HomeMy WebLinkAboutPAVEMENT DESIGN REPORT i"
s,
Geotechnical ® Coastal . Geologic m Environmental
26590 Madison Avenue • Murrieta, California 92562 • (951) 677-9651 • FAX(951) 677-9301
May 12, 2006
W.O. 4511-E-SC
Lennar Homes
40980 County Center Road, Suite 100
Temecula, California 92591
Attention: Ms. Ellen Michiel
Subject: Pavement Design Report for Bankhall Street (Station ±10+00 to ±19+00),
Camden Circle (Station ±18+40 to ±20+00), Diana Lane (Station ±10+00
to ±20+50), Third Street (Station ±27+os to ±29+99), and Offsite Third Street
(Station ±11+40 to +27+06), Tract 31792, Wasson Canyon Area, City of
Lake Elsinore, Riverside County, California
References: 1. "Street Improvement Plans For: Conrad Avenue and Third Street, M.S. 4036 (For Tract
No. 31792, City of Lake Elsinore),"Job No. 63514.10, dated March 21, 2006, by SB&O, Inc.
2. "Street Improvement Plans For: City of Lake Elsinore, Tract No. 31792, Wasson Canyon,"
Job No. 635112.10, plotted March 21, 2006, by SB&O, Inc.
Dear Ms. Michiel:
In accordance with your request, GeoSoils, Inc. (GSI) is submitting herewith final pavement
design recommendations for the above roadways (onsite and offsite) for Tract 31792,
Lake Elsinore, Riverside County, California. Representative samples of the subgrade soils
were obtained and tested to determine the R-value. The material is thought to be typical and
presumed to be representative of the subgrade soils. Testing was performed in general
accordance with the latest revisions to the Department of Transportation, State of California,
Material & Research Test Method No. 301. The test results are presented on the enclosed
R-value Test Results, Figures 1 through 4.
RECOMMENDED PAVEMENT SECTIONS
The pavement sections presented on the following page are based on the R-value data
collected, the Traffic Index (T.I.) indicated on the street improvement "plans (see above
References), and the guidelines presented in the latest revision to the California Department
of Transportation "Highway Design Manual," fifth edition. It is our understanding that the
minimum pavement section required by the City of Lake Elsinore is 3.0 inches of AC
(asphaltic concrete) over 4 inches of Class 2 Aggregate Base for local roads.
ASPHALTIC CLASS 2 BASE
LOCATION TRAFFIC UNTREATED CONCRETE ROCK*
INDEX SUBGRADE THICKNESS THICKNESS
R-VALUE INCHES (INCHES)
Bankhall
Station ±10+ 0-to ±19+00 5.5 38 3.0 5.5
Camden Circle
Station ±1 WE to ±20+00 5.5 17 3.0 9.5
Diana Lane
Station ±10+2 to ±20+so 5.5 17 3.0 9.5
(Onsite) Third Street
Station *27+26 to ±29+2e 5.5 17 3.0 9.5
(Offsite) Third Street
Station ±19+0o to ±27+os 5.5 16 3.0 10.0
(Offsite) Third Street
Station ±11+42 to ±19+00 5.5 15 3.0 10.0
Denotes Caltrans Standard Class 2 aggregate base rock or equivalent(J >78,SE > 25).
The preliminary pavement sections provided above are intended as a minimum guideline.
If thinner or highly variable pavement sections are constructed, increased maintenance and
repair could be expected. If the average daily traffic (ADT) or average daily truck traffic
(ADTT) increases beyond that intended, as reflected by the TI used for design, increased
maintenance and repair could be required for the pavement section. Consideration should
be given to the increased potential for distress from overuse of paved street areas by heavy
equipment and/or construction related heavy traffic (i.e., concrete trucks, loaded supply
trucks, etc.), particularly when the final section is not in place (i.e., topcoat). Best
management construction practices should be followed at all times, especially during
inclement weather.
PAVEMENT GRADING RECOMMENDATIONS
General
All section changes should be properly transitioned. If adverse conditions are encountered
during the preparation of subgrade materials, special construction methods may need to be
employed. A representative of GSI should be present for the preparation of subgrade, base
rock, and asphalt concrete.
Lennar Homes W.O. 4511-E-SC
Tract 31792, Wasson Canyon May 12, 2006
File:e:\wp10\murr\rc4500\4511 e.pdr Page 2
GeoSoils, Inc.
Subgrade
Within street and parking areas,all surficial deposits of loose soil material should be removed
and recompacted as recommended. After the loose soils are removed, the bottom is to be
scarified to a depth of at least 6 inches, moisture conditioned as necessary and compacted
to 95 percent of the maximum laboratory density or City minimum, as determined by ASTM
Test Designation D-1557.
Deleterious material, excessively wet or dry pockets, concentrated zones of oversized rock
fragments, and any other unsuitable materials encountered during grading should be
removed. The compacted fill material should then be brought to the elevation of the
proposed subgrade for the pavement. The subgrade should be proof-rolled in order to
ensure a uniform firm and unyielding surface. All grading and fill placement should be
observed by the project soil engineer and/or his representative.
Base Rock
Compaction tests are required for the recommended base section. Minimum relative
compaction required will be 95 percent of the laboratory maximum density as determined by
ASTM Test Designation D-1557. Base aggregate should be in accordance with the Caltrans
Class 2 base rock (minimum R-value=78).
Paving
Prime coat may be omitted if all of the following conditions are met:
1. The asphalt pavement layer is placed within two weeks of completion of base and/or
subbase course.
2. Traffic is not routed over completed base before paving
3. Construction is completed during the dry season of May through October.
4. The base is kept free of debris prior to placement of asphaltic concrete.
If construction is performed during the wet season of November through April, prime coat
may be omitted if no rain occurs between completion of base course and paving and the time
between completion of base and paving is reduced to three days, provided the base is free
of loose soil or debris. Where prime coat has been omitted and rain occurs, traffic is routed
over base course, or paving is delayed, measures shall be taken to restore base course, and
subgrade to conditions that will meet specifications as directed by the soil engineer.
Lennar Homes W.O. 4511-E-SC
Tract 31792, Wasson Canyon May 12, 2006
File:e:\wp10\murr\rc4500\4511e.pdr Page 3
GeoSoils, Inc.
Drainage
Positive drainage should be provided for all surface water to drain towards the area swale,
curb and gutter, or to an approved drainage channel. Positive site drainage should be
maintained at all times. Water should not be allowed to pond or seep into the ground, such
as from behind unprotected curbs, both during and after grading. If planters or landscaping
are adjacent to paved areas, measures should be taken to minimize the potential for water
to enter the pavement section, such as thickened edges, enclosed planters, etc. Also, best
management construction practices should be strictly adhered to at all times to minimize the
potential for distress during construction and roadway improvements.
Additional Considerations
To mitigate perched groundwater, consideration should be given to installation of subgrade
separators (cut-offs) between pavement subgrade and landscape areas, although this is not
a requirement from a geotechnical standpoint. Cut-offs, if used,should be 6 inches wide and
at least 12 inches below the pavement subgrade contact or 12 inches below the aggregate
base rock.
LIMITATIONS
The materials encountered on the project site and utilized for our analysis are believed
representative of the area; however, soil and bedrock materials vary in character between
excavations and natural outcrops or conditions exposed during mass grading. Site
conditions may vary due to seasonal changes or other factors.
Inasmuch as our study is based upon our review and engineering analyses and laboratory
data,the conclusions and recommendations are professional opinions. These opinions have
been derived in accordance with current standards of practice, and no warranty, either
express or implied, is given. Standards of practice are subject to change with time. GSI
assumes no responsibility or liability forwork or testing performed by others, or their inaction;
or work performed when GSI is not requested to be onsite, to evaluate if our
recommendations have been properly implemented. Use of this report constitutes an
agreement and consent by the user to all the limitations outlined above, notwithstanding any
other agreements that may be in place. In addition, this report may be subject to review by
the controlling authorities. Thus, this report brings to completion our scope of services for
this portion of the project. All samples will be disposed of after 30 days, unless specifically
requested by the client, in writing.
Lennar Homes W.O. 4511-E-SC
Tract 31792, Wasson Canyon May 12, 2006
F 1e:e:\wp10\murr\rc4500\4511 e.pdr Page 4
GeoSoils, Inc.
The opportunity to be of service is sincerely appreciated. If you shout ny
questions, please do not hesitate to contact our office. oOoFESSiov
\N Ski` ��Gl Respectfully sub 5 AL
�5 P FR,q
GeoSoils, In . Q o N�iOu) Via' C�� 57
No. 1340 -t
CertifiedEngineerino
Oeoloplst �-
ohn P. Franklin OF CAL\F°P David W. Skelly
ngineering Geologis , 1340 Civil Engineer, RCE 47857
BEV/JPF/DWS/jh/ps
Enclosures: Figures 1 through 4 - R-value Test Results
Distribution: (4) Addressee
Lennar Homes W.O. 4511-E-SC
Tract 31792, Wasson Canyon May 12, 2006
File:e:\wp10\murr\rc4500\4511 e.pdr Page 5
GeoSoils, Inc.
TEST SPECIMAN A B C D
Compactor air pressure PSI 350 350 170
Water added % 1.0 1.9 2.7
Moisture at compaction _ % 10.0 11.0 11.9
Height of sample IN 2.46 2.43 2.5
Dry density PCF 126.3 126.6 122.8
R Value by exudation 59 40 22
R-Value by exudation, corrected 59 38 22
Exudation pressure PSI 719 310 184
Stability thickness FT 0.52 0.77 1.00
Expansion pressure thickness FT 1 0.301 0.101 0.00
DESIGN CALCULATION DATA SAMPLE INFORMATION
Traffic index, assumed 5.0 Sample location: Bankhall Street 10+00-19+00
Gravel equivalent factor,assumed 1.25 Sample Description: Dark Gray Silty Gravel'W/Sand
Expansion,stability equilibrium 0 Notes:
R-Value by expansion NA 11% Retained on 3/4 inch sieve
R-Value by exudation 38 Test Method: Cal-Trans Test 301
R-Value at equilibrium 38
R-Value By Exudation
80
Expansion,Stability Equilibrium
2.00 70 - —
— — — — 60
i'1.50 - -
- — — 50-
N — a�
— — —— 40 -
S 1.00 aC
c
Y 30
t>
Z
0.50 - — 20 -
o -
-- 10
0.00 U/# 0
0.00 0.50 1.00 1.50 2.00 800 700 600 500 400 300 200 100 0
Cover Thickness by Expansion Pressure(ft) Exudation Pressure(psi)
GeoSoils, Inc.
R.-VALUE TEST RESULTS
5741 Palmer Way Project: LENNAR HOMES
. Carlsbad, CA 92008
Telephone:(760)438-3155 Number: 4511-E-SC
Fax: (760)931-0915
Date: May-06 Figure: 1
TEST SPECIMAN A B C D
Compactor air pressure PSI 350 230 110
Water added % 2.2 3.1 4.1
Moisture at compaction % 11.0 12.0 13.0
Height of sample IN 2.36 2.38 2.47
Dry density PCF 129.0 127.0 121.1
R-Value by exudation 40 22 11
R-Value by exudation, corrected 36 21 11
Exudation pressure PSI 489 355 211
Stability thickness FT 0.84 1.10 1.25
Expansion pressure thickness FT 1.03 0.70 0.37
DESIGN CALCULATION DATA SAMPLE INFORMATION
Traffic index, assumed 5.5 1 Sample Location: Diana Lane 10+00-20+50,Camden 18+40-20+00
Gravel equivalent factor, assumed 1.25 Sample Description: Dark Gray Clayey Gravel W/Sand
Expansion, stability equilibrium 0.89 Notes: Includes Third Street 26+70-29+99
R-Value by expansion 37 20% Retained on 3/4 inch sieve
R-Value by exudation 17 Test Method: Cal-Trans Test 301
R-Value at equilibrium 17
R-Value By Exudation
Expansion,Stability Equilibrium 80
2.00 70 -
60
1'1.50
50
y
40
11.00
-
30
c 0.50 20
V
10
0.00 0
0.00 0.50 1.00 1.50 2.00 800 700 600 500 400 300 200 100 0
Cover Thickness by Expansion Pressure(ft) Exudation Pressure(psi)
GeoSoils, Inc.
R -VALUE TEST RESULTS
5741 Palmer Way Project: LENNAR HOMES
N . Carlsbad, CA 92008
Telephone: (760)438-3155 Number: 4511-E-SC
Fax: (760)931-0915
Date: May-06 Figure: 2
TEST SPECIMAN A B C D
Compactor air pressure PSI 350 280 160
Water added % 2.0 2.9 3.8
Moisture at compaction % 10.0 11.0 12.0
Height of sample IN 2.4 2.41 2.45
Dry density PCF 125.8 124.9 123.3
R-Value by exudation 34 23 12
R-Value by exudation, corrected 32 22 12
Exudation pressure PSI 5231 3891 239
Stability thickness I FT 0.931 1.08 1.24
Expansion pressure thickness I FT 0.401 0.231 0.17
DESIGN CALCULATION DATA SAMPLE INFORMATION
Traffic index, assumed 5.5 Sample Location: Third Street 19+00-27+06
Gravel equivalent factor, assumed 1.25 Sample Description: Dark Yellow Brown Clayey Sand WI Gravel
Expansion, stability equilibrium 0 Notes:
R-Value by expansion NA 10% Retained on 3/4 inch sieve
R-Value by exudation 16 Test Method: Cal-Trans Test 301
R-Value at equilibrium 16
R-Value By Exudation
Expansion,Stability Equilibrium 80
2.00 70
w 60
:�'1.50
50
W
j 40
01.00
d
c
30
L
H
c 0.50 20
U
10
0.00 0 .1
0.00 0.50 1.00 1.50 2.00 800 700 600 500 400 300 200 100 0
Cover Thickness by Expansion Pressure(ft) Exudation Pressure(psi)
GeoSoils, Inc.
R -VALUE TEST RESULTS
L 5741 Palmer Way Project: LENNAR HOMES
Carlsbad, CA 92008
Telephone: (760)438-3155 Number: 4511-E-SC
Fax: (760) 931-0915
Date: Mav-06 Figure: 3
TEST SPECIMAN A B C D
Compactor air pressure PSI 280 160 130
Water added % 1.7 2.7 3.6
Moisture at compaction % 11.0 12.0 13.0
Height of sample IN 2.34 2.36 2.45
Dry density PCF 127.0 125.4 120.0
R-Value by exudation 39 18 12
R-Value by exudation, corrected 35 17 12
Exudation pressure PSI 513 327 264
Stability thickness FT 0.86 1.15 1.24
Expansion pressure thickness FT 1 0.731 0.43 0.07
DESIGN CALCULATION DATA SAMPLE INFORMATION
Traffic index, assumed 5.5 1 Sample Location: Third Street 11+40-19+00
Gravel equivalent factor, assumed 1.25 Sample Description: Yellow Brown Sandy Clay W/Gravel
Expansion, stability equilibrium 0 Notes:
R-Value by expansion NA 3% Retained on 3/4 inch sieve
R-Value by exudation 15 Test Method: Cal-Trans Test 301
R-Value at equilibrium 15
R-Value By Exudation
80
Expansion,Stability Equilibrium — - —
2.00 70
60
Z'1.50
Z 50
Cn m
-I--fall j 40
1.00 . '
c —
30
's
f-
0 0.50 20
V
10 -
0.00 -/ 0
0.00 0.50 1.00 1.50 2.00 800 700 600 500 400 300 200 100 0
Cover Thickness by Expansion Pressure(ft) Exudation Pressure(psi)
GeoSoils, Inc. R -VALUE TEST RESULTS
��r" 5741 Palmer Way Project: LENNAR HOMES
,, ,. Carlsbad, CA 92008
Telephone: (760)438-3155 Number: 4511-E-SC
Fax: (760)931-0915
Date: May-06 Figure: 4