HomeMy WebLinkAboutCC Reso No 1989-50RESOLUTION NO. 89- 50
A RESOLUTION OF THE CITY COUNCIL OF THE CITY
OF LAKE ELSINORE, CALIFORNIA, ESTABLISHING
POLICY RELATING TO SEISMIC HA2ARD
YDENTIFICATION AND REDUCTION PROGRAM.
' WHEREAS, the State of California Legislature in 1986
adopted SB-547 requiring all jurisdictions in Seismic Zone Four
to inventory all buildings with unreinforced masonry walls and
develop a hazard mitigation program; and
WHEREAS, it is the Council's intent in adopting the
policy contained herein to identify and promote public safety by
reducing the risk of death or injury that may result from the
effects of earthquakes on buildings that have been identified as
potentially hazardous.
NOW, THEREFORE, BE IT RESOLVED that the City Council of
the City of Lake Elsinore, California, does hereby establish the
policy relating to seismic hazard identification and reduction
program, as follows:
POLICY
The provisions of these sections are minimum standards for
structural seismic resistance established primarily to reduce the
risk of loss of life or injury and will not necessarily prevent
loss of life or injury or prevent earthquake damage to an exist-
ing building wlxich complies with these sections.
1.0 SCOPE OF PROGRAM
A. Scope. Building defined as "potentially hazardous" may
have the hazard mitigated by strengthening or removal.
Exception: Residential structures containing five (5) or
less dwelling units.
2.0 BUILDING CATEGORIES AND IMPLEMENTATION SCHEDULE
A. Buildina Cateaories. The categories of buildings within
the scope of this policy are set forth in the building
survey attached.
B. Owner Notification. The owners of buildings listed on
the building survey shall be notified by the Building and
Safety Department that they own a potentially hazardous
1
structure. They also will be informed that the Building
Department can provide information and standards
regarding retrofit of these buildings.
C. Imnlementation. The owners of building must submit
engineering reports, plans for correction and mitigate
the hazard only when structural alterations are done to
the building. Documentation acceptable to the Building
Official shall be submitted relative to exempt buildings.
The Building Official may require additional tests,
_. inspections or reports to substantiate the exemption.
3.0 DEFINITIONS
A. "Bearina wall" means any wall supporting a floor or roof
where the total superimposed load exceeds one hundred
(100) pounds per linear foot, or any unreinforced masonry
wall over six (6) feet in height supporting its own
weight.
B. "BUildina", for the purpose of determining occupant load,
means any contiguous or interconnected structure; for
purposes of engineering evaluation, means the entire
structure or a portion thereof which will respond to
seismic forces as a unit.
u
C. "Civil engineer or structural engineer means a licensed
civil or structural engineer registered by the State of
California pursuant to the rules and regulations of Title
16, Chapter 5 of the California Administrative Code.
D. "Occunants1° means the total occupant load of a building
determined by Table 33-A of the current edition of the
Uniform Building Code.
E. "Unreinforced Mason URM " building means any building
containing walls constructed wholly or partially with any
of the following materials:
1. Unreinforced brick masonry
2. Unreinforced concrete masonry
3. Hollow clay tile
4. Adobe or unburned clay masonry
4.0 STRENGTHENING.
Strengthening of unreinforced masonry bearing wall building.
4.1 SCOPE.
The requirements of this section shall apply to all building
or all unreinforced masonry bearing wall structures.
Exception: This section shall not apply to residential
structures containing five (5) or less dwelling units.
4.2 ALTERNATE MATERIALS.
Alternate materials, designs and methods of construction may
be approved by the Building Official in accordance with this
code.
4.3 DEFINITIONS
A. "Cross Walls" are interior walls of masonry or wood frame
construction with surface finish of wood lath and plaster
or minimum 1/2" gypsum wall board. Such walls shall be
full story height with a minimum length of 1 1/2 times
the story height. Cross walls shall be spaced less than
2
40 feet apart in each story.
B. "Essential Facilities" are those structures or buildings
housing an occupancy or use classified as essential
facilities under the earthquake regulations of the
Building Code.
C. "Unreinforced Masonrv Bearina Wall": A masonry wall
having all of the following characteristics:
1. Provides the vertical support for a floor or roof.
2. The total superimposed load is over 100 pounds per
linear foot.
3. The area of reinforcing steel is less than 50 percent
of that required by the Building Code.
4.4
HISTORIC BUILDINGS
A. General. A historic building or structure may comply
with the special provisions set forth in this section and
the State Historic Building Code.
B. Unburned Clav Masonrv or Adobe. Existing or re-erected
walls of adobe construction shall conform to the
following:
1. Unreinforced adobe masonry walls shall not exceed a
height or length to thickness ratio of 5, for
exterior bearing walls and must be provided with a
reinforced bond beam at the top, interconnecting all
walls. Minimum beam depth shall be 6 inches and a
minimum width of 8 inches less than the wall width.
Minimum wall thickness shall be 18 inches for
exterior bearing walls and 10 inches for adobe
partitions. No adobe structure shall exceed one
story in height unless the historic evidence
indicates a two story height. In such cases the
heiqht to thickness ratio shall be the same as above
for the first floor based on the total two story
height and the second floor wall thickness shall not
exceed the ratio 5 by more than 20 percent. Bond
beams shall be provided at the roof and second floor
levels.
2. Foundation footings shall be reinforced concrete
under newly reconstructed walls and shall be 50
percent wider than the wall above, soil conditions
permitting, except that the foundation wall may be 4
inches less in width than the wall if a rock, burned
brick, or stabilized adobe facing is necessary to
provide authenticity.
3. New or existing unstabilized brick and adobe brick
masonry shall test to 75 percent of the compressive
strength required by the Building Code for new
material. Unstabilized brick may be used where
existing bricks are unstabilized and and where the
building is not susceptible to flooding conditions or
direct exposure. Adobe may be allowed a maximum
value of 3 pounds per square inch for shear with no
increase for lateral forces.
4. Mortar may be of the same soil composition and
stabilization as the brick in lieu of cement mortar.
5. Nominal tension stresses due to seismic forces normal
to the wall may be neglected if the wall meets
thicknesses requirements and shear values allowed by
3
this subsection.
C. Archaic Materials. Allowable stresses for archaic
materials not specified in this code shall be based on
substantiating research data or engineering judgment with
the approval of the Buildinq Official.
4.5 ANALYSIS AND DESIGN
A. General. Every structure within the scope of this
section shall be analyzed and constructed to resist
minimum total lateral seismic forces assumed to act
nonconcurrently in the direction of each of the main axes
of the structure in accordance with the the following
equation:
V+IKCSW (A1-1)
The value of KCS need not exceed the values set forth in
Table Al-A based on the seismic zone as determined by the
Building Code, The I factor shall be as specified in
Table A1-B. The value of W shall be as set forth in the
Building Code.
B. Lateral Forces on Elements of Structures. Parts or
portions of buildings and structures shall by analyzed
and designed for lateral loads in accordance with Section
23 of the Building Code but not less that the value for
the following equation:
Fp= ICpSWp (A1-2)
For the provisions of this section, the product of IS
need not exceed the values as set forth in Table A1-C,
The value of Cp and Wp shall be as set forth in the
Building Code.
Exception: Unreinforced masonry walls in buildings not
required to be designed as an essential building may be
designed in accordance with Section 4.6.
C. Anchoraae and Interconnection. Anchorage and
interconnection of all parts, portions and elements of
the structure shall be analyzed and designed for lateral
forces in accordance with Section 23 of this Code and the
equation Fp=2Cp SWp as modified by Table No. A1-C.
Minimum anchoraqe of masonry walls to each floor or roof
shall resist a minimum force of 200 pounds per linear
foot acting normal to the wall at the level of the floor
or roof.
D. Level of Required ReAair. Alterations and repairs
required to meet the provisions of this resolution shall
comply with all other applicable requirements of the
Building Code unless specifically provided for in this
section.
E. Reauired Analysis.
1. General. Except as modified herein, the analysis and
design relating to the structural alteration of
existing structures with the scope of this section
shall be in accordance with he analysis specified in
Chapter 23 of the Building Code.
2. Continuous Stress Path. A complete, continuous
stress path from every part or portion of the
4
structure to the ground shall be provided for the
required horizontal forces.
3. Positive Connections. All parts, portions or ele-
ments of the structure shall be interconnected by
positive means.
F. Analvsis Procedure
1. General. Stresses in materials and existing
construction utilized to transfer seismic forces from
the ground to parts or portions of the structure
shall conform to those permitted by the Code and
those materials and types of construction specified
in Section 4.6.
2. Connections. Materials and connectors used for
interconnection of parts and portions of the
structure shall conform to the Building Code. Nails
may be used as a part of an approved connector.
3. Unreinforced Masonrv Walls. Unreinforced masonry
walls shall be analyzed as specified in the Building
Code to withstand all vertical loads as specified in
Chapter 23 of the Building Code in addition to the
seismic forces required by this section. Such walls
shall meet the minimum requirements set forth in the
Building Code. The 50 percent increase in the
seismic force factor for shear walls as specified in
Table 24-H of the Building Code may be omitted in the
computation of seismic loads to existing shear walls.
No allowable tension stress will be permitted in
unreinforced masonry walls. Walls not capable of
__ resisting the required design forces specified in
this section shall be strengthened or shall be
removed and replaced.
Exceptions•
a. Unreinforced masonry walls in buildings not
classified as an essential building may be
analyzed in accordance with Section 5.7.
b. Unreinforced masonry walls which carry no design
loads other than its own weight may be considered
as veneer if they are adequately anchored to new
supporting elements.
G. Combination of Vertical and Seismic Forces
1. New Materials. All new materials introduced into
the structure to meet the requirements of this
Section which are subjected to combined vertical and
horizontal forces shall comply with Chapter 23 0£ the
Building Code.
2. Existina Materials. When stress in existing lateral
force resisting elements are due to a combination of
- dead loads plus live loads plus seismic loads, the
allowable working stress specified in the Building
~ Code may be increased 100 percent. However, no
increase will be permitted in the stresses allowed in
Section 4.6. The stresses in member due only to
seismic and dead loads shall not exceed the values
permitted by Chapter 23 of the Building code.
3. Allowable Reduction of Bendina Stress bv Vertical
Load. In calculating tensile fiber stress, stresses
5
may be reduced by the
vertical dead loads.
4.6 MATERIALS OF CONSTRUCTION
full direct stress due to
A. General. All materials permitted by this Code including
their appropriate allowable stresses and those existing
configurations of materials specified herein may be
utilized to meet the requirements of this section.
B. Existina Materials.
1. Unreinforced Masonrv Walls. Unreinforced masonry
walls analyzed in accordance with this section may
provide vertical support for roof and floor
construction and resistance to lateral loads. The
bonding of such walls shall be as specified in the
Building Code. Tension stresses due to seismic
forces normal to the wall may be neglected if the
walls do not exceed the height or length to
thickness ratio set forth in Table A1-D and the
in-plane shear stresses due to seismic loads as set
forth in Table No. Al-G.
If the wall height-thickness ratio exceeds the
specified limits, the wall may be supported by
vertical bracing members designed by the
requirements of Chapter 23 of the Building Code.
The deflection of such bracing member at design
loads shall not exceed one-tenth of the wall
thickness.
Exception: The wall may be supported by flexible
vertical bracing members designed in accordance with
this section if the deflection at design loads is
not less than one-quarter nor more than one-third of
the wall thickness.
All vertical bracing members shall be attached to
floor and roof construction for their design loads
independently of required wall anchors. Horizontal
spacing of vertical bracing member shall not exceed
one-half the unsupported height of the wall or ten
feet.
2. Special Provisions for Hollow Clav Tile Wall
Buildinas, Bearing walls of hollow clay tile may be
used to resist lateral forces under the following
conditions:
a. Walls shall meet the height to thickness ratio
required for masonry walls as set forth in Table
A1-D.
b. Where hollow clay tile walls are constructed of
more than one wythe the wythes shall be stitched
together with anchors not exceeding 24 inches on
center in each direction.
- c. The allowable shear stress in hollow clay tile
walls shall not exceed 3 psi unless justified by
i tests as specified for brick masonry walls.
3. Snecial Provisions for Unreinforced Concrete Block
Masonrv Walls. Bearing walls of unreinforced
concrete block may be used to resist lateral forces
under the following conditions:
a. Walls shall meet the height to thickness ratio
6
required in Table A1-D.
b. The allowable shear stress in unreinforced con-
crete block walls shall not exceed 5 psi unless
justified by tests as required in Section d.
below and Table No. A1-E.
4. Existina Roof, Floors. Walls, Footinas, and Wood
Framina. Existing materials including wood shear
walls utilized in the described configuration may be
used as part of the lateral load resisting system,
provided that the stresses in these materials do no
exceed the values shown in Table No. A1-E.
C. Strenathenina of Existina Materials. New materials
including wood shear walls may be utilized to strengthen
portions of the existing seismic resisting system in the
described configurations provided that the stresses do
not exceed the values shown in Table A1-F.
D. Minimum Acceptable 4ualitv of Existin4 Unreinforced
Masonrv Walls.
1. General Provisions. All unreinforced masonry walls
utilized to carry vertical loads and seismic forces
parallel and perpendicular to the wall plane shall
be tested as specified in this Section. Al1 masonry
quality shall equal or exceed the minimum standards
established herein or shall be removed and replaced
by the Building Official. The quality of mortar in
all masonry walls shall be determined by performing
in-place shear tests or by testing eight inch
diameter cores. Alternative methods of testing may
be approved by the Building Official. Nothing
shall prevent pointing with mortar of all the
masonry wall joints before the tests are first made.
Prior to any pointing, the mortar joints must be
raked and cleaned to remove loose and deteriorated
mortar. Mortar for pointing shall be type S or N
except masonry cements shall not be used. All
preparation and mortar pointing shall be done under
the continuous inspection of a Special Inspector.
At the conclusion of the inspection, the inspector
shall submit a written report to the person
responsible for the seismic analysis of the building
setting forth the result of the work inspected.
Such report shall be submitted to the Building
Official for approval as part of the structural
analysis. All testing shall be performed in
accordance with the requirements specified in this
Section by a testing agency. An accurate record of
all such tests and their location in the building
shall be recorded and these results shall be
submitted to the Building Official for approval as
part of the structural analysis.
Number and Location of Tests. The minimum number of
tests shall be two per wall or line of wall elements
resisting a common force, or 1 per 1500 square feet
of wall surface, with a minimum of eight tests in
any case. The exact test or core location shall be
determined at the building site by the person
responsible for the seismic analysis of the subject
building.
3. In-Place Shear Tests. The bed joints of the outer
wythe of the masonry shall be tested in shear by
laterally displacing a single brick relative to the
adjacent bricks in that wythe. The opposite head
joint of the brick to be tested shall be removed and
7
cleaned prior to testing. The minimum quality
mortar in 80 percent of the shear tests shall not be
less than the total of 30 psi plus the axial stress
in the wall at the point of the test. The shear
stress shall be based on the gross area of both bed
joints and shall be that at which movement of the
brick is first observed.
4. Core Tests. A minimum number of mortar test
specimens equal to the number of required cores
shall be prepared from the cores and tested as
specified herein. The mortar joint of the outer
wythe of the masonry core shall be tested in shear
by placing the circular core section in a
compression testing machine with the mortar bed
joint rotated 15 degrees from the axis of the
applied load. The mortar joint tested in shear
shall have an average ultimate stress based of 20
psi based on the gross area. The average shall be
obtained from the total number of cores made. If
test specimens cannot be made from cores taken then
the shear value shall be reported as zero.
E. Testina of Shear Bolts. One-fourth of all new shear
bolts and dowels embedded in unreinforced masonry walls
shall be tested by a Special Inspector using a torque
calibrated wrench to the following minimum torques:
1/2" diameter bolts or dowels = 40 foot-lbs
5/8" diameter bolts or dowels = 50 foot-lbs
3/4" diameter bolts or dowels = 60 foot-lbs
No bolts exceeding 3/4" shall be used. All nuts shall
be installed over malleable iron or plate washers when
bearing on wood and heavy cut washers when bearing on
steelo
F. Determination of Allowable Stresses for Desian Methods
Based on Test Results.
1. Desian Shear Values. Design seismic in-plane shear
stresses shall be substantiated by tests performed
as specified in Items 3 and 4 above.
Design stresses shall be related to test results
obtained in accordance with Table A1-G.
Intermediate values between 3 and 10 psi may be
interpolated.
2. Desian Compression and Tension Values. Compression
stresses for unreinforced masonry having a minimum
design shear value of 3 psi shall not exceed 100
psi. Design tension values for unreinforced masonry
shall not be permitted.
1
G. Five percent of the existing rod anchors utili2ed as all
or part of the required wall anchors shall be tested in
pullout by a testing laboratory approved by the Building
Official. The minimum number tested shall be four per
floor with two tests at walls with joists parallel to the
wall. The test apparatus shall be supported on the
masonry wall at a minimum distance of the wall thickness
from the anchor tested. The rod anchor shall be given a
preload of 300 lbs prior to established a datum for
recording elongation. The tension test load reported
shall be recorded at one-eighth inch relative movement of
the anchor and the adjacent masonry surface. Results of
all tests shall be reported. The report shall include
the test results as related to the wall thickness and
8
joist orientationa The allowable resistance value of the
existing anchors shall be forty percent of the average of
those tested anchors having the same wall thickness and
joist orientation.
H. Qualification tests for devices used for wall anchorage
shall be tested with the entire tension load carried on
the enlarged head at the exterior face of the wall.
Bond on the part of device between the enlarged head and
the interior wall face shall be eliminated for the
qualification tests. The resistance value assigned the
device shall be twenty percent of the average of the
ultimate loads.
4.7 INFORMATION REQUIRED ON PLANS
A. General. In addition to the seismic analysis required
elsewhere in this Section, the person responsible for
the seismic analysis of the building shall determine and
record the information required by the section on the
approved plans.
B. Construction Details. The following requirements with
appropriate construction details shall be made part of
the approved planse
1. All unreinforced masonry walls shall be anchored at
the roof level by tension bolts through the wall as
specified in Table A1-F, or by approved equivalent
at the maximum anchor spacing of six feet.
All unreinforced masonry walls shall be anchored at
all floors with tension bolts through the wall or by
-- existing rod anchors at a maximum anchor spacing of
six feet. All existing rod anchors shall be secured
to the joists to develop the required forces. The
" Building Official may require testing to verify the
adequacy of the embedded ends of existing rod
anchors. Tests when required shall conform to this
section.
When access to the exterior face of the masonry wall
is prevented by proximity of an existing building,
wall anchors conforming to Item 5 in Table A1-F inay
be used.
Alternative devices to be used in lieu of tension
bolts for masonry wall anchorage shall be tested as
specified in Item H of this Section.
2. Diaphragm chord stresses of horizontal diaphragms
shall be developed in existing materials or by
addition of new materials.
3. Where trusses and beams other than rafters or joists
are supported on masonry, columns or ledgers shall
be installed to support vertical loads of the roof
or floor members.
4._ Parapets and exterior wall appendages not capable of
~, resisting the forces specified in this section shall
be removed, stabilized or braced to insure that the
parapets and appendages remain in their original
position.
5. All deteriorated mortar joints in unreinforced
masonry walls shall be pointed with cement mortar.
Prior to any pointing, the wall surface shall have
9
loose and deteriorated mortar removed. All
preparation and pointing shall be done under the
continuous inspection of a Special Inspector. At
the conclusion of the project, the inspector shall
submit a written report to the Building Official
setting forth the portion of work inspected.
6. Repair details of any cracked or damaged
unreinforced masonry wall required to resist forces
specified in this section.
C. Existina Construction. The following existing con-
' struction information shall be made part of the approved
-- plans:
1. The type and dimensions of existing walls and the
size and spacing of floor and roof inembers.
2. The extent and type of existing wall anchorage to
floors and roof.
3. The extent and type of any parapet or other
corrections which were previously performed.
4. Accurately dimensioned floor plans and masonry wall
elevations showing dimensioned openings, piers, wall
thickness and heights.
5. The location of cracks or damaged portions of
unreinforced masonry walls requiring repairs.
6. The type of interior wall surfaces and if
reinstalling or anchoring of ceiling plaster is
necessary.
- 7. The general condition of the mortar joints and if
the joints need pointing.
10
TABLE N0. A1-A
HORIZONTAL FORCE FACTORS BASED
ON OCCUPANT LOAD
OCCUPANT LOAD
Building with an
occupant load
greater than 100
Al1 others
TABLE A1-B
I FACTOR
OCCUPANCY
CKS
0.133
0.100
FACTOR
Essential 1.5
Occupancies
All others 1.0
TABLE N0. A1-C
HORIZONTAL FORCE FACTORS "IS"
FOR P11RTS OR PORTIONS OF STRUCTURES
RATING
CLASSIEICATION IS
Essential Buildings 1.50
Buildings with an
Occupant load of
greater than 100 1.00
All others 0.75
TABLE N0. A1-D
ALLOWABLE VALUE OF HEIGHT-THICKNESS RATIO
OF UNREINFORCED MASONRY WALLS WITH MINIMUM
OUALITY MORTAR (1) (2)
BUILDINGS WITH CROSSWAI,LS AS ALL OTHER
DEFINED BUILDINGS
Walls oP
One Story Buildings 16 13
Eirst Story Wall of
Multi-Story Buildings 16 15
Walls in Top Story of
Multi-Story Buildings 14 9
All Other Walls 16 13
Notes: -
(1) Minimum quality mortar shall be determined by laboratory
testing in accordance with this section.
(2) Table A1-D is not applicable to buildings classi£ied as
essential. Such buildings shall be analyzed in accordance
with Section 806.
The wall height may be measured vertically to bracing
elements other than a floor or roof. Spacing of the
bracing elements and wall anchors shall not exceed six
feet. Bracing elements shall be detailed to minimize
the horizontal displacement of the wall by components
of vertical displacements of the floor or roof.
11
TABLE N0. A1-E
VALUES FOR EXISTING MATERIALS(11
1. , HORIZONTAL DIAPHRAGMS
a. Roofs with straight
sheathing and roofing
applied directly to the
sheathing.
b. Roofs with diagonal
sheathing and roofing
applied directly to the
sheathing.
100 lbs. per foot for
seismic shear
400 lbs. per foot for
~ seismic shear
c. Floors with straight
tongue and groove sheathing.
d. Floors with straight
sheathing and finished
wood flooring.
e. Floors with diagonal
sheathing and finished
wood flooring.
150 lbs. per foot for
seismic shear
300 lbs. per foot for
seismic shear
450 lbs, per foot for
seismic shear
f. Floors or roofs with Add 50 lbs. per foot
straight, sheathing and plaster to the allowable values for
applied to the joist or items l.a and l.c
rafters. (2)
2. SHEAR WALLS
Wood stud walls with
lath and plaster
3. PLAIN CONCRETE FOOTINGS
4. DOUGLAS FIR WOOD
5. REINFORCING STEEL
6. STRUCTURAL STEEL
100 lbs, per foot each
side for seismic shear. °
f'=1500 psi unless
otherwise shown by tests.
Allowable stress same as
No. 1 D.F. (3)
f= 18,000 lbs. per square
inch maximum. (3) -°
f = 20,000 lbs. per
square inch maximum. (3)
Notes:
(1) Material must be sound and in good condition.
(2) The wood lath and plaster must be reattached to existing
joists or rafters in a manner approved by the Department.
(3) Stresses given may be increased for combinations of loads
as specified in Section 106.
12
.
TABLE N0. A1-F
ALLOWABLE VALUES OF NEW MATERIALS USED
IN CONJUNCTION WITH EXISTING CONSTRUCTION
NEW MATERIALS OR
CONFIGURATION OF MATERIALS
1. HORIZONTAL DIAPHRAGMS
Plywood sheathing applied
directly over existing straight
sheathing with ends of plywood
sheets bearing on joists or
rafters and edges of plywood
located on center of individual
sheathing boards.
2. SHEAR WALLS
ALLOWABLE VALUES
Same as specified in
Table No. 25-J o£ the
Building Code for
blocked diaphragms.
a. Plywood sheathing applied Same as values
directly over existing wood specified in Table
studs. No value shall be given No. 25-K of the
to plywood applied over existing of the Building Code
plaster or wood sheathing. for shear walls.
b. Dry wall or plaster applied
directlyover existing wood studs.
c. Dry wall or plaster applied
to plywood sheathing over
existing wood studs.
3. SHEAR BOLTS
Shear bolts and shear dowels
embedded a minimum o£ 8 inches
into unreinforced masonry walls.
Bolt centered in a 2 1/2 inch
diameter hole with dry-pack or
non-shrink grout around cir-
cumference of bolt or dowel. (1)(3)
4. TENSION BOLTS
Tension bolts and tension dowels
extending entirely through
unreinforced masonry walls
secured with bearing plates on
far side of wall with at least
30 sq. inches of area. (2) (3)
5. WALL ANCHORS (Sec. 108 (b))
a. Bolts extending to the exterior
face of the wall with a 2 1/2 inch
' round plate under the head.
__ Install as specified for shear
bolts. Spaced not closer than 12
inches on centers. (1) (2) (3)
75 per cent of the
specified in table No.
47-I of the Building
Code.
33 1/3 percent of the
values speci£ied in
Table No. 47-I of the
Building Code.
100 percent of the
values Por plain masonry
in Table No. 24-G of the
Building Code. No values
larger than those given
for 3/4 in. dia. bolts •~
shall be used.
1200 lbs. per bolt or
dowel.
b. Bolts or dowels extending to
the exterior face of the wall
with a 2 1/2 inch round plate
under the head and drill at an
angle of 22 1/2 degrees to the
horizontal. Installed as
specified for shear bolts, (1) (2) (3)
600 lbs. per bolt.
1200 lbs. per
bolt or dowel.
13
TABLE NO. A1-F (continued)
6. INFILLED WALLS
Reinforced masonry infilled
openings in existing unrein-
forced masonry walls with keys
or dowels to match reinforcing.
7. REINFORCED MASONRY
Masonry piers and walls
reinforc~d per Chapter 24 of
the Building Code.
8. REINFORCED CONCRETE
Concrete footings, walls and
piers reinforced as specified
in Chapter 26 and designed for
tributary loads.
Same as values specified
for unreinforced masonry
walls.
Same as values specified
in Table No. 24-B of the
Building Code.
Same as values specified
in Chapter 26 of the
Building Code.
9. EXISTING FOUNDATION LOADS
Foundation loads for struc-
tures exhibiting no evidence
of settlement.
Calculated existing foun-
dation loads due to maxi-
mum dead load plus live
load may be increased 25
percent dead load, and
may be increased 50 per-
cent for dead load plus
seismic load required by
this section.
_ Notes:
(1)
(2)
(3) Bolts and dowels to be
Bolts and dowels to be
Drilling for bolts and
electric rotary drill.
for drilling holes or tested as specified
1/2 inch minimum in
dowels shall be done
Impact tools shall
tightening anchor and in Sec. 107
diameter.
with an
not be used
shear bolt
nuts.
TABLE NO. A1-G
ALLOWABLE SHEAR STRESS FOR TESTED
UNREINFORCED MASONRY WALLS
SHEAR TESTS
Eighty percent
of test results
in psi not less
Average test results
of cores in psi
Seismic in-plane
area (1)
than
30 plus axial stress
-- 40 plus axial stress
50 plus axial stress
100 plus axial stress
or more
20
27
33_
67 or more
3 psi
4 psi
5 psi
10 psi maximum
(1) Allowable shear stress may be increased by addition of 10%
of the axial stress due to the weight of the wall directly above.
14
PASSED, APPROVED, AND ADOPTED this 24th day of October 1989,
upon the following vote:
AYES: COUNCILMEMBERS: BUCK, DOPIIPIGUEZ, STARKEY, k~ASHBURN, 4!INKLER
NOES: COUNCILMEMBERS: NONE
ABSENT: COUNCILMEPIBERS: NONE
ABSTENTIONSa COUNCILP1EMBERS: NONE ~
'm Winkler, yor
City of Lake Elsinore
T~ST:
~.
Vicki L. Kasad, City Clerk
APPROVED ~$ ~O FORM AND LEGALITY:
Johri R. 'Ha'rper, ity~:ftorney
15
STATE OF CALIFORNIA )
COUNTY OF RIVERSIDE ) SS:
CITY OF LAKE ELSINORE )
I, Vicki Lynne Kasad, City Clerk of the City of Lake Elsinore,
DO ~E~~BY CERm2FV ±rat. the foregoing Resolution duly adopted by the
City Council of the City of Lake Elsinore at a regular meeting
of said Council on the 24th day of October, 1989, and that it was
so adopted by the following vote:
AYES: COUNCILMEMBERS: BUCK, DOMINGUEZ, STARKEY
WASHBURN, WINKLER
NOES: COUNCILMEMBERS: NONE
ABSENT: COUNCILMEMBERS: NONE
AEuTAIN: COUNCILMEMBERS: NONE
f
C I Ll i`` KA D, C TY CLERK
CITY OF LA E ELSINORE
(SEALj
STATE OF CALIFORNIA )
COUNTY OF RIVERSIDE ) SS:
CITY OF LAKE ELSINORE )
I, Vicki Lynne Kasad, City Clerk of the City of Lake Elsinore,
DO HEREBY CERTIFY that the above and foregoing is a full, true and
correct copy of Resolution No. 89-50 of said Council, and that the
same has not been amended or repealed.
D ED: Octcber 25, 1989
~
VICKI LYNSYE SAD, CITY CL RK
CITY,OF LAK .LSINORE
(SEAL)