Loading...
HomeMy WebLinkAboutPAR-2023-06 #2 FIRE COMMENTS Planning Case Comments September 25, 2023 PA 2022-23 PAR 2023-06 West Nichols Logistics Center Multiple APN PLANNER: Joey Mendoza, Associate Planner REVIEWED BY: Traci Williams, Fire Marshal The Fire Department has reviewed this submittal and provides the following comments: 1. The applicant must provide a fire hydrant system capable of delivering fire flow as required by the California Fire Code and Fire Department standards. Fire hydrants shall be spaced in accordance with the California Fire Code. Based on current standards, the required fire flow is estimated to be 4,000 GPM at 20 PSI for a 4 hour duration. Estimated fire flow is based on a 1,225,000 square foot building area with Type III-B construction and the building having a fire sprinkler system per 2022 California Fire Code. 2. The applicant must provide a fire command center for buildings larger than 300,000 square feet in area in accordance with California Fire Code 508, Lake Elsinore Municipal Code Section 15.56 and fire department standards. 3. The applicant will need to evaluate the need for emergency responder radio coverage inside the building in accordance with California Fire Code Section 510. Prior to building plan review, the applicant is encouraged to contact the Riverside County Fire Department for radio requirements. In Cooperation With The California Department of Forestry and Fire Protection 130 South Main Street, Lake Elsinore, CA 92530 • Phone (951) 674-3124 www.rvcfire.org Proudly serving the unincorporated areas of riverside county and the cities of: Banning Beaumont Canyon Lake Coachella Desert Hot Springs Eastvale Indian Wells Indio Jurupa Valley Lake Elsinore La Quinta Menifee Moreno Valley Norco Palm Desert Perris Rancho Mirage Rubidoux CSD San Jacinto Temecula Wildomar BOARD OF SUPERVISORS: Kevin Jeffries District 1 Karen Spiegel District 2 CHARLES WASHINGTON District 3 V. Manual Perez District 4 Jeff Hewitt District 5 4. Gates must meet Fire Department standards at the time of building permit application. 5. Hazardous Fire Area: this project is in a Very High Fire Hazard Severity Zone of Riverside County as shown on a map on file with the Clerk of the Board of Supervisors. Any building constructed within this project shall comply with special construction provisions contained in the California Building Code. 6. In the interest of Public Safety, the project sh all provide an Alternate or Secondary Access(s). Said Alternate or Secondary Access(s) shall have concurrence and approval of both the City Engineering Department and the Riverside County Fire Department. 7. Prior to issuance of Building Permits, the applicant/developer shall provide the Office of the Fire Marshal with an approved site plan for Fire Lanes and signage. (CFC 501.3) These comments are preliminary; further review will occur upon receiving further planning applications. Additional conditions may be necessary at that time. Please feel free to contact me with any questions.