Loading...
HomeMy WebLinkAboutUndergrounding Doc from Tim FlemingNavigate the Energy Division Website Navigate the CPUC Website February 12, 2000 Find a Project or Issue Area UNDERGROUNDING R.00-01-005, Order Instituting RulemakinI g (OIR) into Implementation of Assembly Bill 1149 on Undergrounding . ORDER INSTITUTING RULEMAKING INTO IMPLEMENTATION OF ASSEMBLY-BILL 1149 Download in PDF Format rndutles whMpaper 8 A61149) . Workshop Notice for Workshop on February 10 -11, 2000 - PDF o NOTICE CHANGING LOCATION OF %EtIEAAIkG. CONFERENCE AND WORKSHOP - PDF o Workshop Agenda - PDF o Costs: Generic data request to Jurisdictional Utilities - PDF rlu+anaa- Gnnnrie da+a ran,ma++n 1ur1arllr+1nna1 Il+ili+iec - PDF Sect3 w w w • ~ i 35 Tree Trimming 70s1~ 9s Where overhead wires pass through trees, safety and reliability of service demand that tree trimming be done in order that he wires may clear branches and foliage by / a reasonable distance. The minimum clearances established in Table 1, Case 13, ILL measured between line conductors and vegetation under normal conditions, shall be maintained (Also see Appendix E for tree trimming guidelines.) When a utility has actual knowledge, obtained either through normal operating practices or notification to the utility, dead, rotten and diseased trees or portions thereof, that overhang or lean toward and may fall into a span, should be removed. Communication and electric supply circuits, energized at 750 volts or less, includingiheir serne drops, should be kept clearofliimbs and foliage, in new construction and when circuits are reconstructed or repaired,.whenever practicable. When a utility has actual knowledge, obtained either through normal operating practices or notification to the utility, that any circuit energized at 750 volts or less shows strain or evidences abrasion from tree contact, the condition shall be corrected by slacking or rearranging the line, trimming the tree or placing mechanical protection on the conductor(s). EXCEPTIONS: C~_ule 35 requirements do not apply to conductors, or aerial cable that complies Z f` - th Rule 57.4-C, energized at less tip-6fi,00fPvolts, where-ttamning-or removal u . _ y his not practicable and the conductor is separated from the tree with suitable L = materials or devices to avoid conductor damage by abrasion and grounding of the circuit through the tree. *2. Rule 35 requirements do not apply where the utility has made a "good faith" c S~ r ` effort to obtain permission to trim or remove vegetation but permission was refused 'To I S 0 N /3 X41 _ or unobtainable. A "good faith" effort shall consist of current documentation of a I S VEYC'~ l/J7e7?E~l mtmmum of an attempted personal contact and a written communication, including i documentation of mailing or delivery. However, this does not preclude other action ~/J ELI S Of✓ S or actions from demonstrating "good faith". If permission to trim or remove !Jfl/JI~Lt~✓G dF its ~ /J ~ ~ vegetation is unobtainable and requirements of exception 2 are met, the utility is fr/./ T I T7 not compelled to comply with the requirements of exception 1. S~ l~T li✓~U14YVi L-'7~. control of S b S u e3 J S, he The Commission result in nonconformance a with he rules In uch cases, he utility /Ui;GES Shy A may be directed by he Commission to take prompt remedial action to come into U Y), RA"' N 1 confo*m? ce whethero not the nonconformance gives rise to penalties or is EJ~ W DC e?) A alleged to fall within permitted exceptions or phase-in requirements. I'L) C-0 .Note: Revised November 6,1992 by Resolution No. SU-15, September 20, 1996 by Decision No. 96-09-097 and January 23, 1997 by Decision No. 97-01-044. y ~QwT Rule 37 f s/CSD/US g09 ect3.htm 5ect5 Rule 57 66 Messengers and Insulated Cables 66.1 Definition (See Rules 20.3 and 21.11) 66.2 Use of Messenger Page I of 9 Where a cable is of such weight that it would not meet the safety factors of Table 4 when self-supported, attachment to stranded messenger shall be made for supporting said weight. 66.3 Material and Strength (See Rule 49.7) 66.4 Clearances Basic minimum clearances for messengers and insulated cables are specified in Rules 37 and 38, Tables 1 and 2 respectively and shall be measured to the nearest surfaces of the cable and messenger assembly, including cable rings and messenger supports. The basic clearances specified for conductors, as modified by provisions of Rule 54.4 are applicable to insulated cables. These clearances for messengers and cables are also subject to the following modifications. The clearances required for supply conductors of 0 - 750 volts shall be applied to suitably insulated cables of any voltage having a metallic sheath which is bonded and grounded as specified in Rule 57.8. A Above Ground (1) Messengers and Insulated Cables: The basic clearances specified in Rule 37, Table 1 for conductors, as modified by provisions of Rule 54.4-A, are applicable to messengers and insulated cables (See Rule 57.8). (2) Grounded and Bonded Messengers and Insulated Cables: The basic clearances specified in Rule 37, Table 1, Column D, are applicable to grounded cables having metallic sheaths, and to effectively grounded messengers (see Rule 57.8). Note: Revised January 21, 1992, by Resolution SU-10. B Above Railways and Trolley Lines (1) Which Transport Freight Cars: The clearances specified in Table 1, Case 1, Columns A, B, and D are based upon the maximum height of standard freight cars, 15 feet 1 inch from the http://www.cpuc.ca.gov/divisions/CSDIUSB/go95/Sect5.htm 2/2/00 Sects Page 2 of 9 top of rail to top of running board. These clearances shall in no case be reduced more than 5% because of temperature, wind or mechanical loading. Rule 57.4-F (2) Operated by Overhead Trolley: The clearances specified in Table 1, Case 2, Columns A and D, 26 feet and 27 feet respectively, are based upon a maximum trolley pole throw of 26 feet, the usual maximum height of a free trolley pole above the top of rails or surface of streets used by trolley cars or coaches. EXCEPTION: Messengers, and cables, which are bonded and grounded as specified in Rule 57.8, may have clearances above the rails or surface of streets used by trolley cars or coaches less than the distance specified in Table 1, Case 2, Columns A and D for trolley-throw clearance, provided the messengers and cables are not less than 4 feet above the trolley contact conductor and are encased in wood boxing or moulding with a minimum thickness of 7/8 inch (or other suitable material having the same minimum electrical insulating qualities and mechanical strength) for distances of at least 2 feet horizontally from the vertical plane through each trolley contact conductor. Note: Revised January 21, 1992, by Resolution SU-10. C Between Conductors in Cables No specified clearance is required between the individual conductors of suitably insulated cables, whether single or grouped, and therefore the clearances specified in Table 2, Cases 15, 16 and 17 do not apply between such conductors. Any such multiple-conductor group shall be treated as a single conductor in the application of other clearance requirements. D Between Cables and Messengers Cables supported by messengers are not required to be any specified distance from their supporting messengers. E Between Messengers The clearance specified in Table 2, Case 1, Column A does not apply and no clearance is required where messengers of the same electrical system branch or cross. F From Poles, Crossarms and Other Conductors http://www.cpuc.ca.gov/divisions/CSDIUSB/go95/Sect5.htxn 2/2/00 Sects Page 3 of 9 Messengers, and metal sheathed cables, which are bonded and grounded as specified in Rule 57.8 shall have clearances not less than the minimum clearances required for conductors of 0 - 750 volts with all of the following provisions being applicable: Rule 57.4-F1 (1) Attached to Surfaces of Poles and Crossarms: Such grounded messengers and cables may be attached to the surfaces of poles or crossarms at less than the clearance specified in Table 1. Column D, Cases 8 and 9. When attached to pole or crossarm at less than 15 inches from centerline of pole such grounded messenger or cable shall not be less than 4 feet vertically above or 6 feet vertically below any unprotected supply conductor except that where a guard arm (or arms) is placed above messenger and cable as specified in Rule 57.7, the clearance of 6 feet may be reduced to not less than 4 feet below unprotected conductors of 0 - 750 volts (see Figure 57-1 A). (2) Supported on Same Crossarm above 750 Volts: Such grounded messenger and cable when supported on the same crossarm with unprotected conductors in excess of 750 volts shall be placedon_the side of pole_oppositf-the unprotected conductors (see Figure 57-113). (3) Supported on Same Crossarm 0 - 750 Volts: Such grounded messenger and cable when supported on the same crossarm with unprotected conductors of 0 - 750 volts, shall be placed at not less than pin spacing (Table 2, Case 15, Column D) beyond the outermost unprotected conductor on the same side of pole (see Figure 57-1 Q. (4) Between Cable and Unprotected Conductors: The clearances between a cable and unprotected conductors shall not be held to apply between a grounded cable (and its messenger) and unprotected conductors of the same circuit on poles where unprotected conductors enter (or leave) a cable. On such poles no grounded section of messenger or cable shall be less than 15 inches from surface of pole. (5) Two or More Cables Attached to the Surface of Pole: Where two or more cables are attached to the surface of the same wood pole they. shall be placed on the same side of pole when their vertical separation is less than 8 feet but in no case shall the vertical separation be less than 1 foot. Note: Revised January 21, 1992, by Resolution SU-10. http://www.cpuc.ca.gov/divisions/CSD/USB/go95/Sect5.htm 2/2/00 Sects Page 4 of 9 Rule 57.4-F1 http://www.cpuc.ca.gov/divisions/CSD/USB/go95/Sect5.htm 2/2/00 Sects Rule 57.4-F IF D 4 Min. With Guard Arm 9 Min. Without Guard Arm R Cable Treated As In Rule 57.8 r. 15' Min. I AiI n. oil. I- P rd R ` Alternate Location If No Unprotected Conductor On Same End Of Arm. 1 Figure 57-1 Supply Cables Cables Treated As In Rule 57.8 In. http://www.cpuc.ca.gov/divisions/CSD/USB/go95/Sect5.htm See Rule 32.4A3 Page 5 of 9 2/2/00 Sects Rule 57.4-G G From Buildings and Other Structures Page 6 of 9 Messengers, and metal sheathed cables, which are bonded and grounded as specified in Rule 57.8 are not required to clear buildings and other structures any specified horizontal distance and the clearance specified in Table 1, Case 7, Column D does not apply in such instances. Such cables, and messengers, shall be installed so that they do not interfere with the free use of fire escapes, exits, etc., and should be arranged so as not to hamper or endanger workers and firefighters while performing their duties. Note: Revised January 21, 1992. by Resolution SU-10. H From Nonclimbable Street Lighting or Traffic Signal Poles or Standards Messengers and metal-sheathed cables which are bonded and grounded as specified in Rule 57.8, passing (unattached) nonclimbable street lighting and traffic signal poles or standards, including ma ttarms, brackets, and lighting fixtures may have a clearance less than the 36 inches specified in Table 1, Case 10, Column D, but shall have a clearance of not less than 15 inches, except when the conductors are mechanically protected from abrasion by materials specified in Rule 22.2. Such mechanical protections shall extend not less than 15 inches in each direction along the cable from centerline of pole, standard, attaching mastarut or fixture, whether passing above, below or alongside. The conductors shall be installed in such a manner so as not to interfere with light distribution from lighting fixtures and shall not hamper workmen changing lamps or maintaining equipment. Note: Added January 8, 1980 by Decision No. 91186 and revised March 9, 1988 by Resolution E- 3076. 66.5 Fastenings Hardware used in connection with messengers shall meet the strength requirement of Rule 49:7-C. Dead-end attachments used on messengers or reinforced cables shall have a strength not less than that of the messenger or reinforced cable. Note: Revised January 21, 1992, by Resolution SU-10. 66.6 Sectionalizing of Messengers with Insulators http://www.cpuc.ca.gov/divisions/CSDIUSB/go95/Sect5.htm 2/2/00 Sects Page 7 of 9 The grounding of an extended messenger, as specified in Rule 57.8, is not required provided such extended messenger is sectionalized as a guy by means of insulators. Rule 57.7-A1 66.7 Use of Guard Arms and Coverings Any guard arm which is required to be installed by the provisions of Rule 57.4-F shall be at least 4 feet in length (Rule 20.9-D) and parallel to and not more than 4 inches above the top of the cable or messenger. In lieu of the guard arm, suitable protective covering (Rule 22.2) at least 4 feet in length may be placed around the cable and messenger. Double euard arms shall be used where such a messenger or cable is dead ended on or wrapped around a wood pole, at a vertical separation of less than 6 feet below unprotected supply conductors of other circuits of 750 volts or less. Portions of cables which take the form of a riser or a grounded lateral or vertical run shall be covered as specified in Rule 54.6-E for risers. Note: Revised January 21, 1992, by Resolution SU-10. 66.8 Bonding and Grounding The provisions of Rules 57.4, 57.6 and 57.7 for grounded cables, and grounded messengers are applicable only to cables having metallic sheaths, and to messengers, which are effectively grounded at both ends of each run and at intermediate points not exceeding 800 feet apart. Where such a metal sheathed cable is supported on a messenger, each section of cable between splices shall be permanently bonded to the messenger at not less than two locations. Cables not bonded and grounded as specified above shall conform to the requirements of unprotected supply conductors with the modifications provided in the several parts of Rule 57. 66.9 Sags The sags of messengers which support cables shall be such that under the maximum loading conditions the tensions in the messengers shall not exceed the safe working stresses specified in Rule 49.7-B. http://www.cpuc.ca.gov/divisions/CSD/USB/go95/Sect5.htm 2/2/00 Sect5 67 Miscellaneous Equipment Page x of 9 67.1 Enclosed Equipment (Transformers, Capacitors, Regulators, etc.) A Position on Pole (1) Multiple Units: Where more than one unit is installed on a pole, they shall be placed on the same side of the pole. http://www.cpuc.ca.gov/divisions/CSD/USB/go95/Sect5.htm 2/2/00