot Work
2601.3 RESTRICTED AREAS-
1. Areas where there exists the potential of an explosive atmosphere, such as locations
where flammable gases, liquids or vapors are present.
2. Areas with readily ignitable materials, such as storage of large quantities of bulk sulfur,
baled cotton, lint, dust or loose combustible materials.
2603.3 Hot work program permit- Hot work permits, issued by an approved responsible
person under a hot work program, shall be available for review by the fire code official at
the time the work is conducted and for 48 hours after work is complete.
2603.4 Qualifications of operators- A permit for hot work operations shall not be issued
unless the individuals in charge of performing such operations are capable of performing
such operations safely. Demonstration of a working knowledge of the provisions of this
chapter shall constitute acceptable evidence of compliance with this requirement.
2603.5 Records- The individual responsible for the hot work area shall maintain "prework
check" reports in accordance with Section 2604.3.1. These reports shall be maintained on
the premises for a minimum of 48 hours after work is complete.
2603.6 Signage- Visible hazard identification signs shall be provided where required by
Chapter 27. Where the hot work area is accessible to persons other than the operator of
the hot work equipment, conspicuous signs shall be posted to warn others before they
enter the hot work area. Such signs shall display the following warning:
CAUTION
HOT WORK IN PROGRESS
STAY CLEAR.
2604.1 Protection of combustibles- Protection of combustibles shall be in accordance
with Sections 2604.1.1 through 2604.1.9.
2604.1.1 Combustibles- Hot work areas shall not contain combustibles or shall be
provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed
combustibles.
2604.1.2 Openings- Openings or cracks in walls, floors, ducts or shafts within the hot
work area shall be tightly covered to prevent the passage of sparks to adjacent
combustible areas, or shielded by metal fire - resistant guards, or curtains shall be
provided to prevent passage of sparks or slag.
2604.1.3 Housekeeping- Floors shall be kept clean within the hot work area.
2604.1.5 Partitions- Partitions segregating hot work areas from other areas of the
building shall be noncombustible. In fixed hot work areas, the partitions shall be securely
connected to the floor such that no gap exists between the floor and the partition.
Partitions shall prevent the passage of sparks, slag, and heat from the hot work area.
2604.1.6 Floors- Fixed hot work areas shall have floors with noncombustible surfaces.
2604.1.7 Precautions in hot work- Hot work shall not be performed on containers or
equipment that contains or has contained flammable liquids, gases or solids until the
2
containers and equipment have been thoroughly cleaned, inerted or purged; except that
hot tapping" shall be allowed on tanks and pipe lines when such work is to be conducted
by approved personnel.
2604.1.9 Fire detection systems- Approved special precautions shall be taken to avoid
accidental operation of automatic fire detection systems.
2604.2 Fire watch- Fire watches shall be established and conducted in accordance with
Sections 2604.2.1 through 2604.2.6.
2604.2.1 When required- A fire watch shall be provided during hot work activities and
shall continue for a minimum of 30 minutes after the conclusion of the work. The fire code
official, or the responsible manager under a hot work program, is authorized to extend the
fire watch based on the hazards or work being performed.
Exception: Where the hot work area has no fire hazards or combustible exposures.
2604.2.2 Location- The fire watch shall include the entire hot work area. Hot work
conducted in areas with vertical or horizontal fire exposures that are not observable by a
single individual shall have additional personnel assigned to fire watches to ensure that
exposed areas are monitored.
2604.2.3 Duties- Individuals designated to fire watch duty shall have fire - extinguishing
equipment readily available and shall be trained in the use of such equipment. Individuals
assigned to fire watch duty shall be responsible for extinguishing spot fires and
communicating an alarm.
2604.2.4 Fire training- The individuals responsible for performing the hot work and
individuals responsible for providing the fire watch shall be trained in the use of portable
fire extinguishers.
2604.2.6 Fire extinguisher- A minimum of one portable fire extinguisher complying with
Section 906 and with a minimum 2- A:20 -B:C rating shall be readily accessible within 30
feet (9144 mm) of the location where hot work is performed.
2604.3 Area reviews- Before hot work is permitted and at least once per day while the
permit is in effect, the area shall be inspected by the individual responsible for authorizing
hot work operations to ensure that it is a fire safe area. Information shown on the permit
shall be verified prior to signing the permit in accordance with Section 105.6.
2604.3.1 Pre - hot -work check- A pre- hot -work check shall be conducted prior to work to
ensure that all equipment is safe and hazards are recognized and protected. A report of
the check shall be kept at the work site during the work and available upon request. The
pre- hot -work check shall determine all of the following:
1. Hot work equipment to be used shall be in satisfactory operating condition
and in good repair.
2. Hot work site is clear of combustibles or combustibles are protected.
3. Exposed construction is of noncombustible materials or, if combustible,
then protected.
4. Openings are protected.
5. Floors are kept clean.
3
6. No exposed combustibles are located on the opposite side of partitions,
walls, ceilings or floors.
7. Fire watches, where required, are assigned.
8. Approved actions have been taken to prevent accidental activation of
suppression and detection equipment in accordance with Sections
2604.1.8 and 2604.1.9.
9. Fire extinguishers and fire hoses (where provided) are operable and
available.
2605.3 Precautions- Cylinders, valves, regulators, hose and other apparatus and fittings
for oxygen shall be kept free from oil or grease. Oxygen cylinders, apparatus and fittings
shall not be handled with oily hands, oily gloves, or greasy tools or equipment.
2605.5 Remote locations- Oxygen and fuel -gas cylinders and acetylene generators shall
be located away from the hot work area to prevent such cylinders or generators from
being heated by radiation from heated materials, sparks or slag, or misdirection of the
torch flame.
2605.6 Cylinders shutoff- The torch valve shall be closed and the gas supply to the
torch completely shut off when gas welding or cutting operations are discontinued for a
period of 1 hour or more.
2605.7 Prohibited operation- Welding or cutting work shall not be held or supported on
compressed gas cylinders or containers.
2605.8 Tests- Tests for leaks in piping systems and equipment shall be made with soapy
water. The use of flames shall be prohibited for leak testing.
2609.7 Inspection- Hoses shall be inspected frequently for leaks, burns, wear, loose
connections or other defects rendering the hose unfit for service.
y Fire Safety Specialist Date
Doug Bloom
Owner/ Tenant
F-4
Print Name)
aYr.a 6c c.id J
By Fire Systems Inspector
Pr nt Name)
Date
Vol '1y
Date
4